2014 OREGON fire CODE101 CHAPTER 9 fire PROTECTION SYSTEMSSECTION Scope. The provisions of this chapter shall specifywhere fire PROTECTION SYSTEMS are required and shall apply tothe design, installation, inspection, operation, testing andmaintenance of all fire PROTECTION Construction documents. The fire code official shallhave the authority to require construction documents and cal-culations for all fire PROTECTION SYSTEMS and to require permitsbe issued for the installation, rehabilitation or modification ofany fire PROTECTION system . Construction documents for fireprotection SYSTEMS shall be submitted for review and approvalprior to system Statement of compliance. Before requesting finalapproval of the installation, where required by the fire codeofficial, the installing contractor shall furnish a writtenstatement to the fire code official that the subject fire pro-tection system has been installed in accordance withapproved plans and has been tested in accordance with themanufacturer s specifications and the appropriate installa-tion standard.

FIRE PROTECTION SYSTEMS 2014 OREGON FIRE CODE 103 fire code official by the monitoring service provider being terminated. 901.10 Recall of fire protection components. Any fire pro- tection system component regulated by this code that is the subject of …

Tags:

  System, Protection, Fire, Fire protection system

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of FIRE PROTECTION SYSTEMS - ecodes.biz

1 2014 OREGON fire CODE101 CHAPTER 9 fire PROTECTION SYSTEMSSECTION Scope. The provisions of this chapter shall specifywhere fire PROTECTION SYSTEMS are required and shall apply tothe design, installation, inspection, operation, testing andmaintenance of all fire PROTECTION Construction documents. The fire code official shallhave the authority to require construction documents and cal-culations for all fire PROTECTION SYSTEMS and to require permitsbe issued for the installation, rehabilitation or modification ofany fire PROTECTION system . Construction documents for fireprotection SYSTEMS shall be submitted for review and approvalprior to system Statement of compliance. Before requesting finalapproval of the installation, where required by the fire codeofficial, the installing contractor shall furnish a writtenstatement to the fire code official that the subject fire pro-tection system has been installed in accordance withapproved plans and has been tested in accordance with themanufacturer s specifications and the appropriate installa-tion standard.

2 Any deviations from the design standardsshall be noted and copies of the approvals for such devia-tions shall be attached to the written Permits. Permits shall be required as set forth in Sec-tions and Installation. fire PROTECTION SYSTEMS shall be maintainedin accordance with the original installation standards for thatsystem. Required SYSTEMS shall be extended, altered or aug-mented as necessary to maintain and continue protectionwhenever the building is altered, remodeled or added to. Alter-ations to fire PROTECTION SYSTEMS shall be done in accordancewith applicable Required fire PROTECTION SYSTEMS . fire protectionsystems required by this code or the International BuildingCode shall be installed, repaired, operated, tested and main-tained in accordance with this Nonrequired fire PROTECTION SYSTEMS . Any fireprotection system or portion thereof not required by thiscode or the International Building Code shall be allowed tobe furnished for partial or complete PROTECTION providedsuch installed system meets the applicable requirements ofthis code and the International Building fire areas.

3 Where buildings, or portions thereof,are divided into fire areas so as not to exceed the limitsestablished for requiring a fire PROTECTION system in accor-dance with this chapter, such fire areas shall be separatedby fire barriers constructed in accordance with Section 707of the International Building Code or horizontal assembliesconstructed in accordance with Section 711 of the Interna-tional Building Code, or both, having a fire -resistance ratingof not less than that determined in accordance with of the International Building Code. Additional fire PROTECTION SYSTEMS . In occupan-cies of a hazardous nature, where special hazards exist inaddition to the normal hazards of the occupancy, or wherethe fire code official determines that access for fire appara-tus is unduly difficult, the fire code official shall have theauthority to require additional safeguards. Such safeguardsinclude, but shall not be limited to, the following: automaticfire detection SYSTEMS , fire alarm SYSTEMS , automatic fire -extinguishing SYSTEMS , standpipe SYSTEMS , or portable orfixed extinguishers.

