S4000C Combustible Gas Detector Manual

Model S4000C Intelligent Sensor for Combustible Gas Detection The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized in writing by General Monitors. Instruction Manual 0307 General Monitors reserves the right to change published specifications and designs without prior notice. MANS4000C Part No. MANS4000C Revision G/03-07 S4000C ii This page intentionally left blank S4000C iii Terminal Table of Contents TABLE OF TABLE OF QUI

Model S4000C Intelligent Sensor for Combustible Gas Detection The information and technical data disclosed in this document may be used and disseminated

Tags:

  Combustible, Combustible gas

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of S4000C Combustible Gas Detector Manual

1 Model S4000C Intelligent Sensor for Combustible Gas Detection The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized in writing by General Monitors. Instruction Manual 0307 General Monitors reserves the right to change published specifications and designs without prior notice. MANS4000C Part No. MANS4000C Revision G/03-07 S4000C ii This page intentionally left blank S4000C iii Terminal Table of Contents TABLE OF TABLE OF QUICK START 1 Mounting and Tools

2 Terminal 1 Protection for Special System Integrity PRODUCT 3 General 4 Receipt of Tools Choosing Product Remote Mounting of the Sensor from the Mounting and Terminal Block TB1 Sensor Terminal Block TB2 Power and Signal DC Power and Ground Analog Signal Terminal Block TB3 Relay European Union (EU) Approved Cable Termination in the Non-Hazardous Maintaining the X/P 13 Start-Up Relay User Selectable Model S4000C User Menu Calibration Warning Relay Alarm Relay MODBUS Channel 1 MODBUS Channel 2 Gas Check Procedure for Checking the S4000C iv MODBUS 26 Calibration Aborting Adjustable Calibration Remaining Sensor Initializing the Remaining Sensor Calibration Portable Purge 22 General 23 Fault Codes & Their F2 Failed to Complete F3 EEPROM Checksum F4 Sensor

3 F5 F6 Low Supply F7 EEPROM Verification F8 Failure to Complete F9 Gas Check Period F10 Switch CUSTOMER 25 General Monitors Baud Data MODBUS Read Status Protocol (Query/Response)..26 MODBUS Read Query MODBUS Read Response MODBUS Write Command Protocol (Query/Response)..27 MODBUS Write Query MODBUS Write Response Function Codes Exception Responses and Exception Exception Exception S4000C Command Register S4000C Command Register Unit Software Status Alarm S4000C v Sensitivities to Other Warn Com1 Com1 Baud Com1 Data Com2 Com2 Baud Com2 Data Cal Reset Sensor HazardWatch (Co Calibration Output).

4 34 Total Receive Bus Activity Rate %..34 Function Code Starting Address Number of Register RXD CRC Hi RXD CRC Low Clear Comm 36 Principle of System Mechanical Electrical Environmental Spare Parts and Sensor Sensor Calibration Intelligent Transmitter ( S4000C ) Replacement Recommended Spare Parts for One (1) FMRC S4000C vi Table of Figures Figure 1: Outline and Mounting 1 Figure 2: Spring Type Terminal Block 2 Figure 3: Screw Type Terminal Block 2 Figure 4: Model S4000C Intelligent 3 Figure 5: Outline and Mounting 6 Figure 6.

5 Spring Type Terminal Block 8 Figure 7: Screw Type Terminal Block 8 Figure 8: Wire Strip 8 Figure 9: Relay Protection for DC and AC 11 Figure 10: Relay 14 Figure 11: User Menu 15 Figure 12: Calibration Figure 13: Automatic Calibration 19 Figure 14: Calibration In Progress 19 Figure 15: Calibration Complete 19 S4000 CTable of Tables Table 1: TB2 Power and Signal 7 Table 2: Ground or Common 9 Table 3: Power 9 Table 4: Analog Signal 10 Table 5: Alarm Relay 10 Table 6: Warn Relay 10 Table 7: Fault Relay 10 Table 8: GM 25 Table 9: Data 26 Table 10: Exception 28 Table 11: Command Register 29 Table 12: Command Register Locations 30 Table 13: Com1 Baud 33 Table 14: Com1 Data Table 15: Com2 Baud 33 Table 16: Com2 Data Table 17: 24 VDC Cable 38 Table 18: Analog Output Cable 38 Table 19: Sensor Cable 38 Table 20: Chemical List from1994 40 vii S4000 CQuick Start Guide Mounting and Wiring Tools Required 1.

