Service Manual - daikinac.com

Service ManualRZR-P, RZQ-P(9) SeriesCooling Only / Heat PumpR- 410a 60 HzSiUS281117 SiUS281117 Table of ContentsiRZR-P, RZQ-P(9) SeriesCooling Only / Heat PumpR- 410a 60 HzED ReferenceFor items below, please refer to Engineering except FTQFor FTQ1. Safety Considerations .. Safety Considerations for Repair .. Safety Considerations for Users ..viPart 1 General 11. Model Names and Power Cooling Only .. Heat Pump .. 22. External Appearance .. Indoor Remote Controller .. Outdoor Units .. 4 Part 2 Refrigerant Circuit.

SiUS281117 Table of Contents i RZR-P, RZQ-P(9) Series Cooling Only / Heat Pump R-410A 60Hz ED Reference For items below, please refer to Engineering Data.

Tags:

  410a, 410a r

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Service Manual - daikinac.com

1 Service ManualRZR-P, RZQ-P(9) SeriesCooling Only / Heat PumpR- 410a 60 HzSiUS281117 SiUS281117 Table of ContentsiRZR-P, RZQ-P(9) SeriesCooling Only / Heat PumpR- 410a 60 HzED ReferenceFor items below, please refer to Engineering except FTQFor FTQ1. Safety Considerations .. Safety Considerations for Repair .. Safety Considerations for Users ..viPart 1 General 11. Model Names and Power Cooling Only .. Heat Pump .. 22. External Appearance .. Indoor Remote Controller .. Outdoor Units .. 4 Part 2 Refrigerant Circuit.

2 51. Refrigerant Circuit .. RZR18 / 24 / 30 PVJURZQ18 / 24 PVJU9 RZQ30 PVJU .. RZR36 / 42 PVJURZQ36 / 42 PVJU(9) .. - Cooling OnlyEDUS281120p. 7-132 Specification - Heat PumpEDUS281120p. 14-203 Option ListEDUS281120p. - Heat PumpEDUS281008p. 42 Option ListEDUS281008p. 60 SiUS281117iiTable of Contents2. Functional Parts Layout .. RZR18 / 24 / 30 PVJURZQ18 / 24 PVJU9 RZQ30 PVJU .. 10 Part 3 Remote Controller .. 111. Wired Remote Controller .. Applicable Models .. Names and Functions .. MAIN/SUB Setting when Using 2 Remote Centralized Control Group No.

3 Setting .. 192. Wireless Remote Controller .. Applicable Models .. Names and Functions .. Address and MAIN/SUB Setting .. 243. Service Mode .. BRC1D71 .. BRC1E71 .. 284. Inspection 4 Function and Control .. 311. Function General .. Operation Mode .. 322. Basic Normal Compressor PI Control .. Electronic Expansion Valve PI Control .. Cooling Operation Fan Control .. 363. Special Startup Control .. Oil Return Operation .. Defrosting Operation .. Pump Down Residual Restart Standby.

4 Stopping Operation .. Pressure Equalization Prior to Startup .. 434. Protection Control .. High Pressure Protection Control .. Low Pressure Protection Control .. Discharge Pipe Protection Control .. Inverter Protection Control .. 475. Other Control .. Heating Operation Prohibition .. 486. Outline of Control (Indoor Unit) .. Drain Pump Control .. Louver Control for Preventing Ceiling Dirt .. 51 SiUS281117 Table of Room Temperature Thermistor in Remote Thermostat Control with Operation Mode Set to "AUTO".

5 Freeze-up Prevention .. View of Operations of Swing Flaps .. Hot Start Control (In Heating Operation Only) .. Heater Control (FTQ) .. 4 Step Thermostat Processing (FTQ) .. Interlocked with External Equipment (FTQ) .. 63 Part 5 Field 651. Test Operation .. Procedure and Outline .. Operation when Power is Turned ON .. 692. Field Setting from Remote Wired Remote Controller .. Wireless Remote Controller .. Setting Contents and Code No. for Indoor 743. Field Setting from Outdoor Unit.

6 Location of DIP Switch and BS Setting by DIP Setting by BS Buttons .. Setting Mode 1 .. Setting Mode 2 .. Monitor Mode .. Detailed Explanation of Setting Modes .. 87 Part 6 Service 941. Symptom-based Troubleshooting ..962. Troubleshooting by Remote Controller .. Mode Procedure of Self-diagnosis by Remote Controller .. Error Codes and Error Codes - Sub Error Code Indication by Outdoor Unit PCB .. Error of External Protection Indoor Unit PCB Abnormality.

7 Drain Water Level System Abnormality .. Indoor Unit Fan Motor Abnormality .. Swing Flap Motor Abnormality / Lock .. Abnormal Power Supply Voltage .. Electronic Expansion Valve Coil Abnormality .. Drain System Abnormality .. Capacity Setting Abnormality .. Transmission Error between Indoor Unit PCB and Fan Heat Exchanger (Liquid pipe) Thermistor Abnormality .. Heat Exchanger (Gas Pipe) Thermistor Abnormality .. Combination Error between Indoor Unit PCB and Fan 126 SiUS281117ivTable of Suction Air Thermistor Abnormality.

8 Humidity Sensor System Room Temperature Thermistor in Remote Controller Outdoor Unit PCB Abnormality .. High Pressure Abnormality .. Actuation of Low Pressure Inverter Compressor Motor Lock .. Outdoor Unit Fan Motor Abnormality .. Electronic Expansion Valve Coil Abnormality .. Discharge Pipe Temperature Control Refrigerant Overcharged .. High Pressure Switch System Outdoor Unit Fan Motor Signal Abnormality .. Thermistor System Abnormality .. High Pressure Sensor Abnormality .. Low Pressure Sensor Outdoor Unit PCB Abnormality.

9 Radiation Fin Temperature Rise .. Momentary Overcurrent of Inverter Compressor .. Electronic Thermal (Time Lag).. Inverter Startup Error .. Transmission Error (between Control and Inverter PCB).. Radiation Fin Thermistor Refrigerant Power Supply Voltage Check Operation not Executed .. Transmission Error (between Indoor Units and Outdoor Units) .. Transmission Error (between Remote Controller and Indoor Unit) .. Transmission Error (between Main and Sub Remote Controllers).. Transmission Error (between Centralized Remote Controller and Indoor Unit).

10 System is not Set yet .. Check .. 173 Part 7 Appendix .. 1821. Piping Indoor Unit + Outdoor Unit .. Indoor Unit .. 1852. Wiring Diagrams .. Outdoor Indoor Unit .. 189 Safety ConsiderationsSiUS281117v1. Safety Considerations Read these SAFETY CONSIDERATIONS carefully before performing any repair work. Comply with these safety symbols without of DANGER, WARNING, CAUTION, and NOTE Symbols:DANGER .. Indicates an imminently hazardous situation which, if not avoided, will result in death or serious.