Quick Start Guide00825-0200-4840, Rev BCAugust 2019 Rosemount 3107 Level and 3108 FlowTransmittersUltrasonicContentsAbout this of Rosemount 3107 and before you the Start GuideAugust 20192 Rosemount Ultrasonic 3107 Level and 3108 Flow Transmitters1 About this guideThis installation guide provides basic guidelines for the Rosemount 3107 Level Transmitter and Rosemount 3108 Flow Transmitter. It does notprovide instructions for detailed configuration, diagnostics, maintenance,service, troubleshooting, or installations. Refer to the Rosemount 3107 and3108 Reference Manual for more instructions. Manuals are availableelectronically on WARNINGF ailure to follow these installation guidelines could result in death orserious injury.

Quick Start Guide 00825-0200-4840, Rev BB July 2016 Rosemount Ultrasonic 3107 Level and 3108 Flow Transmitters

Tags:

  Guide, Ultrasonic, Flows, Rosemount, Quick, Start, Quick start guide, 7301, Rosemount ultrasonic 3107

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Quick Start Guide: Rosemount Ultrasonic 3107 …

1 Quick Start Guide00825-0200-4840, Rev BCAugust 2019 Rosemount 3107 Level and 3108 FlowTransmittersUltrasonicContentsAbout this of Rosemount 3107 and before you the Start GuideAugust 20192 Rosemount Ultrasonic 3107 Level and 3108 Flow Transmitters1 About this guideThis installation guide provides basic guidelines for the Rosemount 3107 Level Transmitter and Rosemount 3108 Flow Transmitter. It does notprovide instructions for detailed configuration, diagnostics, maintenance,service, troubleshooting, or installations. Refer to the Rosemount 3107 and3108 Reference Manual for more instructions. Manuals are availableelectronically on WARNINGF ailure to follow these installation guidelines could result in death orserious injury.

2 The Rosemount 3107 and Rosemount 3108 are Ultrasonic must be installed, connected, commissioned, operated, andmaintained by suitably qualified personnel only, observing any nationaland local requirements that may apply. Use the equipment only as specified. Failure to do so may impair theprotection provided by the could result in death or serious injury. Installation of the transmitters in a hazardous environment must be inaccordance with the appropriate local, national, and internationalstandards, codes, and practices. Please review the Product Certificationssection for any restrictions associated with a safe installation.

3 Before connecting a handheld communicator in an explosiveatmosphere, ensure the instruments are installed in accordance withintrinsically safe or non-incendive field wiring practices. Verify that the operating atmosphere of the transmitter is consistentwith the appropriate hazardous locations surface may be hot. Care must be taken to avoid possible leaks could result in death or serious injury. Install and tighten process connectors before applying pressure. Do not attempt to loosen or remove process connectors while thetransmitter is in shock could cause death or serious injury. Ensure that the transmitter is not powered when making connections.

4 If the liquid level switch is installed in a high voltage environment and afault condition or installation error occurs, high voltage may be presenton leads and 2019 Quick Start GuideQuick Start Guide3 WARNINGP hysical accessUnauthorized personnel may potentially cause significant damage to and/ormisconfiguration of end users equipment. This could be intentional orunintentional and needs to be protected security is an important part of any security program andfundamental to protecting your system. Restrict physical access byunauthorized personnel to protect end users assets. This is true for allsystems used within the Start GuideAugust 20194 Rosemount Ultrasonic 3107 Level and 3108 Flow Transmitters2 Overview of Rosemount 3107 and 3108 The Rosemount 3107 and 3108 are sealed 4 20 mA loop-powered liquidlevel transmitters, specifically designed for use in waste water and effluenttreatment plant on aqueous rugged UPVC transmitters are certified Intrinsically Safe for use inZone 0 areas, and factory fitted with up to 165 ft.

