Transcription of Rosemount 644 Temperature Transmitter with …
1 Manual 00809-0300-4728, Rev AAJanuary 2011 Rosemount 644 Temperature Transmitter with profibus PAReference Manual 00809-0300-4728, Rev AAJanuary 2011 Rosemount 644 Temperature Transmitter with profibus PARosemount 644 Hardware Revision 9 NOTICERead this manual before working with the product. For personal and system safety, and for optimum product performance, make sure to thoroughly understand the contents before installing, using, or maintaining this United States has two toll-free assistance numbers and one international Central1-800-999-9307 (7:00 to 7:00 CST)National Response Center1-800-654-7768 (24 hours a day)Equipment service needsInternational1-(952) 906-8888 The products described in this document are NOT designed for nuclear-qualified applications. Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings. For information on Rosemount nuclear-qualified products, contact an Emerson Process Management Sales Manual 00809-0300-4728, Rev AAJanuary 2011 TOC-1 Rosemount 644 SECTION 1 IntroductionSafety Messages.
2 1-1 Warnings .. 1-1 Using This Manual .. 1-2 Transmitter Overview.. 1-2 Device Revision .. 1-3 Considerations.. 1-3 General .. 1-3 Commissioning .. 1-3 Mechanical .. 1-3 Electrical .. 1-3 Environmental.. 1-3 Return of Materials .. 1-4 SECTION 2 ConfigurationSafety Messages .. 2-1 Warnings .. 2-1 Configuration Guidelines .. 2-3 Profile Identification Number Adaptation Mode .. 2-3 Block Modes .. 2-3 Configuration Tools .. 2-3 Basic Setup Tasks .. 2-3 Device Description .. 2-3 Assign Address.. 2-3 Default Configuration .. 2-4 Transmitter Setup Using Class 2 Master .. 2-4 Basic Transmitter Setup .. 2-4 Process Alarms .. 2-4 Simulation.. 2-5 Transmitter Online Setup with DD or DTM .. 2-6 Basic Transmitter Setup .. 2-6 Process Alarms .. 2-7 LCD Display .. 2-7 Simulation.. 2-7 SECTION 3 Hardware InstallationOverview .. 3-1 Safety Messages .. 3-1 Warnings .. 3-1 Mounting .. 3-2 Installation .. 3-3 Typical European Installation.
3 3-3 Typical North American Installation .. 3-4 LCD Display Installation .. 3-5 SECTION 4 Electrical InstallationOverview .. 4-1 Safety Messages .. 4-1 Warnings .. 4-1 Wiring.. 4-2 Sensor Connections .. 4-3 Ground the Transmitter .. 4-5 Table of ContentsReference Manual00809-0300-4728, Rev AAJanuary 2011 Rosemount 644 TOC-2 SECTION 5 CalibrationOverview .. 5-1 Safety Messages .. 5-1 Warnings .. 5-1 Sensor Transducer Block .. 5-2 SECTION 6 TroubleshootingOverview .. 6-1 Safety Messages .. 6-1 Warnings .. 6-1 Diagnostics Identification and Recommendation.. 6-2 Extended Diagnostics Identification with class one master .. 6-4 PlantWeb and NE107 Diagnostics.. 6-6 Alert Messages and Fail Safe Type Selection .. 6-6 APPENDIX ASpecifications and Reference DataProfibus PA Specifications.. A-1 Functional .. A-1 Physical .. A-2 Performance .. A-3 Function Blocks .. A-3 Dimensional Drawings .. A-7 Ordering Information.
4 A-9 Tagging.. A-12 Considerations .. A-12 Dimensional Drawings .. A-14 Configuration .. A-15 APPENDIX BProduct CertificationsApproved Manufacturing Locations .. B-1 European Union Directive Information.. B-1 Hazardous Locations Certificates .. B-2 Rosemount 644 with profibus PA .. B-2 IECEx Certifications .. B-4 Russian GOST Certifications .. B-6 Kazakhstan GOST .. B-6 Ukraine GOST .. B-6 Installation Drawings .. B-7 APPENDIX CProfibus Block InformationOverview ..C-1 Safety Messages ..C-1 Warnings ..C-1 Resource Block ..C-2 Condensed Status ..C-7 Reference Manual 00809-0300-4728, Rev AAJanuary 2011 Rosemount 1 IntroductionSafety Messages .. page 1-1 Using This Manual .. page 1-2 Transmitter Overview .. page 1-2 Device Revision .. page 1-3 Considerations .. page 1-3 Return of Materials .. page 1-4 SAFETY MESSAGESI nstructions and procedures in this section may require special precautions to ensure the safety of the personnel performing the operations.
5 Information that potentially raises safety issues is indicated by a warning symbol ( ). Please refer to the following safety messages before performing an operation preceded by this to follow these installation guidelines could result in death orserious injury. Make sure only qualified personnel perform the could result in death or serious injury. Do not remove the connection head cover in explosive atmospheres when the circuit is live. Before connecting profibus devices in an explosive atmosphere, make sure the instruments in the loop are installed in accordance with intrinsically safe or non-intrinsic field wiring practices. Verify that the operating atmosphere of the Transmitter is consistent with the appropriate hazardous locations certifications. All connection head covers must be fully engaged to meet explosion-proof leaks could result in death or serious injury. Do not remove the thermowell while in operation.
