ECT[DIN]ECT[DIN] 2-Wire Isolator, Converter, and Repeater in an Aluminum HousingMay 2016206-725-00C2-Wire Isolator, Converter, and Repeater in an Aluminum HousingTable of Contents Introduction ..3 Specifications & Ordering Information ..4-5 Input-Loop Powered ..4 Output-Loop Powered ..5 Calibration ..6 Calibration Setup ..6 Calibration Diagrams ..7 Calibration Procedure ..8 Installation ..9 Installation in Hazardous Locations ..10 Electrical Connections ..10 Customer Support ..11 ECTThe Interface Solution Experts 32-Wire Isolator, Converter, and Repeater in an Aluminum HousingIntroductionThis is the users manual for Moore Industries line of 2-wire, Economy Signal Isolators and Converters, the ECT [DIN].

ECT. The Interface Solution Experts . 3. 2-ire Isolator, Converter, and Repeater in an Aluminum Housing. Introduction. This is the users’ manual for Moore Industries’ line of

Tags:

  Industreis, Romeo, Moore industries

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of ECT - Moore Industries International

1 ECT[DIN]ECT[DIN] 2-Wire Isolator, Converter, and Repeater in an Aluminum HousingMay 2016206-725-00C2-Wire Isolator, Converter, and Repeater in an Aluminum HousingTable of Contents Introduction ..3 Specifications & Ordering Information ..4-5 Input-Loop Powered ..4 Output-Loop Powered ..5 Calibration ..6 Calibration Setup ..6 Calibration Diagrams ..7 Calibration Procedure ..8 Installation ..9 Installation in Hazardous Locations ..10 Electrical Connections ..10 Customer Support ..11 ECTThe Interface Solution Experts 32-Wire Isolator, Converter, and Repeater in an Aluminum HousingIntroductionThis is the users manual for Moore Industries line of 2-wire, Economy Signal Isolators and Converters, the ECT [DIN].

2 Available in configurations that accept a variety of inputs, the principal function of the ECT family of products is to provide low cost isolation (up to 1500 Vrms) between instruments at either end of a process loop. Additionally, some ECT configurations perform signal conversion. They accept either dc or ac voltages and provide a precise, industry-standard 4-20mA output. The ECT is a highly cost-effective means of protecting process signals from distortions associated with ground loops, motor noise and other common types of ambient electrical CT/PTSPANZERO+PS PS4-20mA10-50mA1-5V0-10V0-150AC0-250AC0- 5 AAC4-20mA10-50mA1-5 VOptionsThere are several options available for the ECT: EM Externally Mounted Transformer, for use with the 0-5 Aac input configuration, this option consists of a toroidial transformer that physically separates high-level current input from the receiving device in a process loop.

3 This provides the added convenience of allowing the servicing of receivers without having to interrupt process signals. RF RFI/EMI Protection, available for use with our new aluminum housings, this option provides you with outstanding protection against RFI and EMI interference. (requires -EM option for ac current input). With this option, the ECT will not be affected by more than of span at 30 V/m @ 1. The ECT is available in a variety of configurations that accept a myriad of inputs and The Interface Solution Experts2-Wire Isolator, Converter, and Repeater in an Aluminum HousingECTS pecifications2-Wire, Input-Loop Powered ModelsAccuracy: of span Stability: of reading per year Isolation: 500 Vrms between input and output Output Response: 20msec maximum to 99% of output Ripple: 10mV peak-to-peak maximum measured across 250 resistor Over-Voltage Protection: 48V, maximum on output.

4 48V, reverse polarity protection on output Maximum Input Overrange: 200% of full scale Output Current Limiting: 30mA with 250 output load Burden: Volts when outputs are shorted for 4-20mA inputs, with 250 load (Output load voltage is reflected on input. Output should be trimmed for anticipated output load) Operating Range: -29 C to +82 C -20 F to +180 F Storage Range: -40 C to +85 C (-40 F to +185 F) Ambient Temperature Effect: of span/ C; of span/ C gain change Relative Humidity: 0-95% non-condensing RFI/EMI Immunity: Without RF option: Less than of span error when tested at 10V/m @ 20-1000 MHz With RF option: less than of span at 30V/m @ 20-1000 Mhz Common Mode Rejection: Exceeds 95dB at 60Hz with a limit of 500 Vrms Type: Front panel pots Trim.

