KL-3022 Technical Documentation2-Channel AnalogInput Terminal 4 20mAPlease keep for further use !Edition date/Rev. no.:TRS - V - BA - GB - 0108 - 00 Software :KOHTRS ystemtechnik GmbHEglishalde 6D-78647 TrossingenGermanyTel.+49 - (0) 7425 / 228-0 Fax+49 - (0) 7425 / 228-34 Technical Documentation KL-3022TR - Systemtechnik GmbH, Eglishalde 6, 78647 Trossingen, Tel. +49 - (0) 7425-228-0, Fax +49 - (0) 7425-228-34 Date: - V - BA - GB - 0108 - 00 Page 2 of 18 ImprintTRSystemtechnik GmbHD-78647 TrossingenEglishalde 6 Tel.:(++49) 07425/228-0 Fax:(++49) 07425/228-34 Copyright 1998 TRSystemtechnikGuaranteeIn our ongoing efforts to improve our products, TRSystemtechnik reserve the right toalter the information contained in this document without prior manual was edited using text formatting software on a DOS personal text was printed in and bold type are used for the title of a document or to emphasize text written in Courier show text which is visible on the display as well assoftware menu selectio

KL-3022 Technical Documentation 2-Channel Analog Input Terminal 4 – 20mA Please keep for further use ! Edition date/Rev. date: 23.03.1998 Document no./Rev. no.: TRS - V - BA - GB - 0108 - 00

Tags:

  1080, Input, Analog, Analog input

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Technical Documentation 2-Channel Analog Input Terminal 4 ...

1 KL-3022 Technical Documentation2-Channel AnalogInput Terminal 4 20mAPlease keep for further use !Edition date/Rev. no.:TRS - V - BA - GB - 0108 - 00 Software :KOHTRS ystemtechnik GmbHEglishalde 6D-78647 TrossingenGermanyTel.+49 - (0) 7425 / 228-0 Fax+49 - (0) 7425 / 228-34 Technical Documentation KL-3022TR - Systemtechnik GmbH, Eglishalde 6, 78647 Trossingen, Tel. +49 - (0) 7425-228-0, Fax +49 - (0) 7425-228-34 Date: - V - BA - GB - 0108 - 00 Page 2 of 18 ImprintTRSystemtechnik GmbHD-78647 TrossingenEglishalde 6 Tel.:(++49) 07425/228-0 Fax:(++49) 07425/228-34 Copyright 1998 TRSystemtechnikGuaranteeIn our ongoing efforts to improve our products, TRSystemtechnik reserve the right toalter the information contained in this document without prior manual was edited using text formatting software on a DOS personal text was printed in and bold type are used for the title of a document or to emphasize text written in Courier show text which is visible on the display as well assoftware menu selections.

2 "< >" refers to keys on your computer keyboard ( <RETURN>).NoteText following the "NOTE" symbol describes important features of the Information MS-DOS is a registered trademark of Microsoft Documentation KL-3022TR - Systemtechnik GmbH, Eglishalde 6, 78647 Trossingen, Tel. +49 - (0) 7425-228-0, Fax +49 - (0) 7425-228-34 Date: - V - BA - GB - 0108 - 00 Page 3 of 18 Revision HistoryNote:The cover of this document shows the current revision status and the correspondingdate. Since each individual page has its own revision status and date in the footer,there may be different revision statuses within the Documentation KL-3022TR - Systemtechnik GmbH, Eglishalde 6, 78647 Trossingen, Tel.

3 +49 - (0) 7425-228-0, Fax +49 - (0) 7425-228-34 Date: - V - BA - GB - 0108 - 00 Page 4 of 18 Table of contents2-Channel 4 to 20 mA Analog Input Terminal of communication Documentation KL-3022TR - Systemtechnik GmbH, Eglishalde 6, 78647 Trossingen, Tel. +49 - (0) 7425-228-0, Fax +49 - (0) 7425-228-34 Date: - V - BA - GB - 0108 - 00 Page 5 of 182-Channel 4 to 20 mA Analog Input Terminal KL3022 Technical DataKL3022 Number of inputs2 Power supplyvia the K-BusSignal current0 .. 20 mAInternal resistance50 mode voltage UCM35 VResolution12 bitsTotal conversion time~ 2 msElectrical isolation500 V rms (K-bus / signal voltage)Current consumption60 mA widtth in the process imageI: 2 x 16 bits, (2 x 8 bits control/status can be optionally inserted)Configurationno address or configuration settingWeight approximately70 gOperating temperature0 C.

4 +55 CStorage temperture-25 C .. +85 CRelative humidity95% no condensationVibration/shock resistanceIn accordance with IEC 68-2-6 / IEC 68-2-27 EMC resistance burst/ESDIn accordance with EN 61000-4-4 / EN 61000-4-2 Limits to EN 50082-2 Installation positionanyDegree of protectionIP20 Technical Documentation KL-3022TR - Systemtechnik GmbH, Eglishalde 6, 78647 Trossingen, Tel. +49 - (0) 7425-228-0, Fax +49 - (0) 7425-228-34 Date: - V - BA - GB - 0108 - 00 Page 6 of 18 Description of functionsThe Analog Input Terminal KL3022 processes signals within the range from0 20 mA with a resolution of 12 bits (4096 increments). The inputs of theKL3022 are differential inputs which share a common earth.