5 (50 m) of two-core cablefor simple low cost installation in sumps, wet-wells and over open channelflow transmitter may be mounted in a hazardous area if powered from aprotected power supply. They can be connected directly to a plant controlsystem, or used with a Rosemount 3490 Series Control Unit forprogrammable control of operationEach transmitter is designed to be mounted above a liquid, and usesultrasonic pulses to continuously measure the distance to the liquid microprocessor-controlled electronics calculates distance to the liquidlevel from the time delay between the transmitting and receiving of programmed with the bottom reference of the application usuallythe bottom of a tank the transmitter will calculate the liquid depth (level),and output the level (Figure 2-1)

6 As a 4 20 mA signal and a digital HART Rosemount 3107 and 3108 can also calculate contents (volume) oropen channel flow, and then output the result as a 4 20 mA signal and adigital HART is achieved by remote communication using 2019 Quick Start GuideQuick Start Guide5 Figure 2-1: Typical ApplicationA. Rosemount 3108 Flow TransmitterB. Rosemount 3490 Series Control UnitC. 4 20 mA signal outputD. RelayE. PumpF. Transmitter Bottom ReferenceG. 4 20 mA and HART signal inputComponents of the transmitterThe transmitter has a housing containing advanced electronics to generateultrasonic pulses, process the resultant signals, and provide a 4 20 mA andHART is a factory-fitted cable for the signal output and connecting anexternal power supply.

7 The Rosemount 3108 has a factory-fitted remotetemperature Start GuideAugust 20196 Rosemount Ultrasonic 3107 Level and 3108 Flow TransmittersFigure 2-2: Transmitter ComponentsEADDCBA. Mounting bracketB. Two-core cableC. 1-in. mounting threadD. UPVC wetted partsE. Remote temperature sensor ( Rosemount 3108 only)August 2019 Quick Start GuideQuick Start Guide73 Considerations before you installInstall the transmitter where it is protected from ultraviolet radiation toprevent long-term degradation of the plastics used in its construction ( from direct sunlight).NoteSee also Product Certifications for special conditions for safe Installation must be carried out by suitably trained personnel inaccordance with the applicable code of practice.

8 If the equipment is likely to come into contact with aggressivesubstances, it is the responsibility of the user to take suitable precautionsthat prevent it from being adversely affected, thus ensuring that the typeof protection is not compromised. Aggressive substances are acidic liquids or gases that may attack metalsor solvents that may affect polymeric materials. Suitable precautions are regular checks as part of routine inspections, orestablishing, from the material's data sheet, that it is resistant to specificchemicals. The equipment should only be cleaned with a damp cloth; do not usesolvents. The transmitter is double insulated, and therefore protective earthing isnot required.

9 However, the cable screen should be connected (see Figure5-1). Note that if the equipment is used in a manner not specified by themanufacturer, the protection afforded by the equipment may beimpaired. This transmitter is classified Type A in accordance with the EuropeanEMC directive 2004/108/EC. To ensure electro-magnetic compatibility,in any member state, it should not be installed in a residential is not advisable to mount the transmitter in close proximity to a source ofelectrical noise such as a variable-speed drive, or other high-poweredelectrical Rosemount 3107 and 3108 Ultrasonic transmitters are Intrinsically Safe(IS) approved for hazardous area Start GuideAugust 20198 Rosemount Ultrasonic 3107 Level and 3108 Flow Transmitters The Rosemount 3107 is designed for open or closed tank installation.

10 It isweatherproof and protected against the ingress of dust The Rosemount 3108 is designed for open channel flow measurement. Itis weatherproof and protected against the ingress of dust Avoid installing the Rosemount 3107 and 3108 transmitters near heatsourcesFigure 3-1: Environmental ConsiderationsOKOKOKA ugust 2019 Quick Start GuideQuick Start Guide94 Installation Mount the transmitter above the liquid using the 1-in. threadedconnection provided, but no closer than in. (0,35 m) to the transmitter does not detect any liquid surface closer than 12 in. (0,3m) to the transmitter face. The transmitter should be mounted vertically to ensure a good echofrom the liquid surface.