Surgelogic Surge Protective Device I- line Plug-On Unit Series Catalog 1310CT0201R05/09. 2009. Class 1310. CONTENTS. Description .. Page Product Description .. 2. Application Information.. 3. Selection and Specifications.. 4. Replacement Parts.. 6. Dimensions and Weights .. 7. Courtesy of Steven Engineering, Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) Surgelogic Surge Protective Device Product Description Product Description Surge Protective Device (SPD) units protect electronic equipment from transients. The I- line Plug-On Unit with Surgelogic Surge Protective Device (SPD) is a modular parallel Surge Protective Device designed for service entrance, distribution, or branch panel applications.

Surgelogic® Surge Protective Device I-Line® Plug-On Unit Series Catalog 1310CT0201R05/09 2009 Class 1310 CONTENTS Description . . …

Tags:

  Devices, Line, Protective, Surge, Surge protective device

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Surgelogic Surge Protective Device - Steven …

1 Surgelogic Surge Protective Device I- line Plug-On Unit Series Catalog 1310CT0201R05/09. 2009. Class 1310. CONTENTS. Description .. Page Product Description .. 2. Application Information.. 3. Selection and Specifications.. 4. Replacement Parts.. 6. Dimensions and Weights .. 7. Courtesy of Steven Engineering, Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) Surgelogic Surge Protective Device Product Description Product Description Surge Protective Device (SPD) units protect electronic equipment from transients. The I- line Plug-On Unit with Surgelogic Surge Protective Device (SPD) is a modular parallel Surge Protective Device designed for service entrance, distribution, or branch panel applications.

2 The Device is a multi-stage suppression circuit consisting of field-proven, fast-acting 34 mm metal oxide varistors (MOVs). Each MOV is thermally protected for low current faults, and each module is fused. The I- line plug-on unit with a Surgelogic Surge Protective Device is a high performance Surge suppressor package incorporating individual modules for each phase. Modes of protection include: line -to-Neutral (L N). line -to-Ground (L G). Neutral-to-Ground (N G). line -to- line (L L). A filter provides EMI/RFI noise filtering. The suppression elements are encapsulated in a UL Recognized thermosetting epoxy material another I- line Plug-On Unit with Surgelogic SPD performance element that provides additional protection.

3 Each Surge suppression module is individually fused and uses circuitry with thermal cutouts to isolate the SPD and ensure shutdown in the event of MOV damage during severe overvoltages even when operated on high fault current power systems. Online diagnostics continuously monitor the unit status, and LEDs signal a loss of a suppression circuit. An audible alarm with an enable/disable feature and dry contacts are included in the standard diagnostic package. Design Features Same easy installation as I- line circuit breakers Requires in. (343 mm) of mounting space FC units mount in the same mounting slots as FA circuit breakers. FI units mount in the same mounting slots as KA circuit breakers Can be applied in a six-disconnect panel or switchboard (SPD counts as one disconnect).

4 High-energy parallel design for ANSI/IEEE and category B and C3 applications. 2. 06/2009 2009 Schneider Electric All Rights Reserved Courtesy of Steven Engineering, Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) Surgelogic Surge Protective Device Application Information Application Information The effects of lightning and the damage caused by lightning-generated transients are well known. The failure of electronic equipment in a facility located in a high lightning area can easily be attributed directly to lightning-generated transients. Transient protection can be installed on the power distribution system to protect this equipment from these externally generated transients.

5 Lower magnitude transients generated within a facility and their effect on microprocessor-based equipment are less obvious than the transients induced by lightning. Transient voltage generated from inductive motors, pumps, electric welders, etc., may not be large enough to cause immediate damage, but they can cause equipment to malfunction. A damaging transient voltage can enter a facility from several locations. The highest level of protection should be provided at the service entrance. A second level of protection should be provided at distribution points serving critical areas, for example, computer rooms, accounting areas, and laboratories. Other facility entry points that should be protected include panels serving outdoor lights, or outdoor equipment such as motors.