4 fire PROTECTION equipment requiredunder this section shall be installed in accordance with thiscode and the applicable referenced Appearance of equipment. Any device that hasthe physical appearance of life safety or fire protectionequipment but that does not perform that life safety or fireprotection function shall be Pump and riser room size. fire pump and auto-matic sprinkler system riser rooms shall be designed withadequate space for all equipment necessary for the installa-tion, as defined by the manufacturer, with sufficient work-ing space around the stationary equipment. Clearancesaround equipment to elements of permanent construction,including other installed equipment and appliances, shall besufficient to allow inspection, service, repair or replacementwithout removing such elements of permanent constructionor disabling the function of a required fire -resistance-ratedassembly. fire pump and automatic sprinkler system riserrooms shall be provided with a door(s) and an unobstructedpassageway large enough to allow removal of the largestpiece of Installation acceptance testing.

5 fire detection andalarm SYSTEMS , fire -extinguishing SYSTEMS , fire hydrant sys-tems, fire standpipe SYSTEMS , fire pump SYSTEMS , private fireservice mains and all other fire PROTECTION SYSTEMS and appurte-nances thereto shall be subject to acceptance tests as containedin the installation standards and as approved by the fire codeofficial. The fire code official shall be notified before anyrequired acceptance Occupancy. It shall be unlawful to occupy any por-tion of a building or structure until the required fire detec-tion, alarm and suppression SYSTEMS have been tested Inspection, testing and maintenance. fire detection,alarm, and extinguishing SYSTEMS , mechanical smoke exhaustsystems, and smoke and heat vents shall be maintained in anoperative condition at all times, and shall be replaced orrepaired where defective. Nonrequired fire PROTECTION systemsand equipment shall be inspected, tested and maintained orremoved.

6 Standards. fire PROTECTION SYSTEMS shall beinspected, tested and maintained in accordance with the ref-erenced standards listed in Table Page 101 Wednesday, January 15, 2014 12:28 PMFIRE PROTECTION SYSTEMS1022014 OREGON fire CODETABLE PROTECTION system MAINTENANCE Records. Records of all system inspections, testsand maintenance required by the referenced standardsshall be maintained on the premises for a minimum ofthree years and shall be copied to the fire code officialupon Records information. Initial records shallinclude the name of the installation contractor, type ofcomponents installed, manufacturer of the components,location and number of components installed per shall also include the manufacturers operationand maintenance instruction manuals. Such recordsshall be maintained on the SYSTEMS out of service. Where a required fire protec-tion system is out of service, the fire department and the firecode official shall be notified immediately and, whererequired by the fire code official, the building shall either beevacuated or an approved fire watch shall be provided for alloccupants left unprotected by the shutdown until the fire pro-tection system has been returned to utilized, fire watches shall be provided with at leastone approved means for notification of the fire departmentand their only duty shall be to perform constant patrols of theprotected premises and keep watch for Impairment coordinator.

7 The building ownershall assign an impairment coordinator to comply with therequirements of this section. In the absence of a specificdesignee, the owner shall be considered the Tag required. A tag shall be used to indicate thata system , or portion thereof, has been removed from Placement of tag. The tag shall be posted at eachfire department connection, system control valve, firealarm control unit, fire alarm annunciator and fire com-mand center, indicating which system , or part thereof, hasbeen removed from service. The fire code official shallspecify where the tag is to be Preplanned impairment programs. Preplannedimpairments shall be authorized by the impairment coordi-nator. Before authorization is given, a designated individ-ual shall be responsible for verifying that all of thefollowing procedures have been implemented:1. The extent and expected duration of the impairmenthave been The areas or buildings involved have been inspectedand the increased risks Recommendations have been submitted to manage-ment or building The fire department has been The insurance carrier, the alarm company, buildingowner/manager, and other authorities having juris-diction have been The supervisors in the areas to be affected have A tag impairment system has been Necessary tools and materials have been assembledon the impairment Emergency impairments.

