Quick Start Guide00825-0200-4774, Rev BDFebruary 2017 Rosemount 3051 Pressure Transmitter and Rosemount 3051cf series Flowmeterswith FOUNDATION Fieldbus ProtocolNoteBefore installing the Transmitter , confirm the correct device driver is loaded on the host systems. See System readiness on page 20172 Quick Start GuideNOTICEThis guide provides basic guidelines for Rosemount 3051 Transmitters. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or intrinsically safe ( ) installations. Refer to the Rosemount 3051 FOUNDATION Fieldbus Reference Manual for more instruction.

Quick Start Guide 00825-0200-4774, Rev BD February 2017 Rosemount3051 Pressure Transmitter and Rosemount 3051CF Series Flowmeters with FOUNDATION™ Fieldbus Protocol Note Before installing the transmitter, confirm the correct device driver is loaded on the host systems.

Tags:

  Series, Pressure, Transmitter, Rosemount, 3051, 3051cf, Rosemount 3051 pressure transmitter and rosemount, 3051 pressure transmitter and rosemount 3051cf series

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Rosemount 3051 Pressure Transmitter and Rosemount …

1 Quick Start Guide00825-0200-4774, Rev BDFebruary 2017 Rosemount 3051 Pressure Transmitter and Rosemount 3051cf series Flowmeterswith FOUNDATION Fieldbus ProtocolNoteBefore installing the Transmitter , confirm the correct device driver is loaded on the host systems. See System readiness on page 20172 Quick Start GuideNOTICEThis guide provides basic guidelines for Rosemount 3051 Transmitters. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or intrinsically safe ( ) installations. Refer to the Rosemount 3051 FOUNDATION Fieldbus Reference Manual for more instruction.

2 This manual is also available electronically on could result in death or serious of this Transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Please review the approvals section of the Rosemount 3051 FOUNDATION Fieldbus Reference Manual for any restrictions associated with a safe installation. In an Explosion-proof/Flameproof installation, do not remove the Transmitter covers when power is applied to the unit. Process leaks may cause harm or result in death. To avoid process leaks, only use the O-ring designed to seal with the corresponding flange adapter.

3 Electrical shock can result in death or serious injury. Avoid contact with the leads and the terminals. High voltage that may be present on leads can cause electrical entries Unless marked, the conduit/cable entries in the Transmitter housing use a 1/2 14 NPT thread form. Only use plugs, adapters, glands, or conduit with a compatible thread form when closing these System readiness .. 3 Transmitter installation .. 4 Mount the Transmitter .. 4 Tagging .. 9 Consider housing rotation .. 10 Set the switches .. 10 Wire, ground, and power up .. 11 Configure.

4 13 Zero trim the Transmitter .. 19 Product Certifications .. 20 Quick Start Guide3 February correct device driver Verify the correct device driver (DD/DTM ) is loaded on your systems to ensure proper communications. Download the correct device driver at your host vendor download site, or 3051 device revisions and driversTable 1 provides the information necessary to ensure you have the correct device driver and documentation for your 1. Installation FlowchartTable 1. Rosemount 3051 FOUNDATION Fieldbus Device Revisions and FilesDevice revision(1)1. FOUNDATION Fieldbus device revision can be read using a FOUNDATION Fieldbus capable configuration driver (DD)(2)2.

5 Device driver file names use device and DD revision. To access functionality, the correct device driver must be installed on your control and asset management hosts, and on your configuration atDevice driver (DTM)Manual document number8 AllDD4: DD Rev ,Rev, CA or newerAllDD5: DD Rev Device Manager V or higher: DD Rev Device Manager V 8 to : DD Rev : DD Rev 2 Easy Upgrade Utility7 AllDD4: DD Rev ,Rev, BAAllDD5: NAN/AEmersonAMS Device Manager V or higher: DD Rev Device Manager V 8 to : DD Rev / 475: DD Rev 6 Easy Upgrade UtilityStart1. Transmitter installation (Section 3) 2.

6 Commissioning tag (Section )DoneLocate device7. Zero trim the Transmitter (Section ) 3. Housing rotation (Section )5. Grounding, wiring and power up (Section )6. Configuration (Section , )4. Set switches and software write lock (Section ) February 20174 Quick Start the transmitterLiquid applicationsCoplanarIn-line1. Place taps to the side of the Mount beside or below the Mount the Transmitter so that the drain/vent valves are oriented applications1. Place taps in the top or side of the Mount beside or above the applications1.

7 Place taps to the side of the Mount beside or below the Fill impulse lines with Start Guide5 February 2017 Figure 2. Panel and Pipe MountingPanel mount(1) 11/2 panel bolts are customer mountCoplanar flangeTraditional flangeRosemount 3051 TFebruary 20176 Quick Start GuideBolting considerationsIf the Transmitter installation requires assembly of the process flanges, manifolds, or flange adapters, follow the assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitters. Use only bolts supplied with the Transmitter or sold by Emerson as spare parts.

8 Figure 3 on page 6 illustrates common Transmitter assemblies with the bolt length required for proper Transmitter 3. Common Transmitter Assemblies A. Transmitter with coplanar flangeB. Transmitter with coplanar flange and optional flange adaptersC. Transmitter with traditional flange and optional flange adaptersD. Transmitter with coplanar flange and optional manifold and flange adaptersBolts are typically carbon steel or stainless steel. Confirm the material by viewing the markings on the head of the bolt and referencing Table 2 on page 7. If bolt material is not shown in Table 2, contact a local Emerson representative for more information.

9 Use the following bolt installation procedure:1. Carbon steel bolts do not require lubrication and the stainless steel bolts are coated with a lubricant to ease installation. However, no additional lubricant should be applied when installing either type of Finger tighten the Torque the bolts to the initial torque value using a crossing pattern. See Table 2 for initial torque Torque the bolts to the final torque value using the same crossing pattern. See Table 2 for final torque Verify the flange bolts are protruding through the sensor module bolt holes before applying Pressure .

10 B4 (73 mm)A4 (44 mm)C4 (44 mm)4 (38 mm)D4 (44 mm)4 (57 mm)Quick Start Guide7 February 2017O-rings with flange adaptersEnvironmental seal for housingThread sealing (PTFE) tape or paste on male threads of conduit is required to provide a water/dust tight conduit seal and meets requirements of NEMA Type 4X, IP66, and IP68. Consult factory if other Ingress Protection ratings are M20 threads, install conduit plugs to full thread engagement or until mechanical resistance is gage Transmitter orientationThe low side Pressure port (atmospheric reference) on the in-line gage Transmitter is located in the neck of the Transmitter , behind the housing.