CSM_NE1A-SCPU_Series_DS_E_6_41 Safety Network ControllerNE1A-SCPU SeriesAchieve Safety Control through Programming. Compact Safety Controller . The ne1a -SCPU01-V1 provides 16 built-in Safety inputs and 8 built-in Safety outputs. The ne1a -SCPU02 provides 40 built-in Safety inputs and 8 built-in Safety outputs. Reduced wiring with Safety networks. Connect up to 32 Safety Terminals. Monitor the Safety system from Standard Controllers across the Network . ISO13849-1 (PLe) and IEC 61508 SIL3 InformationList of ModelsNote:The standard ne1a Controllers are equipped with spring-cage terminal blocks, but other screw terminal blocks are available if desired, , to replace previous terminals. Refer to CIP Safety on DeviceNet StandardsSpecifications* : Internal control circuitV1-G1 (G): For external input device, test outputV2-G2 (G): For external output deviceThe two ground terminals on the ne1a -SCPU02 are internally connected.

CSM_NE1A-SCPU_Series_DS_E_6_4 1 Safety Network Controller NE1A-SCPU Series Achieve Safety Control through Programming. • Compact Safety Controller.

Tags:

  Controller, Series, Network, Safety, Scup, Safety network controller ne1a scpu series, Ne1a

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Safety Network Controller NE1A-SCPU Series - …

1 CSM_NE1A-SCPU_Series_DS_E_6_41 Safety Network ControllerNE1A-SCPU SeriesAchieve Safety Control through Programming. Compact Safety Controller . The ne1a -SCPU01-V1 provides 16 built-in Safety inputs and 8 built-in Safety outputs. The ne1a -SCPU02 provides 40 built-in Safety inputs and 8 built-in Safety outputs. Reduced wiring with Safety networks. Connect up to 32 Safety Terminals. Monitor the Safety system from Standard Controllers across the Network . ISO13849-1 (PLe) and IEC 61508 SIL3 InformationList of ModelsNote:The standard ne1a Controllers are equipped with spring-cage terminal blocks, but other screw terminal blocks are available if desired, , to replace previous terminals. Refer to CIP Safety on DeviceNet StandardsSpecifications* : Internal control circuitV1-G1 (G): For external input device, test outputV2-G2 (G): For external output deviceThe two ground terminals on the ne1a -SCPU02 are internally connected.

2 * including power consumption for external of I/O pointsModelUnit versionSafety inputsTest outputsSafety outputsSafety Network bodyStandardT V RheinlandNFPA 79-2012EN ISO13849-1: 2008 IEC61508 part 1-7: 2010 IEC61131-2: 2007EN ISO13849-2: 2012EN61000-6-4: 2007EN61000-6-2: 2005EN60204-1: 2006EN ISO13850: 2006(EN418: 1992)ANSI power sup-ply voltage11 to 25 VDC supplied via communications connectorInternal circuit power supply voltage (V0) * to VDC (24 VDC 15%/+10%)I/O power supply voltage (V1, V2) *1 Current con-sumptionCommunicationspower supply24 VDC, 15 mAInternal circuit power supply24 VDC, 230 mA24 VDC, 280 mAI/O power supply *224 VDC, 40 mA (Input)120 mA (Output)24 VDC, 80 mA (Input)150 mA (Output)Overvoltage categoryIINoise immunityConforms to resistance10 to 57 Hz: mm, 57 to 150 Hz: 50 m/s2 Shock resistance150 m/s2: 11 msMounting methodDIN Track (IEC 60715 )Ambient operating temperature 10 to 55 CAmbient operating humidity10% to 95% (with no condensation)Ambient storage temperature 40 to 70 CDegree of protectionIP20 Serial interfaceUSB version g g SeriesSafety Input SpecificationsSafety Output SpecificationsTest Output Specifications*The maximum current for simultaneously ON outputs is A.