5 1% DIN Housing, 145 grams (5 oz)Ordering Information Unit Input Output Power Options Housing ECT 2-wire (Input-Loop Powered) Isolator/ Converter 4-20MA into 275 4-20MA into 0-250 Current Loop Excitation at 4mA: volts loop powered with 4-20mA (plus voltage across output load) RF Enhanced RFI/EMI filtering provides 30V/m @ 20-1000 Mhz protection with less than of span error DIN Aluminum DIN-style housing mounts on 32mm G-type (EN50035) and 35mm Top Hat (EN50022) rails Performance Performance (continued) Ambient Conditions Ambient Conditions (Continued) Adjustments WeightWhen ordering, specify: Unit / Input / Output / Power / Options [Housing] Model number example.

6 ECT / 4-20MA / 4-20MA / / RF [DIN]ECTThe Interface Solution Experts 52-Wire Isolator, Converter, and Repeater in an Aluminum Housing2-Wire, Output-Loop Powered ModelsSpecificationsAccuracy: of span; ( for 0-150AC inputs) Stability: of reading per year Isolation: Without RF option: 1500 Vrms between input and output; With RF option: 500 Vrms between input and output; Output Response Time: 100msec to 99% of output max for DC inputs; 400msec to 99% of output for AC inputs Ripple: 10mV peak-to-peak maximum measured across a 250 ohm resistor Over-Voltage Protection: 48V, maximum on output; 48V reverse polarity protection on output Maximum Input Overrange: 250% of full scale for current inputs; 150% of full scale for DC voltage inputs Burden: 1V maximum with 4-20mA input; maximum with 0-5A input; Load Capability: Vs-12 Vdc 20mA Output Current Limiting: 25mA typical; 30mA max.

7 Operating Range: -40 C to +85 C -40 F to +185 F Storage Range: -40 C to +85 C (-40 F to +185 F) Ambient Temperature Ef-fect: of span/ C typical; of span/ C max. Relative Humidity: 0-95% non-condensing RFI/EMI Immunity: Without RF option: Less than of span error when tested at 10V/m @ 20-1000 MHz With RF option: less than of span at 30V/m @ 20-1000 Mhz Common Mode Rejection: Exceeds 95dB @ 60Hz with a limit of 1500 Vrms Type: Front panel pots Span: 10% Zero: 5% (non-interactive when span is set first) DIN Housing, 145g (5 oz)Ordering Information Unit Input Output Power Options Housing ECT 2-wire (Output-Loop Powered)

8 Isolator, Converter, and Repeater 4-20MA into 50 1-5V into 1M 0-10V into 1M 0-150AC into 100K 0-5 AAC into 4-20MA into 600 with 24 Vdc power supply 12-42DC RF Enhanced RFI/EMI filtering provides 30V/m @ 20-1000 Mhz protection with less than of span error EM Externally-mounted input transformer for current input (available with 0-5 AAC input type only)DIN Aluminum DIN-style housing mounts on 32mm G-type (EN50035) and 35mm Top Hat (EN50022) rails Performance Performance (continued) Ambient Conditions Ambient Conditions (Continued) Adjustments WeightWhen ordering, specify: Unit / Input / Output / Power / Options [Housing] Model number example: ECT / 4-20MA / 4-20MA / 12-42DC RF [DIN]= 6 The Interface Solution Experts2-Wire Isolator, Converter, and Repeater in an Aluminum HousingECTT able 1.

9 Gathering the equipment for 2-wire ECT calibration Voltage or Current Calibrator Power Supply Load Resistor Multimeter ScrewdriverAdjustable, calibrated to an accuracy of (EDC Model CR 103 or MV 105, or equivalent) Rotek Model 811A (or equivalent) recommended for calibrating ac input units. Calibrated, 24 Vdc, 10%, nominal 250 ohms ( ) precision Calibrated to an accuracy of , minimum (Keithley Model 197, or Fluke Model 8840 or 8842, or equivalent) Standard (Blade-type), head width ( in), maximumDevice SpecificationsCalibrationPrior to shipment, every ECT is subjected to rigorous testing by our team of skilled technicians.

10 Every product Moore Industries manufactures, sells and services is guaranteed to meet the strict quality standards that have become synonymous with our company placing your ECT into service, a bench check of basic operation is recommended to ensure that the unit hasn t sustained any damage during transit, and to set zero and span for your unit should be: Checked to verify that the appropriate ECT model has been ordered for the intended application. Connected in a calibration setup (described later in this section) and checked for desired output. Adjusted for desired zero and SetupTable 1 lists the equipment you will need to bench check the ECT.