DOP-B07 High Color Wide Screen User-Friendly HMI Products , Xinglong Rd., Taoyuan City 33068, Taiwan B07S(E)415 / B07S(E)515 / B07PS415 / B07PS515 Instrunction Sheet (1) Preface Thank you for purchasing DELTA s DOP-B series. This instruction sheet will be helpful in the installation, wiring and inspection of Delta HMI. Before using the product, please read this instruction sheet to ensure correct use. You should thoroughly understand all safety precautions before proceeding with the installation, wiring and operation. Place this instruction sheet in a safe location for future reference. Please observe the following precautions: Install the product in a clean and dry location free from corrosive and inflammable gases or liquids. Ensure that all wiring instructions and recommendations are followed. Ensure that HMI is correctly connected to a ground. The grounding method must comply with the electrical standard of the country (Please refer to NFPA 70: National Electrical Code, 2005 Ed.)

DOP-B07 High Color‧Wide Screen‧ User-Friendly HMI Products No.18, Xinglong Rd., Taoyuan City 33068, Taiwan B07S(E)415 / B07S(E)515 / B07PS415 / B07PS515 Instrunction Sheet

Tags:

  Dop b07

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of DOP-B07 - deltaww.com

1 DOP-B07 High Color Wide Screen User-Friendly HMI Products , Xinglong Rd., Taoyuan City 33068, Taiwan B07S(E)415 / B07S(E)515 / B07PS415 / B07PS515 Instrunction Sheet (1) Preface Thank you for purchasing DELTA s DOP-B series. This instruction sheet will be helpful in the installation, wiring and inspection of Delta HMI. Before using the product, please read this instruction sheet to ensure correct use. You should thoroughly understand all safety precautions before proceeding with the installation, wiring and operation. Place this instruction sheet in a safe location for future reference. Please observe the following precautions: Install the product in a clean and dry location free from corrosive and inflammable gases or liquids. Ensure that all wiring instructions and recommendations are followed. Ensure that HMI is correctly connected to a ground. The grounding method must comply with the electrical standard of the country (Please refer to NFPA 70: National Electrical Code, 2005 Ed.)

2 Do not disassemble HMI, modify or remove wiring when power is applied to HMI. Do not touch the power supply during operation. Otherwise, it may cause electric shock. If you have any questions during operation, please contact our local distributors or Delta sales representatives. The content of this instruction sheet may be revised without prior notice. Please consult our distributors or download the most updated version at (2) Safety Precautions Carefully note and observe the following safety precautions when receiving, inspecting, installing, operating, maintaining and troubleshooting. The following words, DANGER, WARNING and STOP are used to mark safety precautions when using the Delta s HMI product. Failure to observe these precautions may void the warranty! Installation Comply with quick start for installation. Otherwise it may cause equipment damage. Do not install the product in a location that is outside the stated specification for the HMI. Failure to observe this caution may result in electric shock, fire, or explosion.

3 Do not install the product in a location where temperatures will exceed specification for the HMI. Failure to observe this caution may result in abnormal operation or damage the product. Please note that this equipment has obtained EMC registration for commercial use. In the event that it has been mistakenly sold or purchased, please exchange it for equipment certified for home use. Do not use this product as an alarm device for disaster early warning that may result in personal injury, equipment damage, or system emergency stop. Wiring Connect the ground terminals to a class-3 ground (Ground resistance should not exceed 100 ). Improper grounding may result in communication error, electric shock or fire. Operation The users should use Delta Screen Editor software to perform editing in Delta's HMI product. To perform editing and confirming HMI programs without using Delta Screen Editor software in Delta's HMI product may result in abnormal operation. To prevent the personal injury and equipment damage, when designing HMI programs, please ensure that a communication error occurred between Delta s HMI product and the connecting controller or equipment will not result in system failure or malfunction.

4 Please be sure to backup the screen data and HMI programs in case they are lost, accidentally deleted or worse. Do not modify wiring during operation. Otherwise it may result in electric shock or personal injury. Never use a hard or pointed object to hit or strike the screen as doing this may damage the screen and let the screen has not respond at all, and then cause HMI to work abnormally. Maintenance and Inspection Do not touch any internal or exposed parts of the HMI as electrical shock may result. Do not remove operation panel while power is on. Otherwise electrical shock may result. Wait at least 10 minutes after power has been removed before touching any HMI terminals or performing any wiring and/or inspection as an electrical charge may still remain in the HMI with hazardous voltages even after power has been removed. Turn the power off before changing backup battery and check system settings after finishing change. (all data will be cleared after changing battery).