3 (T0 to T3: ne1a -SCPU01-V1, T0 to T7: ne1a -SCPU02)A 15 to 400-mA, 24-VDC external indicator can be connected to T3 and Communications SpecificationsInput typeSinking inputs (PNP)ON voltage11 VDC min. between each terminal and groundOFF voltage5 VDC min. between each terminal and groundOFF current1 mA mAOutput typeSourcing outputs (PNP)Rated output A residual V max. between each output terminal and V2 Leakage mA typeSourcing outputs (PNP)Rated output A *ON residual V max. between each output terminal and V1 Leakage mA protocolDeviceNet compliantConnection formMulti-drop system and T-branch system can be combined (for trunk line and branch lines)Communications speed500/250/125 kbpsCommunications mediaSpecial cable, 5 conductors (2 for communications, 2 for power supply, 1 for shielding)Communications distanceCommunications power supply11 to 25 VDCNo. of connectable nodes63 Safety I/O communications (Pre-Ver.)

4 Safety Master function Max. no. of connections: 16 Max. data size: Input 16 bytes or output 16 bytes (per connection) Connection type: Single-cast, multi-castSafety Slave function Max. no. of connections: 4 Max. data size: Input 16 bytes or output 16 bytes (per connection) Connection type: Single-cast, multi-castSafety I/O communications (unit version or later) Safety Master function Max. no. of connections: 32 Max. data size: Input 16 bytes or output 16 bytes (per connection) Connection type: Single-cast, multi-castSafety Slave function Max. no. of connections: 4 Max. data size: Input 16 bytes or output 16 bytes (per connection) Connection type: Single-cast, multi-castStandard I/O communications (all unit versions)Standard Slave function Max. no. of connections: 2 Max. data size: Input 16 bytes or output 16 bytes (per connection) Connection type: Poll, bit-strobe, COS, cyclicMessage communicationsMax.

5 Message length: 552 bytesNote:Figures in parentheses ( ) indicate values when a thin cable is speedMax. Network lengthBranch lengthTotal branch length500 kbps100 m max. (100 m max.)6 m m kbps250 m max. (100 m max.)78 m kbps500 m max. (100 m max.)156 m Series3 FunctionsFunction BlocksNE1A-SCPU- Series Controller support the following logic functions and function blocks. Support depends on the unit version. Logic FunctionsFunction BlocksNameFunction list entrySupporting unitversionsNOTNOTAllANDANDORORE xclusive OREXORE xclusive NOREXNORRS or laterComparatorComparatorNameFunction list entrySupporting unitversionsResetResetAllRestartRestartE mergency Stop MonitoringE-STOPL ight Curtain MonitoringLight Curtain MonitoringSafety Gate MonitoringSafety Gate MonitoringTwo-hand ControllerTwo Hand ControllerOff-Delay TimerOff-Delay TimerOn-Delay TimerOn-Delay TimerUser Mode Switch MonitoringUser Mode SwitchExternal Device or laterEnable Switch MonitoringEnable SwitchPulse GeneratorPulse GeneratorCounterCounterMulticonnectorMul ti Connector4NE1A-SCPU SeriesInternal Circuit DiagramsNE1A-SCPU01-V1NE1A-SCPU02V+CAN HShieldCAN LV D+D USB24 VDCNCNC24 VDCV0G0V0G0V1G1T0T3IN0IN1524 VDCV2G2 LOUT0 LOUT7DC-DC Converter (Insulated)

6 Safety Output CircuitSafety Input CircuitTest Output CircuitDC-DC Converter (Non-insulated)Internal CircuitDeviceNet Physical LayerTerminal nameDescriptionV0 Power supply terminal for internal circuitThe two V0 terminals are internally supply terminal for internal circuitThe two G0 terminals are internally supply terminal for external input device and test outputG1 Power supply terminal for external input device and test outputV2 Power supply terminal for external output deviceG2 Power supply terminal for external output deviceIN0 to IN15 Safety input terminalT0 to T3 Test output terminalConnected to IN0 to IN15 Safety test output terminal outputs a different test pulse T3 also supports a current monitoring function for the output : Muting lampOUT0 to OUT7 Safety output terminalsV+CAN HShieldCAN LV D+D USBV0G0V1GT0T7IN0IN39V2 GLOUT0 LOUT7DC-DC Converter (Insulated) Safety Output CircuitSafety Input CircuitTest Output CircuitDC-DC Converter (Non-insulated)Internal CircuitDeviceNet Physical Layer24 VDC24 VDC24 VDCT erminal nameDescriptionV0 Power supply terminal for internal circuitThe two V0 terminals are internally supply terminal for internal circuitThe two G0 terminals are internally supply terminal for external input device and test outputGPower supply terminal for external input device and test outputV2 Power supply terminal for external output deviceGPower supply terminal for external output deviceIN0 to IN39 Safety input terminalT0 to T3 Test output terminalConnected to IN0 to IN19 Safety test output terminal outputs a different test pulse T3 also supports a current monitoring function for the output.

