Eaton UPS battery handbook

Reference handbook The large UPS. battery handbook The large UPS. battery handbook Understanding your UPS battery It's well understood that the battery in a UPS is the most vulnerable part can extend its life, prevent of the system. In fact, battery failure is costly downtime, and save time a leading cause of load loss. Knowing how to maintain and manage your and money. UPS batteries will extend their life and save you time and potential trouble in the future. Improvements in battery technology have been evolutionary rather than revolutionary. Capabilities such as advanced charging regimens, software management for accurate remaining life information and firmware adding intelligence to batteries have reduced, but not eliminated, the risks inherent in depending on any battery . As a result, it's prudent, if not essential, to take a close look at what may be increasing your risk of unexpected load loss from a failing UPS battery .

voltage, and cell voltage balance, while making ... through their 20-year pro-rated life, at which time the failure mode is most often a short circuit. This situation is not an ... • Electrolyte: The medium that provides the ion transport mechanism between the positive and

Tags:

  Handbook, Medium, Eaton, Trade, Battery, Voltage, Eaton ups battery handbook

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Eaton UPS battery handbook

1 Reference handbook The large UPS. battery handbook The large UPS. battery handbook Understanding your UPS battery It's well understood that the battery in a UPS is the most vulnerable part can extend its life, prevent of the system. In fact, battery failure is costly downtime, and save time a leading cause of load loss. Knowing how to maintain and manage your and money. UPS batteries will extend their life and save you time and potential trouble in the future. Improvements in battery technology have been evolutionary rather than revolutionary. Capabilities such as advanced charging regimens, software management for accurate remaining life information and firmware adding intelligence to batteries have reduced, but not eliminated, the risks inherent in depending on any battery . As a result, it's prudent, if not essential, to take a close look at what may be increasing your risk of unexpected load loss from a failing UPS battery .

2 After all, even large installations with many batteries are vulnerable to the failure of a single battery . 2 Eaton The large UPS battery handbook Table of Contents Table of contents UPS battery overview .. 3. VRLA .. 3. Lithium-ion .. 3. Other common causes of UPS failure .. 3. VLA/flooded-cell .. 4. battery arrangement and power .. 4. battery facts.. 5. Four factors that affect battery life .. 5. battery disposal .. 6. battery maintenance for extended life .. 6. battery safety .. 7. battery FAQ .. 8. Eaton battery products and services .. 10. Eaton battery services overview .. 10. battery preventive maintenance .. 10. Eaton batteries .. 10. Why Eaton batteries? .. 11. Eaton Cellwatch .. 11. Thermal runaway .. 11. Extending battery service life .. 12. Eaton PredictPulse .. 12. Customer Support Center .. 12. Customer success story .. 13. battery glossary .. 14. 3 Eaton The large UPS battery handbook UPS. battery 1.

3 VRLA. VRLA batteries are sealed, usually within overview polypropylene plastic. They were developed because they have the advantage of containing no sloshing acid that might leak or drip out when inverted or handled roughly. The term valve- There are primarily three regulated refers to the method of gas release. If the kinds of batteries used in gas pressure becomes too great inside the battery , Overview the valve will vent when it reaches a certain pressure. UPSs valve-regulated lead-acid (VRLA), also During the charging of a lead-acid battery , hydrogen is known as sealed or normally liberated. In a vented battery , the hydrogen maintenance-free lithium- escapes into the atmosphere. In a VRLA battery , the VRLA batteries are frequently hydrogen recombines with oxygen inside battery , used in UPS or other high-rate ion batteries, and vented applications so water loss is minimized. Under normal float lead acid (VLA) (also conditions, virtually all the hydrogen and oxygen is called flooded-cell).

4 VRLA recombined. Re-sealable valves vent non-recombined batteries usually have gases only when pressure exceeds a safety lower up-front costs but threshold. have a shorter lifetime A VRLA battery is distinguished from a flooded-cell than VLA, usually around battery by the rate at which oxygen is evolved from five years. Flooded-cell the positive plate and diffused to the negative plate, batteries require more ultimately forming water. This rate is several orders of advanced maintenance magnitude faster than a flooded-cell battery . Because but have a longer lifetime, water can't be added, its recombination is critical to up to 20 years. Lithium- the life and health of a the battery . Any factor that ion batteries are smaller increases the evaporation rate or water loss such as ambient temperature and heat from the charging and lighter than the above current reduces the battery life. types, and have changed the traditional status quo The shelf life of a VRLA battery is the length of time for UPS use.

5 Costs are a battery can stand, open circuited, before it can no similar to VRLA, and longer be recovered to full capacity with a single charge. Shelf life is determined by the length of time new energy storage until the battery loses 40% 50% of its initial capacity applications with UPS due to self-discharge. systems, such as grid- sharing and peak shaving, Positive flag Extruded intercell are now viable. These Valve terminal welded connection, new capabilities provide low resistance current path more than just backup time, and can now contribute to significant Cover/lid cost savings for the user in their day-to-day operations. Strap joining negative plates in parallel Negative pasted plate lead alloy grid Polypropylene container/jar Separator Internal and external components of a valve-regulated lead-acid (VRLA) battery 4 Eaton The large UPS battery handbook 2. Lithium-ion 3. VLA. Lithium based batteries have multiple significant benefits VLA or flooded-cell batteries have thick lead-based plates over alternative DC storage techniques for UPS applications.

6 That are flooded with an acid electrolyte. This is a highly The technology has matured in heavy duty applications like reliable design failures normally don't occur until halfway electric vehicles, and is considered ideal for critical power through their 20-year pro-rated life, at which time the failure backup. Small size and light weight are the primary benefits, mode is most often a short circuit. This situation is not an but additional features like built-in battery management (not extreme emergency because any one shorted cell only affects just monitoring), make lithium-ion an attractive alternative to overall reserve time by a very small percentage. However, while Overview traditional batteries. they're very reliable with a long life, there are downsides to flooded-cell batteries. They require more safety measures and a In addition, their high cycle-count (charge-discharge cycles), and space-consuming separate battery room to use.

7 Faster recharge times compared with lead batteries allows their use in non-traditional UPS applications, like grid sharing, peak Regardless of the differences in UPS battery types, both shaving, and industrial or process control support. require monitoring and maintenance to ensure maximum life and system availability. The battery management system is deployed in each battery , as well as in a system level master controller. It manages charge current, voltage , and cell voltage balance, while making adjustments as necessary to eliminate any chance of overtemperature. If temperatures rise above safe levels, the management system will independently disconnect the battery or string via multiple different disconnection means, and notify the user via the battery cabinet monitor, and an alarm on the UPS. Overall, a lithium-ion battery system provides lower TCO. through comparable Capex costs, and Opex savings via a longer replacement interval, and Lithium-ion battery systems Flooded-cell batteries require more advanced maintenance but have a its ability to operate at higher provide a reliable and flexible longer battery service life ambinet temperatures.

8 Solution that ensures 24/7. system uptime Other common causes of UPS failure Did you know? Batteries may be the number one contributor to UPS failure, but these are three other vulnerable components that shouldn't be overlooked. Capacitors: A capacitor is a fairly Filters: Because dust may block Fans: They may slow down or stall simple device that stores and releases air filters and cause a UPS to shut as they age, and a resulting over electrical energy. They can be as small down due to overheating, they must temperature condition will shut down as a thumbnail or as large as a soda be inspected every month. Replacing the UPS unexpectedly. Watch for fan can. A typical UPS contains a dozen or filters is an inexpensive component of fail alarms every week, and plan for more of different types and sizes. Like an effective UPS maintenance plan. replacement at the 8-10 year mark batteries, capacitors degrade over time.

9 At the latest. There may not be visible effects upon immediate failure, but one failure will leave other capacitors to work harder and shorten lifespan. 5 Eaton The large UPS battery handbook battery arrangement and power In most UPSs, you don't use just one cell at a time. They're normally grouped together serially to form higher voltages, or in parallel to form higher currents. In a serial arrangement, the voltages add up. In a parallel arrangement, the currents add up. However, batteries are not quite composition during charging and A. node: The terminal where as linear as the two graphics to discharging, and the electrolyte the current flows in the right depict. For example, is dilute sulfuric acid. In other all batteries have a maximum words, they contain components C. athode: The terminal current they can produce; a that react with each other to where the current flows out Overview 500 milliamp-hour battery can't create DC electrical current.

10 V. alve (used in VRLA. produce 30,000 milliamps for These components are: batteries): Used to vent the one second, because there's no E. lectrolyte: The medium build-up of gas that goes way for its chemical reactions that provides the ion beyond pre-determined levels to happen that quickly. It is also important to realize that at transport mechanism S. eparator: A device used higher current levels, batteries between the positive and for the physical separation can produce a lot of heat, which negative electrodes of a and electrical isolation of wastes some of their power. cell, immobilized in VRLA. electrodes of opposing batteries, and in liquid form polarities Like all batteries, UPS batteries in flooded-cell batteries are electrochemical devices. A J. ar: The container holding the UPS uses a lead-acid storage G. rid: A perforated or battery components battery in which the electrodes corrugated lead or lead alloy are grids of lead containing plate used as a conductor and lead oxides that change in support for the active material Replacement lead acid batteries for data room battery cabinets Connecting in series [double voltage , same capacity (ah)].