Page 1 / 3. CERTIFICATE number: 24297/A0 BV. File number: AP 4222. Product code: 3780H. This CERTIFICATE is not valid when presented without the full attached schedule composed of 7 sections TYPE APPROVAL CERTIFICATE . This CERTIFICATE is issued to consilium Marine & Safety AB. G teborg - SWEDEN. for the type of product ANCILLARIES FOR FIXED FIRE DETECTION AND FIRE ALARM SYSTEMS. addressable and Conventional Manual Call Points Types: Salwico MCP-A, MCP-C, MCP-SPR-A & MCP-SPR-C. addressable Short-Circuit Isolator Type: Salwico SCI-A. Requirements: BUREAU VERITAS Rules for the Classification of Steel Ships.

Consilium Marine & Safety AB Göteborg - SWEDEN for the type of product ANCILLARIES FOR FIXED FIRE DETECTION AND FIRE ALARM SYSTEMS Addressable and Conventional Manual Call Points

Tags:

  Consilium, Addressable

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of TYPE APPROVAL CERTIFICATE - …

1 Page 1 / 3. CERTIFICATE number: 24297/A0 BV. File number: AP 4222. Product code: 3780H. This CERTIFICATE is not valid when presented without the full attached schedule composed of 7 sections TYPE APPROVAL CERTIFICATE . This CERTIFICATE is issued to consilium Marine & Safety AB. G teborg - SWEDEN. for the type of product ANCILLARIES FOR FIXED FIRE DETECTION AND FIRE ALARM SYSTEMS. addressable and Conventional Manual Call Points Types: Salwico MCP-A, MCP-C, MCP-SPR-A & MCP-SPR-C. addressable Short-Circuit Isolator Type: Salwico SCI-A. Requirements: BUREAU VERITAS Rules for the Classification of Steel Ships.

2 EN 54-11:2001 + A1:2005, EN 54-17:2005. This CERTIFICATE is issued to attest that BUREAU VERITAS did undertake the relevant APPROVAL procedures for the product identified above which was found to comply with the relevant requirements mentioned above. This CERTIFICATE will expire on: 18 Oct 2016. For BUREAU VERITAS, At BV GOTHENBURG, on 18 Oct 2011, Magne MOLLER. This CERTIFICATE remains valid until the date stated above, unless cancelled or revoked, provided the conditions indicated in the subsequent page(s) are complied with and the product remains satisfactory in service.

3 This CERTIFICATE will not be valid if the applicant makes any changes or modifications to the approved product, which have not been notified to, and agreed in writing with BUREAU VERITAS. Should the specified regulations or standards be amended during the validity of this CERTIFICATE , the product(s) is/are to be re-approved prior to it/they being placed on board vessels to which the amended regulations or standards apply. This CERTIFICATE is issued within the scope of the General Conditions of BUREAU VERITAS Marine Division available on the internet site Any Person not a party to the contract pursuant to which this document is delivered may not assert a claim against BUREAU VERITAS for any liability arising out of errors or omissions which may be contained in said document, or for errors of judgement, fault or negligence committed by personnel of the Society or of its Agents in establishment or issuance of this document.

4 And in connection with any activities for which it may provide. BV Mod. 530 May 2009 This CERTIFICATE consists of 3 page(s). Page 2 / 3. CERTIFICATE number: 24297/A0 BV. THE SCHEDULE OF APPROVAL . 1. PRODUCT DESCRIPTION: Salwico MCP-A/C are addressable / Conventional Manual Call Points. Salwico SCI-A is an addressable Short-Circuit Isolator. - MCP-A: addressable Manual Call Points Model MCP-A MCP-A MCP-SPR-A. Part Number 5200030-01A 5200031-01A 5200037-01A. Type Type A (simple action). Resettable By replacing the broken glass Protection Index IP 23 Indoor IP 67 - Outdoor IP 67 - Outdoor Short-Circuit Protection Yes Software Version Working Temperature -25 C to 70 C.