7 Muting lampT4 to T7 Test output terminalConnected to IN20 to IN39 Safety test output terminal outputs a different test pulse T7 also supports a current monitoring function for the output : Muting lampOUT0 to OUT7 Safety output terminalsRefer to the CIP Safety on DeviceNet Safety Network Controllers Operation Manual (Cat. No. Z906) for wiring Series5 Dimensions(Unit: mm) (99) 24 VDC 10 1 ON 1 0 1 0 3 2 5 4 7 6 1 0 3 2 5 4 7 6 1 0 3 2 5 4 7 6 9 8 11 10 13 12 15 14 3 2 5 4 7 6 9 8 11 10 13 12 15 14 Safety Network Controller 0 0 USB NS MS LOCK COMM ne1a -SCPU01-V1 NODE ADR BAUD RATE V0 G0 24 VDC OUT IN V1 G1 V2 G2 T0 T2 T1 T3 V1 G1 V2 G2 T0 T2 T1 T3 V0 G0 1 2 3 4 O N ( ) (99) 10 1ON1010325476103217161918T1T0T3T21032171 619189811101312151432547698111013121514 Safety Network CONTROLLER00 USBNSMSLOCKCOMMNE1A-SCPU02 NODE ADRBAUD RATEV0G024 VDCOUTIN37363938 ININV1GV2G212021202322252427265476T5T4T7 T654762928313033323534232225242726292831 3033323534 OUTNCNCNCNC36 3837 39V0G01234ON( )

8 SeriesSafety PrecautionsRefer to the " Safety Precautions for All CIP Safety on DeviceNet Systems" for sure to read the following user's manual for other details required for correct use of the Safety Network Safety on DeviceNet Safety Network Controller User's Manual (Cat. No. Z916)Functions Supported According to Unit Version : Supported, ---: Not supportedModelNE1 ASCPU01NE1 ASCPU01-V1NE1 ASCPU02 Unit versionFunctionPre-Ver. version version processing functionsMaximum program size (total number of function blocks)128254254 New Function Blocks RS flip-flop Multiconnector Muting Enable Switch Monitoring Pulse Generator Counter Comparator--- Selecting a rising edge as the reset condition for Reset and Restart function blocks--- Using local I/O status in logic programming--- Using overall Unit status in logic programming--- Program execution wait functions--- (Unit version or higher) (Unit version or higher)

9 I/O control functionsMonitoring contact operation counter--- Mounting total ON time monitor--- DeviceNet communications functionsNumber of Safety I/O connections for Safety Master163232 Selecting operating mode for Safety I/O communications when communications errors occur--- Attaching local output data to send data during slave operation--- Attaching local I/O monitor data to send data during slave operation--- Functions to communicate with devices existing on other networks(Off-Link connection)--- (Unit version or higher) (Unit version or higher)System startup and error recovery functionsStoring log of nonfatal errors in nonvolatile memory--- Adding function block errors to error log--- Ethernet/IP communications functionsI/O communications---------Message communications ---------Read/write of target I/O area---------Routing between DeviceNet and EtherNet/IPI/O routing---------Message routing---------UDP/IP message communications functionsMessage communications by UDP/IP--------- NE1A-SCPU Series7 Unit Versions and Network Configurator VersionsNetwork Configurator version @ or higher must be used when using a ne1a -SCPU01-V1 or ne1a -SCPU02 Safety Logic Controller with unit version : Applicable, : Not applicable*1: It can be used as unit version.

10 Who use Network Configurator version @ or earlier can upgrade to version @ at no using Network Configurator version @, there are no operational differences in the ne1a -SCPU01-V1 and ConfiguratorVer. @ ne1a -SCPU01-V1 Unit version ne1a -SCPU02 Unit version ne1a -SCPU01-V1 Unit version (*1) ne1a -SCPU02 Unit version (*1) Terms and Conditions Agreement Read and understand this catalog. Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranties. (a) Exclusive Warranty. Omron s exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied.