Example: quiz answers

TECHNICAL GUIDE R-410A Description ZF SERIES 7-1/2 THRU 12 ...

862075-XTG-F-0513.. TECHNICAL GUIDE . R-410A Description ZF SERIES ASHRAE COMPLIANT. YORK Predator units are convertible single packages 7-1/2 THRU 12-1/2 TON with a common footprint cabinet and common roof curb for all 7-1/2 through 12-1/2 ton models. All units have two 50 Hz (Export) compressors with independent refrigeration circuits to provide 2 stages of cooling. The units were designed for light commercial applications and can be easily installed on a roof curb, slab, or frame. All Predator units are self-contained and assembled on rigid full perimeter base rails allowing for 3-way forklift access and overhead rigging. Every unit is completely charged, wired, piped, and tested at the factory to provide a quick and easy field installation. All units are convertible between side and down airflow.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE 862075-XTG-F-0513 TECHNICAL GUIDE Description ASHRAE 90.1 COMPLIANT YORK® Predator® units are convertible single packages with a common footprint cabinet and common roof curb for

Tags:

  Guide, Cabinets, Technical, Technical guide

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of TECHNICAL GUIDE R-410A Description ZF SERIES 7-1/2 THRU 12 ...

1 862075-XTG-F-0513.. TECHNICAL GUIDE . R-410A Description ZF SERIES ASHRAE COMPLIANT. YORK Predator units are convertible single packages 7-1/2 THRU 12-1/2 TON with a common footprint cabinet and common roof curb for all 7-1/2 through 12-1/2 ton models. All units have two 50 Hz (Export) compressors with independent refrigeration circuits to provide 2 stages of cooling. The units were designed for light commercial applications and can be easily installed on a roof curb, slab, or frame. All Predator units are self-contained and assembled on rigid full perimeter base rails allowing for 3-way forklift access and overhead rigging. Every unit is completely charged, wired, piped, and tested at the factory to provide a quick and easy field installation. All units are convertible between side and down airflow.

2 Independent economizer designs are used on side and down discharge applications, as well as all tonnage sizes. Predator units are available in the following configurations: cooling only, cooling with electric heat, and cooling with gas heat. Electric heaters are available as factory-installed options or field-installed accessories. All units provide constant supply air volume. ZF 7-1/2 AND 10 TON. ZF 12-1/2 TON. FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE. 862075-XTG-F-0513. Table of Contents Description .. 1. Table of Contents .. 2. Component Location .. 2. Nomenclature .. 3. Features and Benefits .. 4. GUIDE Specifications .. 10. Physical Data .. 14. Capacity Performance .. 17. Airflow Performance .. 29. Sound Performance .. 40. Electrical Data .. 41. Typical Wiring Diagrams.

3 42. Weights and Dimensions .. 46. Economizer Options .. 55. Component Location Cooling With Gas Heat Simplicity control board Filter Access w/screw connector for T-stat Disconnect location (2 or 4 filter options) Filter drier wiring and network connections (optional disconnect switch) (solid core). Terminal block for ZF SERIES utilize Micro-Channel hi-voltage connection Aluminum Tube/Aluminum Fin Condenser Second model nameplate Slide-out motor and inside hinged blower assembly for access panel easy adjustment and service Dual stage Belt-drive cooling for blower motor maximum comfort Power ventor motor Compressor #2. access (high- 20-gauge alumi- efficiency nized steel tubular compressor heat exchanger for w/crankcase long life (stainless heater) steel option). Two-stage gas Base rails w/forklift heating to maintain slots (three sides) warm, comfortable and lifting holes Slide-out drain pan temperature with 3/4 NPT, Roof curbs in eight- and female connection Intelligent control fourteen-inch heights.

4 Roof board for safe and curbs for transitioning from efficient operation Side entry power Compressor #1 access York Sunline footprint to Toolless (high-efficiency compressor the ZF SERIES footprints and control wiring door latch knockouts w/crankcase heater). are also available (field installed accessory). 2 Johnson Controls Unitary Products 862075-XTG-F-0513. Nomenclature Ton York Model Number Nomenclature Z F 090 N10 A 7 A AA 5 0 1 2 4 A. Product Category Product Style Z = A/C, Single Pkg., R410A A = Style A. Product Identifier Configuration Options (not required for all units). These four digits will not be assigned until a quote is requested, or an order placed. F = EER & 10 Ton A/C. EER Ton A/C SS Drain Pan Honeywell Controller, DFS, APS. Nominal Cooling Capacity Simplicity IntelliComfort Controller Simplicity IntelliComfort Controller w/ModLinc 090 = Ton 2" Pleated Filters, MERV 7.

