HIM-17RJ30-05404 INSTALLATION INSTRUCTIONS & PARTS LISTHORIZONTAL STEAM AND HOT WATER unit HEATERSUnit : READ THIS MANUAL AND ALL LABELS ATTACHED TO THE unit CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THESE UNITS! CHECK unit DATA PLATE FOR TYPE OF GAS AND ELECTRICAL SPECIFICATIONS AND MAKE CERTAIN THAT THESE AGREE WITH THOSE AT POINT OF INSTALLATION. RECORD THE unit MODEL AND SERIAL No.(s) IN THE SPACE PROVIDED. RETAIN FOR FUTURE S RESPONSIBILITYI nstaller Please Note: This equipment has been tested and inspected. It has been shipped free from defects from our factory. However, during shipment and installation, problems such as loose wires, leaks or loose fasteners may occur. It is the installer s responsibility to inspect and correct any problems that may be found. Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment.

him-17r j30-05404 installation instructions & parts list horizontal steam and hot water unit heaters unit no. serial no. attention: read this manual and all labels attached to the unit carefully before

Tags:

  Unit, Water, Horizontal, Steam, Heaters, Horizontal steam and hot water unit, Horizontal steam and hot water unit heaters

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of HORIZONTAL STEAM AND HOT WATER UNIT …

1 HIM-17RJ30-05404 INSTALLATION INSTRUCTIONS & PARTS LISTHORIZONTAL STEAM AND HOT WATER unit HEATERSUnit : READ THIS MANUAL AND ALL LABELS ATTACHED TO THE unit CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THESE UNITS! CHECK unit DATA PLATE FOR TYPE OF GAS AND ELECTRICAL SPECIFICATIONS AND MAKE CERTAIN THAT THESE AGREE WITH THOSE AT POINT OF INSTALLATION. RECORD THE unit MODEL AND SERIAL No.(s) IN THE SPACE PROVIDED. RETAIN FOR FUTURE S RESPONSIBILITYI nstaller Please Note: This equipment has been tested and inspected. It has been shipped free from defects from our factory. However, during shipment and installation, problems such as loose wires, leaks or loose fasteners may occur. It is the installer s responsibility to inspect and correct any problems that may be found. Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment.

2 RECEIVING INSTRUCTIONSI nspect shipment immediately when received to determine if any damage has occurred to the unit during shipment. After the unit has been uncrated, check for any visible damage to the unit . Turn fan by hand to determine if damage has occurred. If any damage is found, the consignee should sign the bill of lading indicating such damage and immediately file claim for damage with the transportation NORTH ELM ST., WESTFIELD, MA 01085 TEL: (413) 568-9571 FAX: (413) OF CONTENTSGENERAL SAFETY INFORMATION ..3 SPECIFICATIONS Dimensional Data ..4 STEAM Performance Data ..5 STEAM Calculations & Correction Factors ..6 Hot WATER Performance Data ..7 Hot WATER Calculations & Correction Factors ..8 Technical Data ..9 Motor Data ..10 LOCATION ..11 INSTALLATION unit Mounting ..12 Piping ..12-16 The following terms are used throughout this manual, in addition to ETL requirements, to bring attention to thepresence of potential hazards or to important information concerning the product: HORIZONTAL hydronic unit heaters are available in both serpentine and header type units.

3 Serpentine units offer outputs from 8,030 to 35,900 BTU s ( to kW) and are ideal for hot WATER (only) installations with limited clearances. Header type HORIZONTAL units range from 18,000 to 360,000 ( to kW) and can operate with either hot WATER or STEAM . Both units are furnished Figure 1 SerpentineType Indicates an imminently hazardous situation which, if not avoided, will result in death, serious injury or substantial property damage. Indicates an imminently hazardous situation which, if not avoided, could result in death, serious injury or substantial property damage. Indicates an imminently hazardous situation which, if not avoided, may result in minor injury or property : Used to notify of special instructions on installation, operation or maintenance which are important to equipment but not related to personal injury CONNECTIONS ..17 Operation ..17 Thermostat Wiring and Location ..17 WIRING INSTALLATION.

4 18 OPTIONS ..19 MAINTENANCE ..20 REPLACEMENT PARTS ..21 TROUBLESHOOTING GUIDE ..22 WARRANTY ..23 INSPECTION SHEET ..24 NOTICE: It is the owner s responsibility to provide any scaffolding or other apparatus required to perform emergency service or annual/periodic maintenance to this 2 HeaderTypewith totally enclosed motors, with explosion proof motors as optional on header types. The designs are certified by ETL to and UL1995. Do not alter these units in any way and do not attach any ductwork to the units. If you have any questions after reading this manual, contact the Failure to comply with the general safety information may result in extensive property damage, severe personal injury or death. Do not alter the unit heater in any way or damage to the unit and/or severe personal injury or death may occur! Disconnect all power supplies before installing or servicing the heater. If the power disconnect is out of sight, lock it in the open position and tag it to prevent unexpected application of power.

5 Failure to do so could result in fatal electric shock, or severe personal injury. Insure that all power sources conform to the requirements of the unit heater or damage to the unit will result!Follow installation instructions CAREFULLY to avoid creating unsafe conditions. All external wiring must conform to applicable current local codes, and to the latest edition of the National Electric Code ANSI/NFPA No. 70. In Canada, all external wiring must conform to the Canadian Electric Code, Part 1 CSA Standard All wiring should be done and checked by a qualified electrician using copper wire only. All STEAM and hot WATER connections should be made and leak-tested by a suitably qualified individual, per instructions in this manual. Also follow procedures listed on the unit Equipment Start-Up Sheet located in this certain that the power source conforms to the electrical requirements of the heater.

