Quick Start Guide00825-0400-2654, Rev BCMarch 2019 Rosemount 214C SensorSafety MessagesNOTICEThis guide provides basic guidelines for Rosemount 214C Sensor the Sensor was orderedassembled to a temperature thermowell or transmitter, see the appropriate productliterature forinformation on configuration and hazardous locations can arise when the sensors and the transmitters to which they are assembled arecertified to compatible, but each has different approvals. Be aware of the following situations: If an approved 214C Sensor is ordered with a housing, a transmitter enclosed in that housingmay have a different approval rating. Refer to the transmitter IS certificate if applicable. If a Sensor and transmitter have different certifications, or if either has more certifications than theother, installation must comply with the most restrictive requirements required by eithercomponent.

Markings II 2 G Ex db IIC T6…T1 Gb, (-60 °C ≤ T. a. ≤ +80 °C) Special Conditions for Safe Use (X): 1. Flameproof joints are not intended for repair. 2. Non-Standard Paint options may cause risk from electrostatic discharge. Avoid installations that cause electrostatic build-up on. i. a

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Rosemount 214C Sensor - Emerson Electric

1 Quick Start Guide00825-0400-2654, Rev BCMarch 2019 Rosemount 214C SensorSafety MessagesNOTICEThis guide provides basic guidelines for Rosemount 214C Sensor the Sensor was orderedassembled to a temperature thermowell or transmitter, see the appropriate productliterature forinformation on configuration and hazardous locations can arise when the sensors and the transmitters to which they are assembled arecertified to compatible, but each has different approvals. Be aware of the following situations: If an approved 214C Sensor is ordered with a housing, a transmitter enclosed in that housingmay have a different approval rating. Refer to the transmitter IS certificate if applicable. If a Sensor and transmitter have different certifications, or if either has more certifications than theother, installation must comply with the most restrictive requirements required by eithercomponent.

2 This is especially (but not exclusively) relevant when combination approvals areordered on either the Sensor or transmitter. Review certifications on both the Sensor andtransmitter for installation requirements and ensure installation of the Sensor /transmitterassembly complies with a single certification that is shared by both of these components and thatmeets the requirements of the application. WARNINGE xplosionExplosions could result in death or serious of Sensor in an explosive environment must be in accordance with appropriate local,national, and international standards, codes, and entriesUnless marked, the conduit/cable entries in the transmitter housing use a 14 NPT thread marked M20 are M20 thread form. On devices with multiple conduit entries, allentries will have the same thread form.

3 Only use plugs, adapters, glands, or conduit with acompatible thread form when closing these installing in a hazardous location, use only appropriately listed or Ex certified plugs, glands,or adapters in cable/conduit use plugs, adapters, glands, or conduit with a compatible thread form when closing diagram for diagram for of Start GuideMarch 20192 Rosemount 214C1 Wiring diagram for RTDsFigure 1-1: RTD Lead Wire Configuration per IEC 60751 Single element, 3-wireSingle element, 4-wireDual element, 3-wireRedRedWhite White Red Red White Red Red WhiteBlackBlackYellow NoteTo configure a single element, 4-wire RTD as a 3-wire system, connect onlyone white lead. Insulate or terminate the unused white lead in a manner thatprevents shorting to the ground. To configure a single element, 4-wire RTDas a 2-wire system, connect matching colored wires first and then connectthe paired wires to the 2019 Quick Start GuideQuick Start Guide32 Wiring diagram for thermocouplesFigure 2-1: Thermocouple Lead Wire ConfigurationSingle thermocouple, 2-wireDual thermocouple, 4-wire( )( + )( + )( + )( )( ) IEC 60584 thermocouple colorsASTM E- 230 thermocouple colorsTypePOS (+)NEG (-)POS (+)NEG (-)JBlackWhiteWhiteRedKGreenWhiteYellowR edTBrownWhiteBlueRedNoteDual thermocouple sensors are shipped with one pair of the wires shrinkwrapped Start GuideMarch 20194 Rosemount 214C3 Product certificationsRev Directive informationA copy of the EU Declaration of Conformity can be found at the end of theQuick Start Guide.