5 Be sure the ventilation holes are not obstructed during operation. Otherwise malfunction may result due to bad ventilation or overheating troubles. Wiring Method Do not use a voltage that will exceed specification for the HMI. Failure to observe this caution may result in electric shock or fire. Remove the terminal block from the HMI before wiring. Insert only one wire into one terminal on the terminal block. If the wiring is in error, perform the wiring again with proper tools. Never use force to remove the terminals or wires. Otherwise, it may result in malfunction or damage. For the power line that forced to take out, ensure to check wiring again and restart. Communication Wiring Comply with communication wiring specification for wiring. Wiring length should comply with the stated specification for the HMI. Proper grounding to avoid bad communication quality. To avoid noise and interference, the communication cable, all power cables, and motor power cable should be placed in separate conduits.

6 (3) Pin Definition of Serial Communication DOP-B07S(E)415 DOP-B07PS415 Series COM1 Port (Supports Flow Control) COM Port PIN Contact RS-232 1 2 RXD 3 TXD 4 5 GND 6 7 RTS 8 CTS 9 Note: Blank = No Connection. COM2 Port (Supports Flow Control) COM Port PIN MODE1 MODE2 MODE3 RS-232 RS-422 RS-485 1 TXD+ D+ 2 RXD 3 TXD 4 RXD+ 5 GND GND GND 6 TXD- D- 7 RTS 8 CTS 9 RXD- Note1: Blank = No Connection.

7 Note2: When COM2 port is used for RS-232 flow control, RTS and CTS signals are used for flow control, COM3 port will become incapable of being used. Note3: When COM2 port is used for RS-422 flow control, please refer to the following COM3 Port signals table for pin assignments. The signals, RTS+, CTS+, RTS- and CTS- shown in brackets are the signals used for flow control. COM3 Port COM Port PIN MODE1 MODE2 MODE3 RS-232 RS-422 RS-485 1 TXD+(RTS+) D+ 2 RXD 3 TXD 4 RXD+(CTS+) 5 GND GND GND 6 TXD-(RTS-) D- 7 8 9 RXD-(CTS-) Note1: Blank = No Connection.

8 Note2: When COM2 port is used for RS-422 flow control, please refer to the COM3 Port signals table above for pin assignments. The signals, RTS+, CTS+, RTS- and CTS- shown in brackets are the signals used for flow control. DOP-B07S(E)515 DOP-B07PS515 Series COM1 Port (Supports Flow Control) COM Port PIN Contact RS-232 1 2 RXD 3 TXD 4 5 GND 6 7 RTS 8 CTS 9 Note: Blank = No Connection. COM2 and COM3 Port COM Port PIN MODE1 MODE2 MODE3 COM2 COM3 COM2 COM3 COM2 COM3RS-232RS-485RS-485RS-485RS-232RS-422 1 D+ TXD+ 2 RXD RXD 3 TXD TXD 4 D+ D+ RXD+ 5 GND GND GND 6 D- TXD- 7 8 9 D- D- RXD- Note1: Blank = No Connection.

9 Note2: B05S111 / B07S(E)515/ B07PS515 series models do not support RS-422 flow control function. Note3: COM3 is the extension port (COM2 and COM3 share one physical port). DOP-B07E415 / DOP-B07E515 Ethernet Interface (LAN) Ethernet Interface (LAN) PIN Contact Ethernet 1 TX+ 2 TX- 3 RX+ 4 5 6 RX- 7 8 Note: Blank = No Connection. (4) Parts Names DOP-B07S(E)415 DOP-B07PS415 (Front View) A : Power LED Indicator Lights in green when HMI works normally. C : Operation LED Indicator (Blue) (Note1) The operation LED indicator blinks in blue when either the communication is carried out or the data is accessing (please refer to the Note1 below for explanation). : Alarm LED Indicator (Red) The alarm LED indicator blinks in red when one of the alarms is on.

10 D Touch Screen / Display NOTE 1. The definition of the operation LED indicator (Blue) can be determined by the users freely. DOP-B07S(E)415 DOP-B07PS415 (Rear View) A Power Input Terminal F Ethernet Interface (LAN) B COM3 (It is provided with two LED indicators to indicate that HMI is in Read or Write status during the communication process.) G USB Host C COM2 (It is provided with two LED indicators to indicate that HMI is in Read or Write status during the communication process.) H Audio Output Interface D COM1 I Memory Card Slot / Battery E USB Slave - - A C BGDCB A IEFH PIN1 PIN1 PIN1 PIN1 PIN1 DOP-B07S(E)515 DOP-B07PS515 (Front View) A Power LED Indicator (Lights in green when HMI works normally.) B Touch Screen / Display DOP-B07S(E)515 DOP-B07PS515 (Rear View) A Power Input Terminal F USB Slave B COM2 (can be extended to COM3 (Note1)) G System Key C COM1 H Ethernet Interface (LAN) D Memory Card Slot / Battery Cover I Audio Output Interface E USB Host - - NOTE 1.