8 When unplannedimpairments occur, appropriate emergency action shall betaken to minimize potential injury and damage. Theimpairment coordinator shall implement the steps outlinedin Section Restoring SYSTEMS to service. When impairedequipment is restored to normal working order, the impair-ment coordinator shall verify that all of the following pro-cedures have been implemented:1. Necessary inspections and tests have been con-ducted to verify that affected SYSTEMS are Supervisors have been advised that PROTECTION The fire department has been advised that protectionis The building owner/manager, insurance carrier,alarm company and other involved parties have beenadvised that PROTECTION is The impairment tag has been Removal of or tampering with equipment. It shall beunlawful for any person to remove, tamper with or otherwisedisturb any fire hydrant, fire detection and alarm system , firesuppression system , or other fire appliance required by thiscode except for the purpose of extinguishing fire , trainingpurposes, recharging or making necessary repairs, or whenapproved by the fire code Removal of or tampering with , gates, doors, barricades, chains, enclosures, signs,tags or seals which have been installed by or at the direc-tion of the fire code official shall not be removed,unlocked, destroyed, tampered with or otherwise vandal-ized in any Termination of monitoring service.

9 For fire alarmsystems required to be monitored by this code, notice shall bemade to the fire code official whenever alarm monitoring ser-vices are terminated. Notice shall be made in writing, to theSYSTEMSTANDARDP ortable fire extinguishers NFPA 10 Carbon dioxide fire -extinguishing system NFPA 12 Halon 1301 fire -extinguishing SYSTEMS NFPA 12 ADry-chemical extinguishing SYSTEMS NFPA 17 Wet-chemical extinguishing SYSTEMS NFPA 17 AWater-based fire PROTECTION SYSTEMS NFPA 25 fire alarm SYSTEMS NFPA 72 Mechanical smoke exhaust systemsNFPA 204 Smoke and heat ventsNFPA 204 Water-mist SYSTEMS NFPA 750 Clean-agent extinguishing SYSTEMS NFPA Page 102 Wednesday, January 15, 2014 12:28 PMFIRE PROTECTION SYSTEMS2014 OREGON fire CODE103fire code official by the monitoring service provider beingterminated. Recall of fire PROTECTION components. Any fire pro-tection system component regulated by this code that is thesubject of a voluntary or mandatory recall under federal lawshall be replaced with approved, listed components in com-pliance with the referenced standards of this code.

10 The firecode official shall be notified in writing by the buildingowner when the recalled component parts have Definitions. The following terms are defined in Chap-ter 2: ALARM NOTIFICATION APPLIANCE. ALARM SIGNAL. ALARM VERIFICATION FEATURE. ANNUNCIATOR. AUDIBLE ALARM NOTIFICATION APPLIANCE. AUTOMATIC. AUTOMATIC fire -EXTINGUISHING system . AUTOMATIC SMOKE DETECTION system . AUTOMATIC SPRINKLER system . AVERAGE AMBIENT SOUND LEVEL. CARBON DIOXIDE EXTINGUISHING system . CLEAN AGENT. CONSTANTLY ATTENDED LOCATION. DELUGE system . DETECTOR, HEAT. DRY-CHEMICAL EXTINGUISHING AGENT. ELEVATOR GROUP. EMERGENCY ALARM system . EMERGENCY VOICE/ALARM COMMUNICATIONS. fire ALARM BOX, MANUAL. fire ALARM CONTROL UNIT. fire ALARM SIGNAL. fire ALARM system . [B] fire AREA. fire DETECTOR, AUTOMATIC. fire PROTECTION system . fire SAFETY FUNCTIONS. FIXED BASE OPERATOR (FBO). FOAM-EXTINGUISHING system . HALOGENATED EXTINGUISHING system . IMPAIRMENT COORDINATOR. INITIATING DEVICE.