Rosemount Volume 1 Sensor Assembly - Emerson

Quick Start Guide00825-0300-2654, Rev FAFebruary 2020 Rosemount Volume 1 Sensor AssemblyContentsAbout this Series 58C sheath cutting .. Start GuideFebruary this guideThis guide provides basic guidelines for Rosemount 0068, 0078, and 0183 Sensor models. It does not provide instructions for configuration,diagnostics, maintenance, service, troubleshooting, explosion-proof,flameproof, or intrinsically safe ( ) installations. If the Rosemount Volume1 Sensor was ordered assembled to a temperature transmitter, see theappropriate transmitter Quick Start Guide for information on configurationand hazardous locations can arise when sensors and the transmitters to which they areassembled have compatible but unique approvals. Be aware of the followingsituation: If an approved 1067 Sensor is ordered with a housing andtransmitter, the transmitter enclosed in that housing may have adifferent approval rating.

December 2017 6 Quick Start Guide 4.0 Product certifications Rev 2.10 4.1 European Directive Information A copy of the EU Declaration of Conformity can be found at the end of the Quick

Tags:

  European, Volume, Rosemount, Assembly, Sensor, Rosemount volume 1 sensor assembly

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Rosemount Volume 1 Sensor Assembly - Emerson

1 Quick Start Guide00825-0300-2654, Rev FAFebruary 2020 Rosemount Volume 1 Sensor AssemblyContentsAbout this Series 58C sheath cutting .. Start GuideFebruary this guideThis guide provides basic guidelines for Rosemount 0068, 0078, and 0183 Sensor models. It does not provide instructions for configuration,diagnostics, maintenance, service, troubleshooting, explosion-proof,flameproof, or intrinsically safe ( ) installations. If the Rosemount Volume1 Sensor was ordered assembled to a temperature transmitter, see theappropriate transmitter Quick Start Guide for information on configurationand hazardous locations can arise when sensors and the transmitters to which they areassembled have compatible but unique approvals. Be aware of the followingsituation: If an approved 1067 Sensor is ordered with a housing andtransmitter, the transmitter enclosed in that housing may have adifferent approval rating.

2 Refer to the transmitter IS certificate ifapplicable. If a Sensor and transmitter have different certifications, or if either hasmore certifications than the other, installation must comply with themost restrictive requirements of either component. This is especially(but not exclusively) relevant when combination approvals are orderedon either the Sensor or transmitter. Review certifications on both thesensor and transmitter for installation requirements and ensureinstallation of the Sensor /transmitter Assembly complies with a singlecertification that is shared by both of these components and that meetsthe requirements of the application. WARNINGP hysical accessUnauthorized personnel may potentially cause significant damage to and/ormisconfiguration of end users equipment.

3 This could be intentional orunintentional and needs to be protected security is an important part of any security program andfundamental to protecting your system. Restrict physical access byunauthorized personnel to protect end users assets. This is true for allsystems used within the 2020 Quick Start GuideQuick Start Guide32 Wiring diagramsFigure 2-1: Rosemount Series 68, 68Q, 78, and 58C RTD Wire ColorsSingle ElementDual Element(1) AABB BBACCD(1)Dual element sensors are only available on Rosemount Series 68Q and RedB. WhiteC. GreenD. BlackNoteFor three-wire systems, use one white and two red leads. Do not connect thewhite leads. Insulate or terminate the unused white lead in a manner thatprevents shorting to the ground. For two-wire systems, connect both sets Start GuideFebruary Series 58C sheath cuttingProcedure1.

4 Determine the length to which the sheath will be cut. The finishedlength needs to include an additional ( cm) forcompression fittings or ( cm) for spring-loaded fittings (seeFigure 4-1).2. Remove and save the heat shrink tubing from the rear of the Place the Sensor in a vise, taking care not to overtighten, and positionthe tubing cutter on the Score the sheath to a depth of approximately 1/64-in. ( cm) Toprevent damage to the lead wire insulation, do not cut completelythrough the Firmly grasp the end of the sheath with your hand or a pair of a sharp snapping motion, break off and remove the excesssheath material. Take care not to strip or damage the lead wireinsulation while removing the excess sheath you are unable to easily break off excess sheath material, deepenthe score and repeat Step Replace the heat shrink 2020 Quick Start GuideQuick Start Guide54 DrawingsFigure 4-1: Rosemount Series 58C SensorABCDEFA.

5 Four lead wires 6-in. (152 mm) X length ( 6)C. ( ) diameterD. Heat shrink tubingE. Do not cut or bend sheath within 2-in (51 mm)F. (15 mm) max. sensing elementFigure 4-2: Rosemount Series 183 Thermocouple Wire ColorsType JType E+ A- B + C- B Type KType T+ D- B + E- B A. WhiteB. RedC. PurpleD. YellowE. BlueQuick Start GuideFebruary 4-1: Rosemount Series 183 Thermocouple CharacteristicsThermocoupletypesThermoco uplewire alloysTemperature rangeLimits of error(interchangeability) C FJIron/constantan0 to 76032 to1400 C ( F) or of measuredtemperature,whichever is greaterKChromel /Alumel 0 to 115032 to2102 C ( F) or of measuredtemperature,whichever is greaterEChromel/constantan0 to 87132 to1600 C ( F) or of measuredtemperature,whichever is greaterTCopper/constantan 180 to 0 292 to32 C ( F) or of measuredtemperature,whichever is greater0 to 37132 to 700 C ( F)

6 Or of measuredtemperature,whichever is greaterNoteTo distinguish the two sensors in dual Rosemount 183 Sensors, there is anouter insulation wrapped around each pair of Sensor 2020 Quick Start GuideQuick Start Guide7 Figure 4-3: Sensor AssemblyABDABDABBBCEFIGHKJLMONPQRSTAOpen identification tagBStandard adapter Sensor assemblyCSensor immersion length X (13 mm) nominalengagementECoupling nippleFExtension lengthGOverall thermowell lengthHLead wire extensions and (13 mm) nominalengagementJExtensionsKUnion nippleLFlat or extended cover aluminumconnection headsMThreaded thermowellNThermowellsOT + ( mm)PSocket weld thermowellQPolypropylene connection headRThermowell immersion lengthSFlanged thermowellTRosemount aluminum connectionheadQuick Start GuideFebruary assemblies can be provided without an enclosure or with anenclosure such as the connection heads shown above or assembled to aRosemount 2020 Quick Start GuideQuick Start Guide95 Product certificationsRev Directive InformationA copy of the EC Declaration of Conformity can be found at the end of theQuick Start Guide.

7 The most recent revision of the EC Declaration ofConformity can be found at Location CertificationAs standard, the transmitter has been examined and tested to determinethat the design meets the basic electrical, mechanical, and fire protectionrequirements by a nationally recognized test laboratory (NRTL) as accreditedby the Federal Occupational Safety and Health Administration (OSHA). AmericaThe US National Electrical Code (NEC) and the Canadian Electrical Code(CEC) permit the use of Division marked equipment in Zones and Zonemarked equipment in Divisions. The markings must be suitable for the areaclassification, gas, and temperature class. This information is clearly definedin the respective FM Explosion proof, Dust-Ignition proofCertificateFM17US0170 XStandardsFM Class 3600: 2011; FM Class 3611: 2004; FM Class 3615:2006; FM Class 3810: 2005; ANSI/NEMA - 250: 1991 MarkingsXP CL I, Div 1, GP B, C, D; DIP CL II/III, Div 1, GP E, F, G; T5(-50 C Ta 85 C); when installed per Rosemount drawing00068-0013; Type CSA Explosion proof and Dust-Ignition proofCertificate1063635 StandardsCSA No.

8 0-M91; CSA No. 25-1966; CSA ; CSA No. 94-M91; CSA No. 142-M1987; CSA No. 213-M1987 MarkingsXP CL I, Div 1, GP B, C, D; DIP CL II/III, Div 1, GP E, F, G; CL I, Div2, GP A, B, C, D; (-50 C Ta 85 C); when installed perQuick Start GuideFebruary drawing 00068-0033; Type 4X (Spring loadedsensors must be installed in a thermowell to maintain Type 4 Xand Cl. II/III rating) ATEX FlameproofCertificateFM12 ATEX0065 XStandardsEN 60079-0: 2012+A11:2013, EN 60079-1: 2014, EN60529:1991 +A1:2000 + A2:2013 MarkingsII 2 G Ex db IIC Gb, T6(-50 C Ta +40 C), (-50 C Ta +60 C)See Process Temperature Limits for process Conditions for Safe Use(X)1. See certificate for ambient temperature The non-metallic label may store an electrostatic charge and becomea source of ignition in Group III Guard the LCD display cover against impact energies greater than Flameproof joints are not intended for A suitable certified Ex d or Ex tb enclosure is required to be connectedto temperature probes with Enclosure option N.

9 6. Care shall be taken by the end user to ensure that the externalsurface temperature on the equipment and the neck of DIN StyleSensor probe does not exceed 130 Non-Standard Paint options may cause risk from electrostaticdischarge. Avoid installations that cause electrostatic build-up onpainted surfaces, and only clean the painted surfaces with a dampcloth. If paint is ordered through a special option code, contact themanufacturer for more IECEx FlameproofCertificateIECEx FMG 60079-0:2011, IEC 60079-1:2014-06 February 2020 Quick Start GuideQuick Start Guide11 MarkingsEx db IIC Gb, T6(-50 C Ta +40 C), (-50 C Ta +60 C)Special Conditions for Safe Use(X)1. See certificate for ambient temperature The non-metallic label may store an electrostatic charge and becomea source of ignition in Group III Guard the LCD display cover against impact energies greater than Flameproof joints are not intended for A suitable certified Ex d or Ex tb enclosure is required to be connectedto temperature probes with Enclosure option N.

10 6. Care shall be taken by the end user to ensure that the externalsurface temperature on the equipment and the neck of DIN StyleSensor probe does not exceed 130 Non-Standard Paint options may cause risk from INMETRO FlameproofCertificateUL-BR NBR IEC 60079-0:2013; ABNT NBR IEC 60079-1:2016;ABNT NBR IEC 60079-31:2014 MarkingsEx db IIC Gb (-50 C Ta +40 C), (-50 C Ta +60 C)Ex tb IIIC T130 C Db (-40 C Ta +70 C)Special Conditions for Safe Use(X)1. See product description for ambient temperature limits and processtemperature The non-metallic label may store an electrostatic charge and becomea source of ignition in Group III Guard the LCD display cover against impact energies greater than A suitable certified Ex d or Ex tb enclosure is required to be connectedto temperature probes with Enclosure option "N".