Transcription of Rosemount 214C Sensor - Emerson Electric
1 Quick Start Guide00825-0400-2654, Rev BCMarch 2019 Rosemount 214c SensorSafety MessagesNOTICEThis guide provides basic guidelines for Rosemount 214c Sensor the Sensor was orderedassembled to a temperature thermowell or transmitter, see the appropriate productliterature forinformation on configuration and hazardous locations can arise when the sensors and the transmitters to which they are assembled arecertified to compatible, but each has different approvals. Be aware of the following situations: If an approved 214c Sensor is ordered with a housing, a transmitter enclosed in that housingmay have a different approval rating.
2 Refer to the transmitter IS certificate if applicable. If a Sensor and transmitter have different certifications, or if either has more certifications than theother, installation must comply with the most restrictive requirements required by eithercomponent. This is especially (but not exclusively) relevant when combination approvals areordered on either the Sensor or transmitter. Review certifications on both the Sensor andtransmitter for installation requirements and ensure installation of the Sensor /transmitterassembly complies with a single certification that is shared by both of these components and thatmeets the requirements of the application.
3 WARNINGE xplosionExplosions could result in death or serious of Sensor in an explosive environment must be in accordance with appropriate local,national, and international standards, codes, and entriesUnless marked, the conduit/cable entries in the transmitter housing use a 14 NPT thread marked M20 are M20 thread form. On devices with multiple conduit entries, allentries will have the same thread form. Only use plugs, adapters, glands, or conduit with acompatible thread form when closing these installing in a hazardous location, use only appropriately listed or Ex certified plugs, glands,or adapters in cable/conduit use plugs, adapters, glands, or conduit with a compatible thread form when closing diagram for diagram for of Start GuideMarch 20192 Rosemount 214C1 Wiring diagram for RTDsFigure 1-1.
4 RTD Lead Wire Configuration per IEC 60751 Single element, 3-wireSingle element, 4-wireDual element, 3-wireRedRedWhite White Red Red White Red Red WhiteBlackBlackYellow NoteTo configure a single element, 4-wire RTD as a 3-wire system, connect onlyone white lead. Insulate or terminate the unused white lead in a manner thatprevents shorting to the ground. To configure a single element, 4-wire RTDas a 2-wire system, connect matching colored wires first and then connectthe paired wires to the 2019 Quick Start GuideQuick Start Guide32 Wiring diagram for thermocouplesFigure 2-1.
5 Thermocouple Lead Wire ConfigurationSingle thermocouple, 2-wireDual thermocouple, 4-wire( )( + )( + )( + )( )( ) IEC 60584 thermocouple colorsASTM E- 230 thermocouple colorsTypePOS (+)NEG (-)POS (+)NEG (-)JBlackWhiteWhiteRedKGreenWhiteYellowR edTBrownWhiteBlueRedNoteDual thermocouple sensors are shipped with one pair of the wires shrinkwrapped Start GuideMarch 20194 Rosemount 214C3 Product certificationsRev Directive informationA copy of the EU Declaration of Conformity can be found at the end of theQuick Start Guide.
6 The most recent revision of the EU Declaration ofConformity can be found at Location CertificationThe Rosemount 214c has been examined and tested to determine that thedesign meets the basic electrical, mechanical, and fire protectionrequirements by a nationally recognized test laboratory (NRTL) as accreditedby the Federal Occupational Safety and Health Administration (OSHA).North AmericaThe US National Electrical Code (NEC) and the Canadian Electrical Code(CEC) permit the use of Division marked equipment in Zones and Zonemarked equipment in Divisions.
7 The markings must be suitable for the areaclassification, gas, and temperature class. This information is clearly definedin the respective USA Explosionproof (XP) and Dust-Ignitionproof (DIP)Certificate70044744 StandardsFM 3600:2011, FM 3615:2006, UL 50E:2007, UL61010-1:2010, ANSI/ISA 60529:2004 MarkingsXP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP E, F, G; CL III; T6(-50 C Ta +80 C), T5 (-50 C Ta +95 C); Seal notrequired; installed per Rosemount drawing 00214-1030; Type4X and IP 66/67; Vmax 35 VDC, 750 mWmaxSpecial Conditions for Safe Use (X):1.
8 Flameproof joints are not intended for Cable entries must be used which maintain the ingress protection ofthe enclosure. Unused cable entries must be filled with suitableblanking USA Division 2 (NI)Certificate70044744 March 2019 Quick Start GuideQuick Start Guide5 StandardsFM 3600:2011, FM 3611:2004, UL 50E:2007, UL61010-1:2010, ANSI/ISA 60529:2004 MarkingsNI CL I, DIV 2, GP A, B, C, D; T6 (-50 C Ta +80 C), T5 (-50 C Ta +95 C); installed per Rosemount drawing 00214-1030;Type 4X and IP 66/67; Vmax 35 VDC, 750 Canada Explosionproof (XP) and Dust-Ignitionproof (DIP)Certificate70044744 StandardsCAN/CSA No.
9 0:2010, CAN/CSA No. 25-1966 (R2000),CAN/CSA No. 30-M1986 (R2012), CAN/CSA (R2011), CAN/CSA No. 61010-1:2012 MarkingsXP CL I, DIV 1, GP B*, C, D; DIP CL II, DIV 1, GP E, F, G; CL III; T6(-50 C Ta +80 C), T5 (-50 C Ta +95 C); Seal notrequired; installed per Rosemount drawing 00214-1030; Type4X and IP 66/67; Vmax 35 VDC, 750 mWmaxSpecial Conditions for Safe Use (X):1. Flameproof joints are not intended for Cable entries must be used which maintain the ingress protection ofthe enclosure.
10 Unused cable entries must be filled with suitableblanking Canada Division 2 Certificate70044744 StandardsCAN/CSA No. 0:2010, CAN/CSA No. 94-M1991(R2011), CAN/CSA No. 213-M1987 (R2013), CAN/CSA 61010-1:2012 MarkingsCL I, DIV 2, GP A, B, C, D; T6; ( 50 C Ta +80 C), T5 ( 50 C Ta +95 C); installed per Rosemount drawing 00214-1030;Type 4X and IP 66/67; Vmax 35 VDC, 750 mWmax Spring loaded indicator has reduced ingress and dust ratings. Spring loadedsensors must be installed in a thermowell to maintain dust and ingressratings.