259336-XTG-C-1208 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALEHIGH EFFICIENCYSINGLE PACKAGE heat PUMPSBP 090 & 1207-1/2 and 10 NOMINAL EERTECHNICALGUIDE TECHNICALGUIDE 50 HZ DESCRIPTIONYORK Predator heat pump units are convertible SINGLE pack-ages with a common footprint cabinet and common roof curb for all 7-1/2 and 10 ton models. The units were designed for light commercial applications and can be easily installed on a roof curb, slab, or Predator heat pump units are self-contained and assembled on rigid full perimeter base rails allowing for 3-way forklift access and overhead rigging. Every unit is completely charged, wired, piped, and tested at the factory to provide a quick and easy field units are convertible between side and down airflow. Indepen-dent economizer designs are used on side and down discharge applications, as well as all tonnage Controls Unitary ProductsTABLE OF CONTENTSDESCRIPTION.

259336-xtg-c-1208 for distribution use only - not to be used at point of retail sale high efficiency single package heat pumps bp 090 & 120 7-1/2 and 10 nominal tons

Tags:

  Pumps, Heat, Single, Packages, Single package heat pumps

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of SINGLE PACKAGE HEAT PUMPS - UPGNET

1 259336-XTG-C-1208 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALEHIGH EFFICIENCYSINGLE PACKAGE heat PUMPSBP 090 & 1207-1/2 and 10 NOMINAL EERTECHNICALGUIDE TECHNICALGUIDE 50 HZ DESCRIPTIONYORK Predator heat pump units are convertible SINGLE pack-ages with a common footprint cabinet and common roof curb for all 7-1/2 and 10 ton models. The units were designed for light commercial applications and can be easily installed on a roof curb, slab, or Predator heat pump units are self-contained and assembled on rigid full perimeter base rails allowing for 3-way forklift access and overhead rigging. Every unit is completely charged, wired, piped, and tested at the factory to provide a quick and easy field units are convertible between side and down airflow. Indepen-dent economizer designs are used on side and down discharge applications, as well as all tonnage Controls Unitary ProductsTABLE OF CONTENTSDESCRIPTION.

2 1 FEATURES .. 3 FACTORY INSTALLED OPTIONS .. 5 FIELD INSTALLED ACCESSORIES .. 6 NOMENCLATURE .. 7 LIST OF FIGURESFig. #Pg.#1 PREDATOR COMPONENT LOCATION ..32 UNIT 4 POINT LOAD ..253 UNIT CENTER OF GRAVITY ..254 UNIT 6 POINT LOAD ..255 UNIT DIMENSIONS ..266 PREDATOR ROOF CURB DIMENSIONS ..277 SUNLINE TO PREDATOR TRANSITIONROOF CURBS ..278 BOTTOM DUCT OPENINGS (FROM ABOVE) ..289 REAR DUCT DIMENSIONS ..2810 DOWNFLOW ECONOMIZER HOOD DETAIL ..2911 FACTORY INSTALLED DOWNFLOWECONOMIZER ..3012 FIELD INSTALLED DOWNFLOW ECONOMIZERW/POWER EXHAUST ..3013 FIELD INSTALLED HORIZONTAL ECONOMIZERW/POWER EXHAUST ..3114 SLAB ECONOMIZER DOWNFLOW W/POWER EXHAUST ..3115 SLAB ECONOMIZER END RETURN W/POWER EXHAUST ..3216 7-1/2 & 10 TON heat PUMP WITH OR WITHOUT ELECTRIC heat WIRING DIAGRAM ..33 LIST OF TABLESTbl. #Pg.