6 5mm Allen head wrench to remove enclosure lid (included with gas Detector ). 2. Flat-head screwdriver maximum 3/16 (5 mm) width for terminal block connections (included with gas Detector ). 3. Adjustable wrench for conduit or cable gland connections (not included). It is not necessary to seal the Model S4000C housing to maintain its explosion-proof integrity; however, conduit runs containing wires attached to the Model S4000C s relay contacts must be sealed. Information on Class I location seals can be found in the NEC, Article 501-5. Figure 1: Outline and Mounting Dimensions Terminal Connections The terminal blocks (TB) are located inside the housing and can be accessed by removing the cover. A label on the inside of the housing cover provides details of all the terminal connections. WARNING: Do not connect +24 VDC to TB1. Damage to the electronics, or sensor may result. It is recommended that a three-wire (red, black, white) shielded cable be used for making power and output signal connections on the Model S4000C .

7 The Spring Type terminal block accepts 14 AWG to 20 AWG and the Screw Type terminal block accepts 12 AWG to 18 AWG stranded or solid wire. Each wire should be stripped before wiring the Model S4000C Intelligent Sensor. To connect wiring to the Spring Type terminal block, insert a screwdriver into the orange tab and press down (Figure 2), opening the terminal. Insert the wire into the terminal 1 S4000C 2 and release the orange tab, clamping the wire in the terminal. Check the hold of the wire by GENTLY tugging it to ensure it is locked in.

8 To connect wiring to the Screw Type terminal block, (Figure 3) use a screwdriver to loosen the top screw counter clock wise. Insert the wire into the terminal and tighten the top screw clock wise. Check the hold of the wire by GENTLY tugging it to ensure it is locked in. Figure 2: Spring Type Terminal Block Operation Figure 3: Screw Type Terminal Block Operation NOTE: Power must remain disconnected until all other wiring connections have been made. The maximum distance between the Model S4000C and the power supply is 3430 feet or 1040 meters (each cable run should be as short as possible). See Section for cable length specifications. Connect +24 VDC to TB2, position 9. Connect the ground or common to TB2, position 8. The instrument is now ready to operate. Please consult the Manual for more information on the instrument s many features. NOTE: If you have any problems in the set-up or testing of the Detector , please refer to the Trouble Shooting Section , or call the factory direct.

9 S4000C 3 Worldwide service is available by calling: Lake Forest, California (24 hr. service) Toll Free: +1-800-446-4872 Phone: +1-949-581-4464 Fax: +1-949-581-1151 Houston, Texas Phone: +1-281-855-6000 Fax: +1-281-855-3290 Ireland Phone: +353-91-751175 Fax: +353-91-751317 Singapore Phone: +65-6748-3488 Fax: +65-6748-1911 United Arab Emirates Phone: +971-4-8815751 Fax: +971-4-8817927 United Kingdom Phone: +44-1625-619583 Fax: +44-1625-619098 Introduction Protection for Life General Monitors mission is to benefit society by providing solutions through industry leading safety products, services, and systems that save lives and protect capital resources from the dangers of hazardous flames, gases, and vapors.

10 This Manual provides instruction for installing and operating General Monitors Model S4000C for Combustible Gas Detection. While the S4000C is easy to install and operate, this Manual should be read in full and the information contained herein understood before attempting to place the system in service. The safety products you have purchased should be handled carefully and installed, calibrated, and maintained in accordance with the respective product instruction Manual . Remember these products are for your safety. Special Warnings The Model S4000C Intelligent Sensor contains components, which can be damaged by static electricity. Special care must be taken when wiring the system to ensure that only the connection points are touched. Toxic, Combustible and flammable gases and vapors are very dangerous. Extreme caution should be used when these hazards are present.