Fuse Sizing Guide - Omega Engineering

Z-1061 Main Service Conductor Cable Limiters ( 240, 450-6): a) Select by cable size and mounting terminal configurations Main Service Circuit Fuses Mixed Loads: a) Size fuses same as item Transformer Circuit Fuses ( 450-3b, 240-3, 240-21, 384-16d, 430-72b Ex. 3, 4 & (c) as required):* a) PRIMARY FUSES: Size fuses not over 125%. As exceptions exist, refer to the appropriate paragraphs. Recommended fuses: LESRK, ECSR, JDL, LCL+.* b) SECONDARY FUSES (Sum of following): 125% of the continuous load plus 100% of non-continuous load. fuse size not to exceed 125% of transformer secondary rated amps.

Fuse Ratings Fuses with an A-C voltage rating may be applied at system voltages below the fuse voltage rating, but not at voltages above the fuse voltage rating. The other A-C fuse ratings remain the same at applied voltages below the fuse voltage rating. ... Fuse Sizing Guide ...