Transcription of Technical Information Process Display RIA 250
1 Process DisplayRIA 250 Multifunctional 1 channel Display withuniversal input, loop power supply, alarm limits,and analog outputApplication Areas Plant and machine construction Control panels Laboratory fittings Temperature Display and monitoring Process Display and monitoring Process control Signal match and transformingAdvantages Multi functional:All normal measurement signals canbe directly connected (bipolar voltageand current, thermocouple, RTD) Display :Active numeric measured valuedisplay with bar graph Alarm:Flexible set point monitor with2 relay contacts Active:Adjustable current or voltage analogoutput Power:Integrated loop power supply forconnected sensors Communicative:RS 232 interface for set-upconfiguration and measured valueoutputTechnical InformationTI 060R/24/aeThe Power of Know How2 FunctionsThe presettable universal input enablesdirect connection of various sensors,including current, voltage, RTD andthermocouples.
2 Using the built-in looppower supply, the RIA 250 can power aconnected sensor, and then it canevaluate its signal to the RIA 250. Twopresettable alarm set points monitor themeasured value for any deviation fromthe preset adjustable analog output offers aninstrument from which a matched signalfor further analysis equipment can beobtained. Simple configuration isavailable directly at the RIA 250 via a control is simplified with theRIA 250 which can transmit power to atransmitter, receive and indicate auniversal input, and transmit an analogoutput signal (optional) or communicatevia withReadWin 2000 PCSoftwareThe RIA 250 can be set up extremelyeasily using the built-in RS 232 serialinterface and the Endress+HauserReadWin 2000 PC software. Safe andsecure set-up is made possible via on-line help text. ReadWin 2000 softwareand interface cable are Features Compatible with Windows 95/98/2000/NT/XP/CE PC operatingsystem Storage of unit settings in a data bank Instantaneous value Display Printout of unit settingsAlarm limitindicators5-digit LED display12-segment LEDbargraph displaySelectionpushbuttonsEnterpushbutt on3 LinearizationThe RIA 250 Display has a built inlinearization function.
3 It is possible forthe user to set up a connection betweenthe input signal and the value to bedisplayed on the unit. These points canbe set up using the 3 front mounted pushbuttons, or they can be easily definedand transmitted using the ReadWin2000 operator :Linearization of a vessel signal thatdescribes the relationship between thefilling height and the vessel OutputTransmitterAlarm LimitsThe RIA 250 Display can be fitted with ananalog output (optional). The outputsignal is proportional to the displayedmeasured value and the bargraphdisplays the input signal Features Current/Voltage output Galvanic isolation Infinite scaling within the displayrange Presettable fault operation to NAMUR recommendation NE43 Invertable measurement signal outputUsing the linearization function and theanalog output, the RIA 250 processdisplay can also be applied as an easy-to-use amplifier.
4 The large number ofalready stored temperature linearizationtables as well as a square root functioncan be easily selected from the :The signal from a temperature sensor isconnected to the input of the unit, thenlinearized and displayed as a tempera-ture analog output is made available toother instrumentation ( data loggersor recorders) as a current or voltagesignal proportional to the additional limit function monitors themeasured signal once per second toverify that the preset parameters havebeen limits can be individually set-up forminimum or maximum security, as a highor low limit with presettable hysteresis aswell as being able to define a switchtime delay. The set point infringement isindicated using 2 LEDs. An optionaloutput relay can be hVol ume V20%30%100%5%10%15%20%100%40%ENDRESS+HAU SERRIA250 LIMIT 1 LIMIT 24 DimensionsElectrical "(92 mm) "(45 mm) "(96 mm)Panel "(48 mm) "(150 mm) "(9 mm)ENDRESS+HAUSERRIA250 LIMIT 1 LIMIT 2L/++N/-4142 4351525311111213141516++++++RS232 Relays 1 and 2(max.)