4 The most recent revision of the EU Declaration ofConformity can be found at Location CertificationThe Rosemount 214C has been examined and tested to determine that thedesign meets the basic electrical, mechanical, and fire protectionrequirements by a nationally recognized test laboratory (NRTL) as accreditedby the Federal Occupational Safety and Health Administration (OSHA).North AmericaThe US National Electrical Code (NEC) and the Canadian Electrical Code(CEC) permit the use of Division marked equipment in Zones and Zonemarked equipment in Divisions. The markings must be suitable for the areaclassification, gas, and temperature class. This information is clearly definedin the respective USA Explosionproof (XP) and Dust-Ignitionproof (DIP)Certificate70044744 StandardsFM 3600:2011, FM 3615:2006, UL 50E:2007, UL61010-1:2010, ANSI/ISA 60529:2004 MarkingsXP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP E, F, G; CL III; T6(-50 C Ta +80 C), T5 (-50 C Ta +95 C); Seal notrequired; installed per Rosemount drawing 00214-1030; Type4X and IP 66/67; Vmax 35 VDC, 750 mWmaxSpecial Conditions for Safe Use (X):1.

5 Flameproof joints are not intended for Cable entries must be used which maintain the ingress protection ofthe enclosure. Unused cable entries must be filled with suitableblanking USA Division 2 (NI)Certificate70044744 March 2019 Quick Start GuideQuick Start Guide5 StandardsFM 3600:2011, FM 3611:2004, UL 50E:2007, UL61010-1:2010, ANSI/ISA 60529:2004 MarkingsNI CL I, DIV 2, GP A, B, C, D; T6 (-50 C Ta +80 C), T5 (-50 C Ta +95 C); installed per Rosemount drawing 00214-1030;Type 4X and IP 66/67; Vmax 35 VDC, 750 Canada Explosionproof (XP) and Dust-Ignitionproof (DIP)Certificate70044744 StandardsCAN/CSA No. 0:2010, CAN/CSA No. 25-1966 (R2000),CAN/CSA No. 30-M1986 (R2012), CAN/CSA (R2011), CAN/CSA No. 61010-1:2012 MarkingsXP CL I, DIV 1, GP B*, C, D; DIP CL II, DIV 1, GP E, F, G; CL III; T6(-50 C Ta +80 C), T5 (-50 C Ta +95 C); Seal notrequired; installed per Rosemount drawing 00214-1030; Type4X and IP 66/67; Vmax 35 VDC, 750 mWmaxSpecial Conditions for Safe Use (X):1.

6 Flameproof joints are not intended for Cable entries must be used which maintain the ingress protection ofthe enclosure. Unused cable entries must be filled with suitableblanking Canada Division 2 Certificate70044744 StandardsCAN/CSA No. 0:2010, CAN/CSA No. 94-M1991(R2011), CAN/CSA No. 213-M1987 (R2013), CAN/CSA 61010-1:2012 MarkingsCL I, DIV 2, GP A, B, C, D; T6; ( 50 C Ta +80 C), T5 ( 50 C Ta +95 C); installed per Rosemount drawing 00214-1030;Type 4X and IP 66/67; Vmax 35 VDC, 750 mWmax Spring loaded indicator has reduced ingress and dust ratings. Spring loadedsensors must be installed in a thermowell to maintain dust and ingressratings. Un-painted aluminum enclosures are Type 4 rated. *Assembly is notCanada Explosionproof (E6) rated to Group B if a 0079 connection head ATEX FlameproofCertificateDEMKO 16 ATEX 1677 XQuick Start GuideMarch 20196 Rosemount 214 CStandardsEN 60079-0:2012+A11 2013, EN 60079-1:2014 Markings II 2 G Ex db IIC Gb T6(-50 C Ta +80 C), T5(-50 C Ta +95 C), (-50 C Ta +100 C) Vmax = 45 Vdc, Pmax= 750 mWInstallation Instructions:1.

