CHAPTER 29 PLUMBING SYSTEMSSECTION 2901 PLUMBING CODEP lumbing SYSTEMS shall comply with thePlumbing 2902 NUMBER OF number of PLUMBING fixtures within abuilding shall not be less than set forth for each type of buildingoccupancy in Table 29-A. Fixtures located within unisex toiletand bathing rooms shall be included in determining the numberof fixtures provided in an occupancy. Accessible toilet andbathing facilities shall be provided in accordance with Chapter11. For sanitation requirements, see Section :1. Required sanitary facilities for temporary uses shallbe determined by the building Buildings not normally Separate occupant load factors shall beas shown in Table :Where separate toilet facilities are provided forthe public and employees, the number of required fixturesfor employees shall be based on the actual number ofemployees on the largest occupant load shall be divided equally between :Where circumstances dictate that a differentratio is needed, the adjustment shall be approved by thebuilding Separate faciliti

CHAPTER 29 PLUMBING SYSTEMS SECTION 2901 PLUMBING CODE Plumbing systems shall comply with the Plumbing Code. SECTION 2902 NUMBER OF FIXTURES 2902.1 General. The number of plumbing fixtures within a

Tags:

  System, Chapter, Plumbing, Chapter 29 plumbing systems

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of CHAPTER 29 PLUMBING SYSTEMS - ecodes.biz

1 CHAPTER 29 PLUMBING SYSTEMSSECTION 2901 PLUMBING CODEP lumbing SYSTEMS shall comply with thePlumbing 2902 NUMBER OF number of PLUMBING fixtures within abuilding shall not be less than set forth for each type of buildingoccupancy in Table 29-A. Fixtures located within unisex toiletand bathing rooms shall be included in determining the numberof fixtures provided in an occupancy. Accessible toilet andbathing facilities shall be provided in accordance with Chapter11. For sanitation requirements, see Section :1. Required sanitary facilities for temporary uses shallbe determined by the building Buildings not normally Separate occupant load factors shall beas shown in Table :Where separate toilet facilities are provided forthe public and employees, the number of required fixturesfor employees shall be based on the actual number ofemployees on the largest occupant load shall be divided equally between :Where circumstances dictate that a differentratio is needed, the adjustment shall be approved by thebuilding Separate facilities shall be pro-vided for each sex as specified in Table :1.

2 Separate facilities shall not be required in structuresor tenant spaces with a total occupant load, includingboth employees and customers, of 15 or less. Thefacility provided shall have one water closet and onelavatory in the same room with privacy lock and an occupied Unisex restrooms may be provided in satisfying thetotal number of required Separate inmate facilities shall not be required indetention facilities, if serving one sex Separate facilities shall not be required for dwellingunits and sleeping Required public toilet andpatrons shall be provided with public toilet facilities in struc-tures and tenant spaces intended for public utilization. Thenumber of PLUMBING fixtures located within the required toiletfacilities shall be provided in accordance with Section all users.

3 Employees shall be provided with toilet facilitiesin all occupancies. Employee toilet facilities shall either be sep-arate or combined employee and public toilet route to the public toilet facilitiesrequired by Section shall not pass through kitchens,storage rooms or closets. Access to the required facilitiesshall be from within the building or from the exterior of thebuilding. All routes shall comply with the accessibilityrequirements of this code. The public shall have access tothe required toilet facilities at all times that the building :In Group B (other than restaurants and din-ing facilities), F, H, M and S occupancies, toilet facilitiesmay be located in an adjacent building on the same Location of toilet facilities in occupancies otherthan covered mall occupancies other thancovered mall buildings, the required public and employeetoilet facilities shall be located not more than one storyabove or below the space required to be provided with toiletfacilities and the path of travel to such facilities shall notexceed a distance of 500 feet (152 400 mm).

4 Exception:The location and maximum travel distancesto required employee facilities in factory and industrialoccupancies are permitted to exceed that required by thissection, provided that the location and maximum traveldistance Location of toilet facilities in covered mall buildings,the required publicand employee toilet facilities shall be located not more thanone story above or below the space required to be providedwith toilet facilities, and the path of travel to such facilitiesshall not exceed a distance of 300 feet (91 440 mm). Incov-ered mall buildings, the required facilities shall be based ontotal square footage, and facilities shall be installed in eachindividual store or in a central toilet area located in accor-dance with this section.

5 The maximum travel distance to thecentral toilet facilities in covered mall buildings shall bemeasured from the main entrance of any store or tenantspace. Incovered mall buildings, where employees toiletfacilities are not provided in the individual store, the maxi-mum travel distance shall be measured from the employees work area of the store or tenant Pay pay facilities are installed,such facilities shall be in excess of the required minimumfacilities. Required facilities shall be free of Separation from food closet rooms inconnection with food establishments where food is prepared,stored or served shall have a nonabsorbent interior finish asspecified in Sections and , shall havehand-washing facilities therein or adjacent thereto, and shall be2010 OREGON STRUCTURAL SPECIALTY CODE5911M:\data\CODES\STATE CODES\Oregon\2010\Structural Specialty_Building\Final VP\ , January 08, 2010 12:38:03 PMColor profile: Generic CMYK printer profileComposite Default screenseparated from food preparation and storage rooms as speci-fied in Section Dwelling units shall be provided with akitchen equipped with a kitchen sink.