5 250 VAC, 3A)AnalogOutput2-wire transmitterloop power supply24 VDC, 30 mAVoltage input 100 mVCurrent input 20 mA0/4 to 20 mAThermocouplesRTD2-wireRTD3-wireRTD4-wi reVoltage input 10 V,0 to 1 V or 0 to 10 VPower Supply90 to 253 VAC50/60 HzPower Supply18 to 36 VDCor 24 VAC 15%5 Technical DataGeneralApplicationOperation and SystemConstructionManufacturerEndress+Ha userDescriptionRIA 250 ApplicationProcess Display for panel mountingProcess Display ,The Display receives an analog signal and shows the corre-Transmittersponding value on the Display . The analog output transmits thisdisplayed value either as a current or voltage. Two presettablelimit values monitor the measured value for any infringement ofthe preset conditions and control the two output relays. Aconnected transmitter can be directly powered by the analog signal is digitized, analyzed aand indicated on thedisplay.
6 A digital analog convertor makes a proportional currentor voltage signal available for additional peripheral equipment atthe output terminalsMeasurement SystemMicrocontroller controlled Display with LED Display , analog input,analog output, limit relays and loop power supplyInput TypesVoltage, current, resistive thermometer (RTD), andthermocouple (TC)Measurement RangesVoltage: 100 mV, maximum 5 V 10 V, maximum 50 VRi = 1 M Current:0/4 to 20 mA, maximum 200 mA, Ri = 5 RTD:Pt 100, -328 to +1562 F (-200 to +850 C,DIN EN60751)Ni 100, -76 to +356 F (-60 to +180 C, DIN43760)Sensor current, approximately 250 A, pulsedConnection; 2-wire, 3-wire, 4-wireCable compensation, 40 Thermocouple:Type T, -454 to +752 F (-270 to +400 C)Type J, -346 to +2192 F (-210 to +1200 C)Type K, -328 to +2502 F (-200 to +1372 C)Type R, -58 to +3272 F (-50 to +1800 C)Type S, +32 to +3272 F (0 to +1800 C)Type B, +32 to +3308 F (0 to +1820 C)Type N, -454 to +2372 F (-270 to +1300 C)Type U, -328 to +1112 F (-200 to +600 C)Type L, -328 to +1652 F (-200 to +900 C)Type W3, +32 to +4199 F (0 to + 2315 C)Type W5, +32 to +4199 F (0 to + 2315 C)Type T, J, K, R, S, B, N to DIN EN60584 Type U, L to DIN 43710.
7 Type W3, W5 to ASTME988-96 LinearizationUp to 32 points maximumIntegration Time1 secondLoop Power Supply24 V, 20%, 30 mANumber of Outputs1 Galvanic IsolationTo all other current circuitsOutput Signal0/4 to 20 mA, 20 to 4/0 mA or 0 to 10 V, 10% over rangeVoltageOutput current maximum, 20 mACurrentLoad maximum 500 Fault MessagePresettable mA or 21 mA. Actions to NAMUR recommendation NE43D/A ResolutionCurrent; 13 bit; voltage, 15 bitNumber of Outputs1 Galvanic IsolationTo all other current circuitsOutput SignalBinary, switches when set point is reachedNumber of Relays2 Contact TypeSPDTC ontact Load< = maximum 250 VAC, 3 AInputOutputOptional Analog OutputOptional Relay of end valueTemperature drift, / 10K ambient of end valueTemperature drift, / 10K ambient temperatureRTD2-wire, F ( C)3-wire, F ( C)4-wire, F ( C)Temperature drift, / 10K ambient temperatureThermocoupleType T: F ( C);T < -238 F, F (T < -150 C, C)Type J: F ( C).