5 Power Supply 20-38 VDC. - MCP-C: Conventional Manual Call Points Model MCP-C MCP-C MCP-SPR-C. Part Number 5200010-01A 5200014-01A 5200016-01A. Type Type A (simple action). Resettable By replacing the broken glass Protection Index IP 24 Indoor IP 67 - Outdoor IP 67 - Outdoor Short-Circuit Protection None Software Version None Working Temperature -10 C to 55 C -25 C to 70 C -25 C to 70 C. Power Supply 16-30 VDC. - SCI-A: addressable Short-Circuit Isolator Part Number 5200120-00A. Protection Index IP 67 - Outdoor Software Version Working Temperature -25 C to 70 C.

6 Power Supply 20-38 VDC. 2. DOCUMENTS AND DRAWINGS: KAC: Letter dated on 17 February 2010. consilium Marine: Data Sheets No. 5200030-01A , No. 5200031-01A , No. 5200037-01A , No. 5200010-01A , No. 5200014-01A , No. 5200016-01A and No. 5200120-00A Bill of Materials MCP-A, SCI-A, Ref S-4 RA. Drawing MCP-A SCI-A No. Rev. R4, dated March 07, 2010. 3. TEST REPORTS: BRE: Test Report No. TE214876 (EN 54-11 KAC Series) issued on 05 July 2004. Test Report No. TE222228 (EN 54-11 KAC WCP Series) issued on 05 January 2005. Test Report No. TE225839 issued on 31 May 2006 (IACS E10).

7 Nemko: Environmental Test Report No. dated 2010-03-23. Test Report - EN 54-11 No. 131410-2 dated 2010-03-25. Test Report - EN 54-17 No. 131410-3 dated 2010-03-25. Cape Engineering UK Limited: CERTIFICATE of Testing (EN 60529 WCP) Serial No. 14194 issued on 5th May 2005. BV Mod. 530 May 2009 This CERTIFICATE consists of 3 page(s). Page 3 / 3. CERTIFICATE number: 24297/A0 BV. 4. APPLICATION / LIMITATION: - BUREAU VERITAS Rules for the Classification of Steel Ships. - APPROVAL valid for ships intended to be granted with the following additional class notations: AUT-UMS, AUT-CCS, AUT-PORT and AUT-IMS.

8 - APPROVAL valid for ships having to comply with SOLAS 74 Convention, as amended, and for units having to comply with IMO Resolution A649 (The "MODU Code"). - The equipment fulfils the EMC requirements for installation on the Bridge and Deck Zone. - BUREAU VERITAS Environmental Category, EC Code: 41S for Outdoor Units, 21/31 for Indoor Units. - The complete installation design showing the location of the Manual Call Points / Short-Circuit Isolators should be submitted to the Society's Surveyors for APPROVAL . - Satisfactory performance tests should be witnessed on each installation by the Society's Surveyor after installation on board.

9 - Only Hardware and Software successfully tested together in compliance with the regulations as referred to in page one, according to the declaration of the manufacturer are covered by this CERTIFICATE . 5. PRODUCTION SURVEY REQUIREMENTS: - The above Manual Call Points and the Short-Circuit Isolator are to be manufactured, examined and tested by consilium Marine & Safety AB in accordance with the type(s) described in this CERTIFICATE and Bureau Veritas Rules for the Classification of Steel Ships. - Production sites are to be recognized by Bureau Veritas as per NR320 for HBV products.

10 To this end consilium Marine & Safety AB has to make the necessary arrangements for a Society's Surveyor to perform visits and product audits at the production sites. - consilium Marine & Safety AB declared to Bureau Veritas that the type of product described in this CERTIFICATE are manufactured at the following production sites: KAC ALARM COMPANY LTD. Address Units 15-19 Trescott Road Trafford Park Smallwood B98 7AH REDDITCH. Worcestershire UNITED KINGDOM. and consilium Marine & Safety AB. Box 8763. S-40276 G teborg SWEDEN. 6. MARKING OF PRODUCT: According to EN 54-11 and / or EN 54-17 requirements.