7 Use field wiring suitable for both the minimum and maximum These devices are provided without cable glands/conduit sealingdevices/blanking elements. Proper selection of suitable cable glands/conduit sealing/blanking elements should occur in the Unused apertures shall be closed with suitable blanking The enclosures may be provided with up to three 14 NPT, 14 NPT, or M20 x entries, with location of the entries specified in theinstallation instructions Conditions for Safe Use (X):1. Refer to certificate for details regarding process and ambienttemperature When the Rosemount 214C Sensor is provided with an enclosurewith a display cover, the maximum ambient shall be 95 The non-metallic label on the device may store an electrostaticcharge and become a source of ignition in Group III shall be taken to reduce electrostatic build-up.

8 For example, thenon-metallic label may be rubbed with a damp The display covers were impacted at 4 J according to a low risk ofmechanical danger. Guard the display covers against impact energiesgreater than 4 Flameproof joints are not intended for The stand-alone Rosemount 214C sensors without an enclosuremust be assembled to a suitable Ex certified enclosure of a volume nogreater than L to maintain the types of protection db and tb .7. The spring loaded sensors and DIN sensors must be installed in athermowell to maintain IP6X Contact indicating sensors do not meet requirements for protectiontype tb and therefore are not tb 2019 Quick Start GuideQuick Start ATEX Intrinsic SafetyCertificateBaseefa16 ATEX0101 XStandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012 Markings II 1 G Ex ia IIC T5/T6 Ga (SEE CERTIFICATE FOR SCHEDULE)Thermocouples; Pi = 500 mWT6 60 C Ta +70 CRTDs; Pi = 192 mWT6 60 C Ta +70 CRTDs; Pi = 290 mWT6 60 C Ta +60 CT5 60 C Ta +70 CSpecial Conditions for Safe Use (X):1.

9 The equipment must be installed in an enclosure which affords it adegree of ingress protection of at least ATEX Zone 2 CertificateBAS00 ATEX3145 StandardsEN 60079-0:2012+A11:2013, EN 60079-15:2010 Markings II 3 G Ex nA IIC T5 Gc T5(-40 C Ta 70 C) ATEX Dust IgnitionproofCertificateDEMKO 16 ATEX 1677 XStandardsEN 60079-0:2012+A11 2013, EN 60079-31:2014 Markings II 2 D Ex tb IIIC T130 C Db(-50 C Ta +100 C)Vmax = 45 Vdc, Pmax = 750 mWInstallation Instructions:1. Use field wiring suitable for both the minimum and maximum These devices are provided without cable glands/conduit sealingdevices/blanking elements. Proper selection of suitable cable glands/conduit sealing/blanking elements should occur in the Unused apertures shall be closed with suitable blanking The enclosures may be provided with up to three 14 NPT, 14 NPT, or M20 x entries, with location of the entries specified in theinstallation instructions Start GuideMarch 20198 Rosemount 214 CSpecial Conditions for Safe Use (X):1.

10 Refer to certificate for details regarding process and ambienttemperature When the 214C Sensor is provided with an enclosure with a displaycover, the maximum ambient shall be 95 The non-metallic label on the device may store an electrostaticcharge and become a source of ignition in Group III shall be taken to reduce electrostatic build-up. For example, thenon-metallic label may be rubbed with a damp The display covers were impacted at 4 J according to a low risk ofmechanical danger. Guard the display covers against impact energiesgreater than 4 Flameproof joints are not intended for The stand-alone Rosemount 214C sensors without an enclosuremust be assembled to a suitable Ex certified enclosure of a volume nogreater than L to maintain the types of protection db and tb .7. The spring loaded sensors and DIN sensors must be installed in athermowell to maintain IP6X Contact indicating sensors do not meet requirements for protectiontype tb and therefore are not tb IECEx FlameproofCertificateIECEx UL 60079-0:2011, IEC 60079-1:2014 MarkingsEx db IIC Gb T6(-50 C Ta +80 C), T5(-50 C Ta +95 C), (-50 C Ta +100 C) Vmax = 45 Vdc, Pmax = 750mW Installation Instructions:1.