6 Do not depend upon a thermostat or other switch as sole means of disconnecting power when installing or servicing heater. Always disconnect power at main circuit breaker as described above. Failure to do so could result in fatal electric attention must be given to any grounding information pertaining to this heater. To prevent the risk of electrocution, the heater must be securely and adequately grounded. This should be accomplished by connecting a grounded conductor between the service panel and the heater. To ensure a proper ground, the grounding means must be tested by a qualified SAFETY INFORMATIONDo not insert fingers or foreign objects into the heater or its air moving device. Do not block or tamper with the heater in any manner while in operation or just after it has been turned off, as some parts may be hot enough to cause meet ETL and OSHA requirements, units mounted below 8 feet ( ) from the floor must be equipped with an OSHA fan guard.

7 It is good practice to have a shutoff switch on the electrical power lines controlling the heater. Whenever a unit is serviced, shut power off to the unit . Since these units are installed in most instances higher than 8 feet ( ), proper type of ladders or scaffolding should be used, as set up by OSHA requirements (see Notice on page 2).In industrial plants, professional maintenance crews should service this HORIZONTAL unit heaters are shipped fully assembled and may be used for STEAM or hot WATER applications. Coils are factory tested at 250 psig ( kg).Each unit is packaged individually and marked for proper identification. Use normal care in handling and during installation to prevent damage to the coils fins, fan and otherwise specified, the following conversions may be used for calculating SI unit measurements:1 foot = m1 inch = mm1 psig = kPa1 pound = kg1 gallon = L1 inch WATER column = kPameter/second = FPM = CFM x Btu per hour = kW1000 Btu/Cu.

8 Ft. = MJ/m31 cubic foot = m34145 8(371)145 8(371)171 8(435)171 8(435)183 8(467)207 8(530)195 8(498)207 8(530)233 8(594)233 8(594)245 8(625)277 8(708)277 8(708)333 8(848)12 (311)12 (311)14 (375)14 (375)16(406)18 (470)17 (438)18 (470)21(533)21(533)22 (565)25 (648)25 (648)31(787)4566788899910101318243648607 2849610812013214415618020424028030036075 16(186)75 16(186)89 16(217)89 16(217)93 16(233)107 16(265)913 16(249)107 16(265)1111 16(297)1111 16(297)125 16(313)1315 16(354)1315 16(354)1611 16(424)15(381)18(457)20 (521)20 (521)21 (552)24 (616)24(610)25 (641)27 (705)27 (705)29(737)30 (768)30 (768)37 (959)7 (191)9(229)10 (260)10 (260)107 8(276)121 8(308)12(305)125 8(321)137 8(352)137 8(352)14 (368)151 8(384)151 8(384)187 8(479)61 8(156)61 8(156)57 8(149)57 8(149)6(152)61 8(156)65 16(160)65 16(160)65 16(160)65 16(160)63 8(162)81 8(206)81 8(206)9(229)215 16(75)215 16(75)215 16(75)215 16(75)215 16(75)215 16(75)33 16(81)33 16(81)33 16(81)33 16(81)33 16(81)33 16(81)

9 33 16(81)33 16(81)3 (83)3 (83)511 16(144)51 16(129)51 16(129)511 16(144)7 (191)611 16(170)75 8(194)77 16(194)77 16(194)57 8(149)95 8(244)95 8(244)93 8(238)93 8(238)117 16(291)1015 16(278)111 16(281)1113 16(300)1313 16(351)13(330)14(356)13 (349)13 (349)14(356)17 (451)185 8(473)9 (241)12 (318)15(381)15(381)16 (413)18 (476)17 (445)18 (476)21 (540)21 (540)22 (572)23 (603)23 (603)31 (794)1 (32)1 (32)1 (32)1 (32)1 (32)1 (32)1 (38)1 (38)1 (38)1 (38)1 (38)2(51)2(51)2(51)2 (57)2 (57)1 (44)1 (44)1 (44)1 (44)1 (44)1 (44)1 (44)1 (44)1 (44)1 (44)1 (44)1 (44)127 8(327)127 8(327)153 8(391)153 8(391)165 8(422)191 8(486)177 8(454)191 8(486)215 8(549)215 8(549)227 8(581)261 8(664)261 8(664)315 8(803)9(229)10(254)12(305)12(305)14(356) 14(356)16(406)18(457)18(457)18(457)18(45 7)20(508)20(508)24(610)26( )30( )41( )41( )44( )47( )49( )59( )74( )74( )90( )143(65)154(70)203(92)22 ( )24 ( )25 ( )31 ( )APPROXIMATESHIP (kg)DIMENSIONAL DATAF igure 3 Serpentine Type Models 108A, 118A, 125A, 136 ATable 2 Figure 4 Header ModelsNOMINAL FAN DIAMETER inches (mm)NUMBEROFLOUVERSUNIT SIZE* Applies to standard motor with standard fan guard.

10 When optional motors or OSHA fan guards are requested, dimensions will vary according to the substitutions : 1. OSHA guard standard on all serpentine models and header models 18 thru 48 supplied with 1 phase motors (dimensions shown in tables). 2. Standard motor and standard guard shown. 3. All 3 phase and explosion proof motors are shelf mounted. A B C D E F G* H* J K L M N inches inches inches inches inches inches inches inches inches inches inches inches inches (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm)Figure 4 Header Type Models 18 thru 360 Hinches (mm)Binches (mm)APPROXIMATE SHIP WT. lbs. (kg)NOMINAL FAN DIAMETER inches (mm)NUMBEROFLOUVERSC inches (mm)108A118A125A136 AWinches (mm) unit SIZE5556 Table 1 Figure 3 Serpentine ModelsNOTE: Motors are totally enclosed, thermally protected, sleeve bear-ing, with 2"(h) x 4"(w) conduit connection boxes.