Digital Temperature Controllers E5CC/E5EC Solutions Guide ...

Digital Temperature Controllers E5CC/E5 ECSolutions Guide for FAQsUsing Basic FunctionsBasic Setup ProcedureSTARTC onnect sensor and operating terminal. Turn ON Setting the sensor type2. Using ON/OFF control3. Using PID controlSetting the set point4. Setting Temperature alarms5. Setting heater burnout alarmsOperationCONTENTS1. Setting the Sensor Type2. Using ON/OFF Control3. Using PID Control4. Setting Temperature Alarms5. Setting Heater Burnout AlarmsIntroduction This Solutions Guide is based on customer questions that were received at OMRON's Customer Support Center.

←Default setting is 5 (5): K thermocouple at Initial Setting Level ←in-t(IN-T) will be displayed to show that the Initial Setting Level has been entered. Press the Key for at least 3 seconds. ← Flashes 3 times. 2 ←If a sensor is not connected or if the setting of the Input Type parameter does not agree with the

Tags:

  Thermocouple, K thermocouple

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Digital Temperature Controllers E5CC/E5EC Solutions Guide ...

1 Digital Temperature Controllers E5CC/E5 ECSolutions Guide for FAQsUsing Basic FunctionsBasic Setup ProcedureSTARTC onnect sensor and operating terminal. Turn ON Setting the sensor type2. Using ON/OFF control3. Using PID controlSetting the set point4. Setting Temperature alarms5. Setting heater burnout alarmsOperationCONTENTS1. Setting the Sensor Type2. Using ON/OFF Control3. Using PID Control4. Setting Temperature Alarms5. Setting Heater Burnout AlarmsIntroduction This Solutions Guide is based on customer questions that were received at OMRON's Customer Support Center.

2 It provides practical operating procedures for setting and changing the most common items: setting the sensor type, ON/OFF control, PID control, setting Temperature alarms, and setting heater burnout alarms. Keep this Guide in a convenient location onsite to help you make settings and changes. If you are having trouble with Temperature Controller settings, this is the guidebook for you. OMRON, 2012 All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in anyform, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior writtenpermission of OMRON.

3 No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRONis constantly striving to improve its high-quality products, the information contained in this manual is subject to changewithout notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes noresponsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of theinformation contained in this publication. Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5 ECSetting the Sensor Type 1-1 Setting the Sensor Type Setting the Sensor Type Select and set the sensor type ( , the Input Type parameter) to the set value that corresponds to the type of sensor used in the application and the required Temperature range.

4 The parameter is set to 5 ( k thermocouple at 200 to 1,300 C) by default. Thermocouples Resistance Thermometers E5CC/E5 ECK J T R. etc. Pt JPt E5CC/E5EC Input type Sensor typeInput Temperature setting range in C Input Temperature setting range in F E5CC/E5EC set value 200 to 850 C 300to1500 F0 to C F1 Pt100 to F2 to C F3 Resistance thermometer JPt100 to F4 200 to 1300 C 300to2300 F5 (default) K to F6 100 to 850 C 100to1500 F7 J to F8 200 to 400 C 300to700 F9 T to C F10 E 200 to 600 C 300to1100 F11 L 100 to 850 C 100to1500 F12 200 to 400 C 300to700 F13 U to C F14 N 200 to 1300 C 300to2300 F15 R 0 to 1700 C0to3000 F16 S 0 to 1700 C0to3000 F17 B 100 to 1800 C300to3200 F18 W 0 to 2300 C0to3200 F19 thermocouple PLII 0 to 1300 C0to2300 F20 * When using the

5 ES1B Infrared Temperature Sensor and an analog input, refer to the E5CC/E5EC Digital Temperature Controllers User's Manual (Cat. No. H174). If the setting of the Input Type parameter does not agree with the connected sensor, ( : Input Error) will flash on the display as shown at the left when the power supply is turned ON. Use the procedure on page 1-2 to set the Input Type parameter correctly. Any value can be set for any model. Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC Setting the Sensor Type 1-2 Setting the Sensor Type You set this parameter in the Initial Setting Level.

6 The parameter is set to 5 ( k thermocouple at 200 to 1,300 C) by default. 1 Setting the Sensor Type Change the set value with the (Up and Down) Keys. Operating Display in-t (IN-T): Indicates the Input Type parameter. Default setting is 5 (5): k thermocouple at 200 to 1,300 C. Initial Setting Level in-t(IN-T) will be displayed to show that the Initial Setting Level has been entered. Press the Key for at least 3 seconds. Flashes 3 times.

7 2 Set the parameter with the Keys. If a sensor is not connected or if the setting of the Input Type parameter does not agree with the connected sensor, ( : Input Error) will flash on the display when the power supply is turned ON. If the sensor is not connected, connect it now. Input Type: 0 (Pt100 resistance thermometer at 200 to 850 C) (example) Set the number that you selected for theInput Type parameter on page 1-1. 3 Turn ON the power supply. Initial Setting LevelInitial Setting Level1 Press the (Level) Key for atleast 3 seconds.

8 (When finished, press the (Level) Key for at least 1 second to return to the operation display.) Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5 ECUsing ON/OFF Control 2-1 Using ON/OFF Control Using ON/OFF Control The procedure to use ON/OFF control is given step by step in this section. The default setting is for reverse operation. For heating control, select reverse operation. For cooling control, select direct operation. With ON/OFF control, you can adjust the reset width (called the hysteresis) for heating or cooling operation.

9 The default setting is C. Heating (Reverse) Operation Cooling (Direct) Operation When the output turns OFF at the set point, the Temperature will decrease. You can set the Temperature width that determines when the output will turn ON again. When the output turns OFF at the set point, the Temperature will increase. You can set the Temperature width that determines when the output will turn ON again. 1 Select direct or reverse point ON OFF Te m p e r a t ur eOutput turns OFF if the Temperature is greater than the set point.

10 Output turns ON if the Temperature is lower than the set point. Heating Reverse Operation (Default) ON OFF Cooling Set point TemperatureOutput turns ON if the Temperature is greater than the set point. Output turns OFF if the Temperature is lower than the set point. Direct Operation (Default) 2 Adjust the hysteresis. Set point ON OFF Temper atureThis width can be set as the hysteresis. Heating ON OFF Set point TemperatureThis width can be set as the hysteresis. Cooling Step 1 Determining the Control MethodSimplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC Using ON/OFF Control 2-2 Using ON/OFF Control You set this parameter in the Initial Setting Level.