5 120 = Ton 150 = Ton 4" Pleated Filters, MERV 13. BAS Ready Unit with Belimo Economizer Heat Type and Nominal Heat Capacity Shipping Bag Any Combination of Additional Options that Don't Have an Option Code Pre-assigned C00 = Cooling Only. No heat installed Gas Heat Options*. Product Generation N10 = 100 MBH Output Aluminized Steel N15 = 150 MBH Output Aluminized Steel 5 = Fifth Generation N20 = 200 MBH Output Aluminized Steel S10 = 100 MBH Output Stainless Steel S15 = 150 MBH Output Stainless Steel Additional Options S20 = 200 MBH Output Stainless Steel * N10/S10 Not Available on ZF120/150 AA = None RC = Coil Guard & American Flag AB = Phase Monitor TA = Technicoat Condenser Coil Electric Heat Options* AC = Coil Guard TJ = Technicoat Evaporator Coil AD = Dirty Filter Switch TS = Technicoat Evaporator & Condenser Coils E18 = 18 KW AE = Phase Monitor & Coil Guard EA = ElectroFin Condenser Coil E24 = 24 KW AF = Phase Monitor & Dirty Filter Switch EJ = ElectroFin Evaporator Coil E36 = 36 KW AG = Coil Guard & Dirty Filter Switch ES = ElectroFin Cond & Evap Coils

6 E54 = 54 KW AH = Phase Monitor, Coil Guard & Dirty Filter Switch * No Electric Heat Options for ZF090. ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be Airflow located in digits 15-18. A = Std. Motor B = Std. Relief (Downflow Installation Options Only). C = Std. Exhaust (Downflow Only) A = No Options Installed D = Std. Motor/Motorized Damper (Downflow Only) B = Option 1. E = Std. Motor/Horizontal Economizer (No Baro.) E = Option 3. F = Std. Motor/Slab Exhaust F = Option 4. (Downflow Only). G = Options 1 & 3. G = Std. Motor/Slab Relief H = Options 1 & 4. (Downflow Only). L = Options 1,3 & 4. N = Hi Static Mtr.**. P = Hi Static Relief R = Options 3 & 4. (Downflow Only). Q = Hi Static Exhaust Options (Downflow Only). R = Hi Static Damper (Downflow Only) 1 = Disconnect S = Hi Static Economizer (No Baro.)

7 3 = Smoke Detector T = Hi Static Exhaust 4 = Smoke Detector (Downflow Only). U = Hi Static Relief (Downflow only) Voltage ** Only Hi Static Is Offered On ZF150 7 = 380/415-3-50. Johnson Controls Unitary Products 3. 862075-XTG-F-0513. Features and Benefits when the economizer operates at low outdoor air temperatures while the compressors are running. Every unit Standard Features has solid-core liquid line filter-driers and high and low- High Efficiency High efficiency units reach as high as pressure switches. Internal compressor protection is EER. Gas/electric units have electronic spark ignition standard on all compressors. Crankcase heaters are and power vented combustion with steady state efficiencies standard on reciprocating compressors. Scroll compressors of 80%. These efficiencies exceed all legislated minimum do not require crankcase heaters.

8 Phase Monitors are levels and provide low operating costs. standard on units with scroll compressors. This accessory monitors the incoming power to the unit and protects the Service Friendly The Predator incorporates a number unit from phase loss and reversed phase rotation. of enhancements which improve serviceability. Advanced Controls - Simplicity control boards have The motor and blower slide out of the unit as a common standardized a number of features previously available assembly. This facilitates greater access to all the indoor only as options or by utilizing additional controls. airflow components, thus simplifying maintenance and adjustment. Low Ambient - An integrated low-ambient control Service time is reduced through the use of hinged, allows all units to operate in the cooling mode down to toolless panels.

9 Such panels provide access to frequently 0 F outdoor ambient without additional assistance. inspected components and areas, including the control Optionally, the control board can be programmed to box, compressors, filters, indoor motor & blower, and the lockout the compressors when the outdoor air tem- heating section. The panels are screwed in place at the perature is low or when free cooling is available. factory to prevent access by children or other unauthorized persons. It is recommended that the panels be secured with screws once service is complete. Service windows have been placed in both condenser section walls. Rotation of the cover allows easy access to The Simplicity control board used in this product the condenser coils for cleaning or inspection. will effectively operate the cooling system down to Both the unit control board and ignition control board utilize 0 F when this product is applied in a comfort cooling flash codes to aid in diagnosis of unit malfunctions.

10 Unique application for people. An economizer is typically alarm codes quickly identify the source of the unit alarm. included in this type of application. When applying this product for process cooling applications (com- All units use the same standard filter size. This puter rooms, switchgear, etc.), please reference standardization removes any confusion on which filter applications bulletin AE-011-07 or call the applica- sizes are needed for replacement. tions department for Unitary Products @ 1-877- The non-corrosive drain pan slides out of the unit to permit UPG-SERV for guidance. Additional accessories easy cleaning. The drain pan is accessed by removing the may be needed for stable operation at temperatures drain pan cover plate on the rear of the unit. Once the plate is below 30 F. removed, the drain pan slides out through the rear of the unit.