6 Protection should also be provided for critical areas with equipment essential to the company. Square D brand SPD products offered by Schneider Electric provide protection at every level of the electrical distribution system. Typical applications include: Banking Transportation Retail Education Wastewater/Sanitation Utility Government Medical Insurance Petrochemical Financial Data Processing Military Telecommunications Publishing Automated Manufacturing 3. 2009 Schneider Electric 06/2009. All Rights Reserved Courtesy of Steven Engineering, Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) Surgelogic Surge Protective Device Selection and Specifications Selection and Specifications Model Number Format The model number format consists of: Device Type, Voltage Code, SPD.

7 FC 4 IMA 16 C. Model, Surge Current Rating Code, and Option Code. The possible Device types and codes are shown in the tables below. Option Code In the example at left, FC4 IMA16C is an integral suppressor for 480Y/ 277 Vac Surge Current Rating Code 3-phase 4-wire 160 kA Surge capacity with Surge counter. SPD Model (IMA only). Voltage Code Specifications Device Type Device Types, Interrupting Ratings, and Continuous Current Ratings Interrupting Rating Device Continuous Type at 240 Vac at 480 Vac at 600Y/347 Vac Current Rating FC 100 kA 65 kA 60 A. FI 200 kA 200 kA 100 kA 60 A. Voltage Codes and Systems Voltage Code Voltage System 1 120/240 Vac 1-phase, 3-wire 2 208Y/120 Vac 3-phase, 3- or 4-wire 3 240/120 Vac 3-phase, 4-wire (high leg Delta).

8 4 480Y/277 Vac, 3-phase, 3- or 4-wire 7 380Y/220 or 415Y/240 Vac, 3-phase, 3- or 4-wire 8 600Y/347 Vac, 3-phase, 3- or 4-wire Surge Current Rating Codes and Surge Capacities Per Mode Surge Current Rating Code Per Phase L N L G N G. 12 120 kA 60 kA 60 kA 120 kA. 16 160 kA 80 kA 80 kA 120 kA. 24 240 kA 120 kA 120 kA 120 kA. Descriptions and Option Codes Option Description Option Code Displays the combined total number of transient Surge counter voltage surges detected from L N, L G, N G, and C. L L since the counter was last reset. Displays the alarm status of the Surge Protective Order catalog Remote monitor Device up to 1000 ft (305 m) away from the unit. This number option uses the dry contacts.

9 TVS12 RMU. Dry contacts Provides available Form C type contacts. Standard Audible alarm with Provides audible indication that there is a loss of Standard enable/disable switch protection. 4. 06/2009 2009 Schneider Electric All Rights Reserved Courtesy of Steven Engineering, Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) Surgelogic Surge Protective Device Selection and Specifications UL Suppression Voltage Ratings IMA Series Voltage Specifications UL Suppression Voltage Rating (SVR). Partial Catalog Voltage Service L N L G N G L L MCOV . Number FC1 IMA 120/240 Vac, 400 400 400 800 150. FI1 IMA 1-phase, 3-wire FC2 IMA 208Y/120 Vac, 400 400 400 800 150.

10 FI2 IMA 3-phase, 3- or 4-wire 240/120 Vac, FC3 IMA. 3-phase, 4-wire 800/400 800/400 400 1500/800 275/150. FI3 IMA. (high leg Delta). FC4 IMA 480Y/277 Vac, 800 800 800 1600 320. FI4 IMA 3-phase, 3- or 4-wire FC7 IMA 380Y/220 Vac 800 800 800 1600 320. FI7 IMA 3-phase, 3- or 4-wire 600Y/347 Vac, FI8 IMA 1200 1200 1200 2000 420. 3-phase, 3- or 4-wire Surgelogic I- line Plug-on SPD Unit MCOV = Maximum Continuous Operating Voltage. Not available as FC Device . Standard Features and Descriptions Feature Description Relative humidity: 0 to 95% non condensing Operating frequency: 47 63 Hz Environmental Surge suppression operating temperature: -40 +65 C (-40 +149 F) . Storage temperature: -40 +65 C (-40 +149 F).