3 #1 PHYSICAL DATA ..82BP CAPACITY RATINGS ..83 COOLING CAPACITY 7-1/2 TON HP COOLIMPERIAL ..94 COOLING CAPACITY 7-1/2 TON HP COOLMETRIC ..105 COOLING CAPACITY 10 TON HP COOLIMPERIAL ..116 COOLING CAPACITY 10 TON HP COOLMETRIC ..127 HEATING APPLICATION DATA 7-1/2 TON HP heat (IMPERIAL) ..138 HEATING APPLICATION DATA 7 1/2 TON HP heat (METRIC) ..149 HEATING APPLICATION DATA 10 TON HP heat (IMPERIAL) ..15 Tbl. #Pg.#10 HEATING APPLICATION DATA 10 TON HP heat (METRIC) .. 1611 ELECTRICAL DATA - 7-1/2 TON HP .. 1712 ELECTRICAL DATA - 10 TON HP .. 1713 UNIT VOLTAGE LIMITATIONS .. 1714 ELECTRIC heat MULTIPLIERS .. 1715 BLOWER PERFORMANCE 7-1/2 TON STANDARD MOTOR - SIDE DUCT (IMPERIAL) .. 1816 BLOWER PERFORMANCE 7-1/2 TON STANDARD MOTOR - SIDE DUCT (METRIC) .. 1817 BLOWER PERFORMANCE 7-1/2 TON OPTIONAL MOTOR - SIDE DUCT (IMPERIAL).

4 1818 BLOWER PERFORMANCE 7-1/2 TON OPTIONAL MOTOR - SIDE DUCT (METRIC) .. 1919 BLOWER PERFORMANCE 10 TON STANDARD MOTOR - SIDE DUCT (IMPERIAL) .. 1920 BLOWER PERFORMANCE 10 TON STANDARD MOTOR - SIDE DUCT (METRIC) .. 1921 BLOWER PERFORMANCE 10 TON OPTIONAL MOTOR - SIDE DUCT (IMPERIAL) .. 2022 BLOWER PERFORMANCE 10 TON OPTIONAL MOTOR - SIDE DUCT (METRIC) .. 2023 BLOWER PERFORMANCE 7-1/2 TON STANDARD MOTOR - DOWNSHOT (IMPERIAL) .. 2124 BLOWER PERFORMANCE 7-1/2 TON STANDARD MOTOR - DOWNSHOT (METRIC) .. 2125 BLOWER PERFORMANCE 7-1/2 TON OPTIONAL MOTOR - DOWNSHOT (IMPERIAL) .. 2126 BLOWER PERFORMANCE 7-1/2 TON OPTIONAL MOTOR - DOWNSHOT (METRIC) .. 2227 BLOWER PERFORMANCE 10 TON STANDARD MOTOR - DOWNSHOT (IMPERIAL) .. 2228 BLOWER PERFORMANCE 10 TON STANDARD MOTOR - DOWNSHOT (METRIC) .. 2229 BLOWER PERFORMANCE 10 TON OPTIONAL MOTOR - DOWNSHOT (IMPERIAL).

5 2330 BLOWER PERFORMANCE 10 TON OPTIONAL MOTOR - DOWNSHOT (METRIC) .. 2331 ADDITIONAL STATIC RESISTANCE - IMPERIAL .. 2432 ADDITIONAL STATIC RESISTANCE - METRIC .. 2433 ELECTRIC heat MINIMUM SUPPLY AIR - MPERIAL .. 2534 ELECTRIC heat MINIMUM SUPPLY AIR - METRIC .. 2535 INDOOR BLOWER SPECIFICATIONS .. 2536 4 POINT LOAD WEIGHT .. 2537 6 POINT LOAD WEIGHT .. 2638 UNIT WEIGHTS .. 2639 UNIT CLEARANCES .. 2640 ECONOMIZER USAGE .. 29259336-XTG-C-1208 Johnson Controls Unitary Products3 FEATURES High Efficiency High efficiency units reach as high EER. Service Friendly The Predator incorporates a num-ber of enhancements which improve motor and blower slide out of the unit as a commonassembly. This facilitates greater access to all the indoorairflow components, thus simplifying maintenance time is reduced through the use of hinged, tool-less panels.

