Z-1061 Main Service Conductor Cable Limiters ( 240, 450-6): a) Select by cable size and mounting terminal configurations Main Service Circuit Fuses Mixed Loads: a) Size fuses same as item Transformer Circuit Fuses ( 450-3b, 240-3, 240-21, 384-16d, 430-72b Ex. 3, 4 & (c) as required):* a) PRIMARY FUSES: Size fuses not over 125%. As exceptions exist, refer to the appropriate paragraphs. Recommended fuses: LESRK, ECSR, JDL, LCL+.* b) SECONDARY FUSES (Sum of following): 125% of the continuous load plus 100% of non-continuous load. fuse size not to exceed 125% of transformer secondary rated amps.
Fuse Ratings Fuses with an A-C voltage rating may be applied at system voltages below the fuse voltage rating, but not at voltages above the fuse voltage rating. The other A-C fuse ratings remain the same at applied voltages below the fuse voltage rating. ... Fuse Sizing Guide ...
Domain:
Source:
Link to this page:
Please notify us if you found a problem with this document:
{{id}} {{{paragraph}}}
Guide Low Voltage Motors Basics of IEC, GUIDE, Electric, POWER Ratings, Generator sizing guide, Generator sizing guide EATON www.eaton.com, Eaton, Power, Ratings, ELECTRIC POWER RATINGS GUIDE, SPECIFIER GUIDE INTRODUCTION, Baldor Electric, Fuse Selection Guide, Design of Electrical Power Supply System in, Electric power, Electrical inspection checklists, POWER AND VOLTAGE RATING, Electrical Appliance Typical Energy Consumption