6 Dwelling units, congre-gate residences and lodging houses shall be provided with abathroom equipped with facilities consisting of a water closet,lavatory and either a bathtub or shower. Each sink, lavatory andeither a bathtub or shower shall be equipped with hot and coldrunning water necessary for its normal Water closet space all occupancies,the water closet stool shall be located in a clear floor space notless than 30 inches (762 mm) in width. The clear floor space infront of the water closet stool shall not be less than 24 inches(610 mm). See CHAPTER 11 for accessible water 2903 DRINKING fountains shall be provided whererequired by this section. Drinking fountains shall be accessibleas required by CHAPTER :Drinking fountains are not required when theoccupant load is 30 or Where Group A occupancies, at least onedrinking fountain shall be provided at each floor level in anapproved :A drinking fountain need not be provided in adrinking or dining Group E occupancies, there shall be at least one drink-ing fountain on each floor of elementary and secondaryschools.

7 Drinking fountains shall not be installed in 2904 ALTERATION OF EXISTINGGROUP A alteration where thetotal cost of all alterations (including, but not limited to, electri-cal, mechanical, PLUMBING and structural changes) for a build-ing or facility within any 12-month period amounts to 60percent or more of the appraised alteration that haslittle likelihood of being accomplished because existing struc-tural conditions would require removing or altering a load-bearing member that is an essential part of the structural frame,or because site constraints prohibit modification or addition ofelements, spaces or features which are in full and strict compli-ance with the minimum requirements for new substantial alterations are madeto an existing Groups A, M and E occupancy with an occupantload in excess of 300, water closets, as specified in Table 29-Afor new construction, shall be.

8 The building official may approve substantialalterations without the installation of additional water clos-ets only where it is structurally infeasible to make such alter-ations; where existing site conditions, including the size ofexisting public water or sewer lines, prohibit such installa-tions; or where zoning regulations prohibit adding floor areato the existing building. The number of water closets pro-vided shall be the maximum number feasible but need notexceed the number required for new OREGON STRUCTURAL SPECIALTY CODEPLUMBING SYSTEMS2M:\data\CODES\STATE CODES\Oregon\2010\Structural Specialty_Building\Final VP\ , January 08, 2010 12:38:03 PMColor profile: Generic CMYK printer profileComposite Default screen2010 OREGON STRUCTURAL SPECIALTY CODE593 PLUMBING SYSTEMSTABLE 29-AMINIMUM PLUMBING FIXTURES1 TYPE OF BUILDING OR OCCUPANCY2 WATER CLOSETS3(fixtures per person)MALE FEMALELAVATORIES4(fixtures per person)MALE FEMALEBATHTUB OR SHOWER(fixtures per person)For the occupancies listed below, use 30 square feet ( m2)

9 Per occupant for the minimum number of PLUMBING A, and assembly usesConference rooms, dining rooms, drinkingestablishments, exhibit rooms, gymnasiums,lounges, stages and similar uses, includingrestaurants classified as Group B occupanciesamusement parks, entertainment and sportsarenas, community halls, special event centers1:1 251:1 252:26 752:26 753:76 1253:76 1254:126 2004:126 2005:201 3005:201 3006:301 4006:301 400 Over 400, add one fixture for eachadditional 200 males or 150 for each water closet up to four;then one for each two additionalwater closetsFor the assembly occupancies listed below, use the number of fixed seating or, where no fixed seating is provided, use 15 square feet ( m2) peroccupant for the minimum number of PLUMBING placesAuditoriums, convention halls, dance floors,lodge rooms, stadiums and casinos1:1 503:1 502:51 1004:51 1003:101 1506:101 2004:151 3008:201 400 Over 300 males, add one fixture foreach additional 200, and over 400females add one for each :1 2001:1 2002:201 4002:201 4003:401 7503.

10 401 750 Over 750, add one fixture for eachadditional 500 the assembly occupancies listed below, use the number of fixed seating or, where no fixed seating is provided, use 30 square feet ( m2) peroccupant for the minimum number of PLUMBING placesPrincipal assembly areaWorship placesEducational and activity unitone per 150one per 75one per 125one per 75one per two water closetsone per two water closetsFor the occupancies listed below, use 200 square feet ( m2) per occupant for the minimum number of PLUMBING BOffices or public buildings1:1 151:1 152:16 352:16 353:36 553:36 55 Over 55, add one for each 50 per two water closetsFor the occupancies listed below, use 50 square feet ( m2) per occupant for the minimum number of PLUMBING ESchools for staff useAll schools1:1 151:1 152:16 352:16 353:36 553:36 55 Over 55, add one fixture for eachadditional 40 per 40one per 40 Schools for student useDay care1:1 201:1 202:21 502:21 50 Over 50, add one fixture for eachadditional 50 :1 251:1 252:26 502.