6 Such panels provide access to frequentlyinspected components and areas, including the controlbox, compressors, filters, indoor motor & blower, and theheating section. The panels are screwed in place at thefactory to prevent access by children or other unauthor-ized persons. It is recommended that the panels besecured with screws once service is windows have been placed in both condensersection walls. Rotation of the cover allows easy accessto the condenser coils for cleaning or unit control board utilizes flash codes to aid in diag-nosis of unit malfunctions. Unique flash codes quicklyidentify the source of the unit units use the same standard filter size. This stan-dardization removes any confusion on which filter sizesare needed for non-corrosive drain pan slides out of the unit to per-mit easy cleaning.

7 The drain pan is accessed by remov-ing the drain pan cover plate on the rear of the the plate is removed, the drain pan slides outthrough the rear of the Predator units have a second model nameplatelocated inside the control access door. This is to preventdeterioration of the nameplate through weathering. Environmentally Aware For improved Indoor AirQuality, foil faced insulation is used exclusively through-out the units. Convertible Airflow Design The side duct openingsare covered when they leave the factory. If a side sup-ply/return is desired, the installer simply removes the twoFIGURE 1 - PREDATOR COMPONENT LOCATIONC ompressor #1 Access (High-Eff Compressor)Tool-lessDoor LatchSide entry power and control wiring knockoutsSlide-out drain pain with steel 3/4 NPT ConnectionBelt-driveblower motorCondensersectionFilter drier (solid core)Filter access(2 throw-away)Disconnect location(optional disconnect switch)Compressor #2 Access (High-Eff Compressor)Simplicity Control board w/screw connectors for T-stat wiring and network connectionRoof curbs in eight- and fourteen-inch heights.

8 Roof curbs for transitioning from Sunline footprint to the BP series footprint are also available (field installed accessory)Base Rails w/ Forklift Slots (3 Sides) & Lifting HolesTerminal block for hi-voltage connectionDual stage cool-ing for maximum comfort (7-1/2 - 12-1/2 Only)Second Model Nameplate Inside Control DoorSlide-out motor and blower assembly for easy adjustment and Controls Unitary Productsside duct covers from the outside of the unit and installsthem over the down shot openings. No panel cutting isrequired. Convertible airflow design allows maximumfield flexibility and minimum inventory. System Protection - Suction line freezestats are suppliedon all units to protect against loss of charge and coil frost-ing when the economizer operates at low outdoor air tem-peratures while the compressors are running. Every unithas solid-core liquid line filter-driers and high and low-pressure switches.

9 Internal compressor protection is stan-dard on all compressors. Crankcase heaters are standardon reciprocating compressors. Scroll compressors do notrequire crankcase heaters. Phase Monitors are standardon units with scroll compressors. This accessory monitorsthe incoming power to the unit and protects the unit fromphase loss and reversed phase rotation. Advanced Controls - Simplicity control boards havestandardized a number of features previously availableonly as options or by utilizing additional controls. Low Ambient - An integrated low-ambient controlallows all units to operate in the cooling mode downto 0 F ( C) outdoor ambient without additionalassistance. Optionally, the- control board can beprogrammed to lockout the compressors when theoutdoor air temperature is low or when free coolingis available.

10 Anti-Short Cycle Protection - To aid compressorlife, an anti-short cycle delay is incorporated into thestandard controls. Compressor reliability is furtherensured by programmable minimum run times. Fortesting, the anti-short cycle delay can be temporarilyoverridden with the push of a button. Fan Delays - Fan on and fan off delays are fully pro-grammable. Furthermore, the heating and coolingfan delay times are independent of one another. Allunits are programmed with default values basedupon their configuration of cooling and heating. Safety Monitoring - The control board monitors thehigh and low-pressure switches, the freezestats andthe temperature limit switch on electric heat unit control board will alarm on compressorlockouts and repeated limit switch trips. Nuisance Trip Protection and Strikes - To preventnuisance trouble calls, the control board uses a three times, you re out philosophy.