8 T < -238 F, F (T < -150 C, C)Type K: F ( C)Type R: F ( C)Type S: F ( C)Type N: F ( C)Type B: T > 752 F, F (T > 400 C, C)Type U: F ( C)Type L: F ( C)Type W3: F ( C)Type W5: F ( C)Temperature drift, / 10K ambient temperatureAnalog of end valueTemperature drift, / 10K ambient temperatureThermocouple Cold F ( C)JunctionResolution, F ( C)Ambient Temperature15 to 120 F (-10 to + 50 C)Storage Temperature-20 to +155 F (-30 to + 70 C)Climatic ClassTo EN 60654-1 Class B2 Ingress ProtectionNEMA 4 (IP 65) front; NEMA 1 (IP 20) for terminalsRFI ProtectionTo EN 55011 Group 1, Class ANormal SafetyTo EN 61010-1 protection Class 1, overvoltage catagory II,installation over current protection 10 AESDTo EN 61000-4-2, 6kV/8kVElectromagnetic FieldsTo EN 61000-4-3, 10 V/mBurst (supply)To EN 61000-4-4, 4 kVBurst (signal)To EN 61000-4-4, 4 kVSurge (AC supply)To EN 61000-4-5, sym.
9 1 kV, unsym. 2 kVSurge (DC supply)To EN 61000-4-5, sym. kV, unsym. 1 kVCable High FrequencyTo EN 61000-4-6, 10 VCommon Mode NoiseRejection80 dB at 60 V, 50/60 HzNormal Mode NoiseRejection60 dB at input range 1/10, 50/60 HzDimensionsH, (48 mm); W, (96 mm); D, (150 mm) lbs (600 g)MaterialsHousing front, die cast aluminumCasing, galvanized sheet steelRear panel, ABS plasticElectrical ConnectionPlug on screw terminals, 16 AWG ( mm2) solid, 18 AWGstranded cable ( mm2) with ferruleDisplayLED Display , 2 colorNumeric Display , 5 x 7 segment (red or green) (13 mm)Bargraph Display , 12 segment, yellowLimit indicator, 4 x 1 segment, yellowRange-19999 to + 99999 Operation3 pushbuttons (+, -, E) and/or ReadWin 2000 softwareInterfaceRS 232, connects to rear panel, mm stereo connectionLimit FunctionOff, minimum, maximum, alarmNumber of Limits2 Limit Display2 LEDs per limitScan Rate1 secondApplication ConditionsMechanical ConstructionDisplay and Operation7 Power Supply90 to 253 VAC, 50/60 HzOptional 18 to 36 VDC, 24 VAC 15%, 50/60 HzPower Consumption4 VACE Mark89/336/EWG and 73/23/EWG guide linesBy attaching the CE mark, Endress+Hauser confirms that theinstrument fulfills all the requirements of the relevant ECdirectivesInput PowerCertificatesOrdering InformationRIA 250 Process DisplayRIA 250 -1 CertificationAGeneral purpose2 Power Supply190 to 253 VAC, 50/60 Hz218 to 36 VDC / 20 to 28 VAC, 50/60 Hz3 Signal Input10/4 to 20 mA, 0 to 10 V, 100 mV, 10 Vthermocouple and Pt 100.
10 Ni 1004 DisplayRRed numeric Display , 5-digitGGreen numeric Display , 5-digit5 Analog Output / Limit Relays1 Analog output and limit relays not required22 limit relays, SPDT, 250 VAC, 3A3 Analog output 0/4 to 20 mA, 0 to 10 V and2 limit relays (SPDT, 250 VAC, 3A)6 ModelKStandard North American region, panel mountedLNEMA 4X field mounted housing, North American region2 Factory calibration certificate, panel mounted4 Factory calibration certificate, NEMA 4X (IP 65) field housingAccessoriesPC software ReadWin 2000 for unit set up with 3 ft. (1 m)connection cable, 9 pin Sub. D connector and mmstereo plug (plugs into rear of RIA 250).Part 250RS 232PC59162 RxD83 TxD5 Gnd231 2 3 4 5 6 Endress+HauserThe Power of Know HowUnited StatesEndress+Hauser, Endress PlaceGreenwood, IN 46143 Phone: (317) 535-7138888-ENDRESSFAX: (317) 535-8498TI 060R/24/ 2003 Endress+Hauser, +HauserCanada Graham s LaneUnit 1, BurlingtonON, L7S 1W3 Phone: (905) 681-9292800-668-3199 FAX: (905) 681-9444 MexicoEndress+HauserPaseo del Pedregal No.