Product Data Sheet Tracer UC400 Programmable Controller Ordering Number: BMUC400 AAA0100011. TheTracer UC400 controller is a multi-purpose, programmable, wireless sensor support field- or factory-installed device is designed to control the following equipment: Single- and dual-duct variable-air-volume (VAV) units Fan coils Unit ventilators Blower coils Water-source heat pumps (WSHP). Small air handlers Features and Benefits Feature Benefit bacnet MS/TP An open standard building automation communications protocol which enables connections to other BAS systems and controllers Configurable and fully programmable Factory programs available through quick configuration for lowest setup time Programmable for flexibility to meet unique sequence or hardware needs Total of 23 I/O points built in Meets most terminal unit needs with extra built-in I/O available to network or additional programming on controller Expandable to 55 points Flexibility to meet additional equipment needs Data logging 25,000 samples Easier investigation of equipment, zone, or building problems Factory and field mounting options Options to best meet job schedule and bidding process Removable connectors.

BACnet MS/TP An open standard building automation communications protocol which enables connections to other BAS systems and controllers Configurable and fully programmable • Factory programs available through quick configuration for lowest setup time • Programmable for flexibility to meet unique sequence or hardware needs

Tags:

  Bacnet, Bacnet ms tp

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Product Data Sheet

1 Product Data Sheet Tracer UC400 Programmable Controller Ordering Number: BMUC400 AAA0100011. TheTracer UC400 controller is a multi-purpose, programmable, wireless sensor support field- or factory-installed device is designed to control the following equipment: Single- and dual-duct variable-air-volume (VAV) units Fan coils Unit ventilators Blower coils Water-source heat pumps (WSHP). Small air handlers Features and Benefits Feature Benefit bacnet MS/TP An open standard building automation communications protocol which enables connections to other BAS systems and controllers Configurable and fully programmable Factory programs available through quick configuration for lowest setup time Programmable for flexibility to meet unique sequence or hardware needs Total of 23 I/O points built in Meets most terminal unit needs with extra built-in I/O available to network or additional programming on controller Expandable to 55 points Flexibility to meet additional equipment needs Data logging 25,000 samples Easier investigation of equipment, zone, or building problems Factory and field mounting options Options to best meet job schedule and bidding process Removable connectors.

2 DIN rail mounting, Ease of installation and service multiple service tool connections Compatible with Trane Wireless Comm Provides wireless communication between Trane bacnet unit and system controllers and zone sensors. This allows faster, easier, lower-risk installation and life-cycle savings due to future space re-configuration, upgrades, and expansions. June 2013 BAS-PRC033-EN. Controller Specifications and Agency Compliance Storage Temperature: -48 F to 203 F (-55 C to 95 C). Relative humidity: Between 5% to 95% (non-condensing). Operating Temperature: -40 F to 158 F (-40 C to 70 C). Humidity: Between 5% to 95% (non-condensing). Vac (24 Vac, 15% nominal) 50 60 Hz 24 VA. Power: (24 VA plus binary output loads for a maximum of 12 VA for each binary output). Mounting weight of controller: Mounting surface must support.

3 80 lb. (.364 kg). Environmental rating (enclosure): NEMA 1. Altitude: 6,500 ft maximum (1,981 m). Installation: UL 840: Category 3. Pollution UL 840: Degree 2. Wiring/Transformer 16 AWG (recommended) copper wire UL Listed, Class 2 power transformer Vac (24 Vac, 15% nominal). The transformer must be sized to provide adequate power to the UC400 controller (12 VA) and outputs (maximum 12 VA per binary output). Agency Compliance UL-864/UUKL listed (when installed and programmed in accordance with the Engineered Smoke Control System Application Guide, BAS-APG019-EN). UL916 PAZX- Open Energy Management Equipment UL94-5V Flammability CE Marked FCC Part 15, Subpart B, Class B Limit AS/NZS CISPR 22:2006. VCCI V-3 ICES-003, Issue 4:2004. Communications bacnet MS/TP, supports bacnet protocol ASHRAE 135-2004 and meets bacnet Testing Laboratory (BTL) as an Application Specific Controller (ASC).

4 Profile device Controller dimensions in. (55 mm). in. ( mm). in. (44 mm). 35 mm DIN Rail in. Mount ( mm). Important: Slotted release clip shown if removing or repositioning the controller, the user must remove terminal connectors before proceeding. 2 BAS-PRC033-EN, 10 Jun 2013. Device Connections Table 1. Device connections Connection Quantity Types Range Notes Temperature 10 k thermistor *Analog input 5 Setpoint 0 to 1,000 . (AI1 to AI5). Resistive 200 to 20 k Typically used for fan speed switch. Linear 0 20 mA. Linear 0 10 Vdc These inputs may be configured to be thermistor inputs, 0 10. * Refer to analog input connection for Vdc inputs, or 4 20 mA inputs. Universal input Resistive 2 ranges and types above (UI1 and UI2). Binary Solid state open collector Minimum dwell time is 25 milliseconds (ms) ON and 25.

5 Pulse Solid state open collector milliseconds OFF. The UC400 controller provides the 24 Vac that is required to Binary input(a). 3 24 Vac detect drive the binary inputs when using the recommended (BI1 to BI3). connections. A @24 Vac pilot duty (For further power ratings, refer to Power needs to be wired to the binary output. All outputs are Binary output(a). (BO1 to BO3). 3 Relay the Tracer UC400 Installation, isolated from each other and from ground or power. Ranges Operation, and Maintenance Manual given are per contact. [BAS-SVX20]). A max @24-277 Vac, resistive and pilot duty Use for modulating TRIAC. User determines whether closing Binary output(a) (For further power ratings, refer to high side (providing voltage to the grounded load) or low side 6 TRIAC. (BO4 to BO9) the Tracer UC400 Installation, (providing ground to the power load).)

6 Ranges given are per Operation, and Maintenance Manual contact and power comes from TRIAC SUPPLY circuit. [BAS-SVX20]). Linear output 0 20 mA. Analog output/binary input Each termination must be configured as either an analog output 2 Linear output 0 10 Vdc (AO1/BI4 and or binary input. AO2/BI5). Binary input Dry contact Pressure inputs Pressure inputs supplied with 5 volts of power. Designed for 2 3-wire 0 5 in H2O. (PI1 and PI2) Kavlico pressure transducers. Overall Point Total 23. (a) Binary Inputs, Binary Outputs, and TRIACs: For safety precautions, do not mix Class 1 and Class 2 voltages in an enclosure or on a controller without a physical barrier between these units. BAS-PRC033-EN, 10 Jun 2013 3. Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts.

7 For more information, visit Trane has a policy of continuous Product and Product data improvement and reserves the right to change design and specifications without notice. 2012 Trane. All rights reserved. We are committed to using environmentally BAS-PRC033-EN 10 Jun 2013 conscious print practices that reduce waste. Supersedes BAS-PRC033-EN 01 Nov 2012.