5 As aresult theKL3022 is ideally suited to measuring earth free current loops. A voltagedifference at the inputs, due cross voltages, of up to 35 V result in anegligible inconsentency in the measured value of the formatof process dataIn the default setting, process data is represented in the twos complement(-1 corresponds to 0xFFFF). By way of the feature register, other modes ofrepresentation can be selected ( amount representation,Siemens output format).Measured valueDecimal outputHexadecimal output4mA00x000012mA163830x3 FFF20mA327670x7 FFFLED displayThe four RUN LEDs indicate the operating state of the affiliated LEDs: RUN:On normal opeationOff a watchdog-timer overflow has occurred.

6 The green LEDs go off if noprocess data is transferred by the bus coupler for 100 LEDs: EROROn The end stop of the ADC-Converter is reached. The current is higherthan normal operationProcess dataThe process data that is transferred to the bus coupler is calculated on thebasis of the following equations:X_adc: AD convertor output valuesY_aus : Process data to the PLCB_a,A_a :Manufacturer gain und offset adjustment (R17,R18)B_h,A_h : Manufacturer scaling (R19,R20)B_w,A_w : User scaling(R33,R34)a) neither user nor manufacturer scaling active:Y_a = (B_a+X_adc)* A_a ( )Y_aus =Y_ab) Manufacturer scaling active: (default)Y_1 =B_h + A_h * Y_a ( )Y_aus= Y_1 Technical Documentation KL-3022TR - Systemtechnik GmbH, Eglishalde 6, 78647 Trossingen, Tel.

7 +49 - (0) 7425-228-0, Fax +49 - (0) 7425-228-34 Date: - V - BA - GB - 0108 - 00 Page 7 of 18c) User scaling active:Y_2 =B_w + A_w * Y_a ( )Y_aus= Y_2d) Manufacturer and user scaling active:Y_1 = B_h + A_h * Y_a ( )Y_2 =B_w + A_w * Y_1 ( )Y_aus = Y_2 The straight-line equations are activated by means of scalingmanuf. , Offset bitsTerminal configurationThe Terminal can be configured and parametrized by way of the internalregister Terminal channel is mapped in the bus coupler. The Terminal s data ismapped differently in the bus coupler s memory depending on the type ofthe bus coupler and on the set mapping configuration ( / Intelformat, word alignment,..). For parametrization of a Terminal , the control/status byte must also be LightbusCoupler BK2000In the case of the TRS Lightbus coupler BK2000, the control /status byte isalways mapped besides the data bytes.

8 It is always in the low byte at theoffset address of the Terminal Terminal1 Channel1 = 0 Offset Terminal2 Channel1 = 4KL3022 Offset Terminal2 Channel2 = 8 User data allocation dependingon mappingK-BusTRS-Lightbusbus couplerBK2000To the bus terminalLHC/S - 0D0 - 0D0 - 1D1 - 0D1 - 1C/S - 1C/SC/SData LData HData HData LC/SThe Terminal ismapped in thebus Documentation KL-3022TR - Systemtechnik GmbH, Eglishalde 6, 78647 Trossingen, Tel. +49 - (0) 7425-228-0, Fax +49 - (0) 7425-228-34 Date: - V - BA - GB - 0108 - 00 Page 8 of 18 Profibus Coupler BK3000In the case of the Profibus coupler BK3000, for which Terminal channelsthe control /status byte is also to be inserted must be defined in the masterconfiguration.

9 If the control /status byte is not evaluated, the KL3022occupies 4 bytes of Input data (2 bytes of user data per channel).Offset Terminal1 Channel1 = 0 Offset Terminal1 Channel2 = 3 Offset Terminal2 Channel1 = 6KL 3022 Channel1KL 3022 Channel 2 The control-/status byte must be inserted for bus couplerBK3000To the bus terminalData HData LD1 - 0D0 - 0D0 - 1D1 - 1C/S - 0C/SC/S - 10 The Terminal ismapped in the bus Coupler BK4000By default, the Interbus coupler BK4000 maps the KL3022 with 4 bytes ofinput data (2 bytes of user data per channel). Parametrization via the fieldbus is not possible. The KS2000 software is required for configuration ifuse is to be made of the control /status Terminal1 Channel1 = 0 Offset Terminal2 Channel1 = 4 Offset Terminal1 Channel2 = 2 Offset Terminal2 Channel1 = 6 The control/status bytemust be inserted forparameterization (KS2000).

10 K-BusInterbus bus couplerBK4000To the bus terminalD0 - 1D0 - 0 Data HData HData HD1 - 0D1 - 1 Data LData L0 The Terminal ismapped in thebus bus couplers andfurther informationYou will find further information on the mapping configuration of buscouplers in the annex of the respective bus coupler manual under theheading of "Configuration of masters".ReferenceThe annex contains an overview of the possible mapping configurationsdepending on the adjustable with theKS2000 softwareParametrization operations can be carried out independantly of the fieldbus system using the TRS KS2000 configuration software via the serialconfiguration interface in the bus Documentation KL-3022TR - Systemtechnik GmbH, Eglishalde 6, 78647 Trossingen, Tel.