6 Install and tighten thermowells and sensors before applying pressureElectrical shock could cause death or serious injury. Use extreme caution when making contact with the leads and Manual00809-0300-4728, Rev AAJanuary 2011 Rosemount 6441-2 USING THIS MANUALThe sections in this manual provide information on installing, operating, and maintaining the Rosemount 644 with profibus PA protocol. The sections are organized as follows:Section 2: Configuration provides instruction on commissioning and operating the Rosemount 644 PA Transmitter . Information on software functions, configuration parameters, and online variables is also 3: Hardware Installation contains mechanical mounting and installation instructions, and field upgrade 4: Electrical Installation contains electrical installation instructions, with wiring and power 5: Calibration contains techniques for calibration and troubleshootingAppendix A: Specifications and Reference Data supplies reference and specification data, as well as ordering B: Product Certifications contains intrinsic safety approval information, European ATEX directive information, and approval C: profibus Block Information contains profibus block and parameter OVERVIEWF eatures of the Rosemount 644 with profibus PA include.
7 Accepts inputs from a wide variety of sensors (T/C, RTD, Ohm, mV) Configuration using Siemens SIMATIC PDM Electronics that are completely encapsulated in epoxy making the Transmitter extremely durable and ensuring long-term reliability A compact size and a variety of housing options allowing mounting flexibility for the control room or the fieldRefer to the following literature for a full range of compatible connection heads, sensors, and thermowells provided by Emerson Process Management. Temperature Sensors and Assemblies Product Data Sheet, Volume 1 (document number 00813-0100-2654) Temperature Sensors and Assemblies Product Data Sheet, Volume 2 (document number 00813-0200-2654) Rosemount 1067 compact sensor and 1097 Thermowell Product Data Sheet (00813-0100-4951) Rosemount 65Q and 65B Resistance Temperature Sensors for Hygienic and Sanitary Applications Product Data Sheet (00813-0100-4827)NOTEFor Rosemount 644 with HART or FOUNDATION fieldbus, see Rosemount Product Manual Manual 00809-0300-4728, Rev AAJanuary 20111-3 Rosemount 644 DEVICE REVISIONT able 1-1.
8 Device Revisions (NE53)CONSIDERATIONSG eneralElectrical Temperature sensors such as RTDs and thermocouples produce low-level signals proportional to their sensed Temperature . The 644 converts the low-level sensor signal to digital profibus PA signal that is relatively insensitive to lead length and electrical noise. This signal is then transmitted to the control room via two Transmitter can be commissioned before or after installation. It may be useful to commission it on the bench, before installation, to ensure proper operation and to become familiar with its functionality. Make sure the instruments in the loop are installed in accordance with intrinsically safe, FISCO, or non-incendive field wiring choosing an installation location and position, take into account the need for access to the MountingSpecial mounting hardware is available for mounting a 644 head mount Transmitter to a DIN rail, or assembling a new 644 head mount to an existing threaded sensor connection head (former option code L1).
9 Electrical Proper electrical installation is necessary to prevent errors due to sensor lead resistance and electrical noise. For best results, shielded cable should be used in electrically noisy environments. Make wiring connections through the cable entry in the side of the connection head. Be sure to provide adequate clearance for cover Transmitter electronics module is permanently sealed within the housing, resisting moisture and corrosive damage. Verify that the operating atmosphere of the Transmitter is consistent with the appropriate hazardous locations Effects The Transmitter will operate within specifications for ambient temperatures between 40 and 185 F ( 40 and 85 C). Heat from the process is transferred from the thermowell to the Transmitter housing. If the expected process Temperature is near or beyond specification limits, consider the use of additional thermowell lagging, and extension nipple, or a remote mounting configuration to isolate the Transmitter from the process.
10 DateSoftware RevisionProfibus ProfileChanges to SoftwareCompatible FilesManual Revision11 Product644 GSD: GSD: : see : see Manual00809-0300-4728, Rev AAJanuary 2011 Rosemount 6441-4 Figure 1-1 provides an example of the relationship between Transmitter housing Temperature rise and extension length. Figure 1-1. 644 head mount Transmitter Connection Head Temperature Rise vs. Extension LengthExampleThe Transmitter specification limit is 85 C. If the ambient Temperature is 55 C and the process Temperature to be measured is 800 C, the maximum permissible connection head Temperature rise is the Transmitter specification limit minus the ambient Temperature (moves 85 to 55 C), or 30 this case, an extension of 100 mm meets this requirement, but 125 mm provides a margin of 8 C, thereby reducing any Temperature effects in the OF MATERIALSTo expedite the return process in North America, call the Emerson Process Management National Response Center toll-free at 800-654-7768.