Manual: Rosemount™ 8600 Series Vortex Flowmeter

Reference Manual00809-0100-4860, Rev BDOctober 2016 rosemount 8600 Series Vortex FlowmeteriiiReference manual 00809-0100-4860, Rev BDTable of ContentsOctober2016 Table of to use this manual .. messages .. description .. 1 1 Section 1: Introduction 2 Section 2: .. variables .. Variable (PV) .. of range .. output .. other variables .. setup.. configuration .. K-factor .. type .. pipe ID (Inside Diameter) .. mapping .. units .. values .. damping .. adjust filter .. 18 3 Section 3: messages .. considerations .. sizing .. orientation .. material selection .. considerations.. locations .. configuration ..27 ContentsivReference Manual00809-0100-4860, Rev BDTable of ContentsOctober 2016 Table of mode vs.

Reference Manual 00809-0100-4860, Rev BD Title Page October 2016 Title Page vii Rosemount™ 8600D Smart Vortex Flowmeter NOTICE Read this manual before working with the prod uct.

Tags:

  Manual, Series, Rosemount, Vortex, Flowmeter, 6800, Vortex flowmeter, Rosemount 8600 series vortex flowmeter

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Manual: Rosemount™ 8600 Series Vortex Flowmeter

1 Reference Manual00809-0100-4860, Rev BDOctober 2016 rosemount 8600 Series Vortex FlowmeteriiiReference manual 00809-0100-4860, Rev BDTable of ContentsOctober2016 Table of to use this manual .. messages .. description .. 1 1 Section 1: Introduction 2 Section 2: .. variables .. Variable (PV) .. of range .. output .. other variables .. setup.. configuration .. K-factor .. type .. pipe ID (Inside Diameter) .. mapping .. units .. values .. damping .. adjust filter .. 18 3 Section 3: messages .. considerations .. sizing .. orientation .. material selection .. considerations.. locations .. configuration ..27 ContentsivReference Manual00809-0100-4860, Rev BDTable of ContentsOctober 2016 Table of mode vs.

2 Saturation output values .. indicator option .. body installation tasks .. direction .. bolts.. Flowmeter mounting .. grounding .. considerations .. installations .. connections .. installation .. gland .. the transmitter case .. procedure.. electronics .. configuration .. the indicator .. protection .. the Transient Protector .. 44 4 Section 4: .. test .. output test .. simulation .. trim(Digital-to-Analog Trim) .. D/A trim .. freq at URV .. functionality .. set-up .. meter .. outputs .. processing .. information .. 64vReference manual 00809-0100-4860, Rev BDTable of ContentsOctober2016 Table of Contents 5 Section 5: messages .. tables .. troubleshooting.. messages .. test points.

3 Messages on LCD .. procedures .. replacement .. the terminal block in the housing .. the electronics boards .. the electronics housing .. the sensor .. electronics procedure .. cable at the electronics housing .. the housing orientation .. sensor replacement (MTA option only).. of material ..88 AAppendix A: Specifications and Reference .. specifications .. flow ranges .. specifications .. accuracy .. specifications .. drawings .. 100 BAppendix B: Product .. certifications .. manufacturing locations .. certifications (IECEx) .. certifications (NEPSI) .. certifications (ATEX) .. Conformity (EAC) .. Standards Association (CSA) ..109viReference Manual00809-0100-4860, Rev BDTable of ContentsOctober 2016 Table of Contents CAppendix C: Electronics messages.

4 Verification .. verification using flow simulation mode .. flow rate simulation .. flow rate simulation .. verification using an external frequency generator .. output variables with known input frequency .. units .. units ..120 DAppendix D: HART Menu .. 123 Reference manual 00809-0100-4860, Rev BDTitle PageOctober 2016viiTitle PageRosemount 8600 DSmart Vortex FlowmeterNOTICERead this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the contents before installing, using, or maintaining this the United States, Emerson Process Management has two toll-free assistance numbers:Customer CentralTechnical support, quoting, and order-related (7:00 am to 7:00 pm CST)North American Response CenterEquipment service (24 hours includes Canada)Outside of the United States, contact your local Emerson Process Management products described in this document are NOT designed for nuclear-qualified applications.

5 Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate information on rosemount nuclear-qualified products, contact your local Emerson Process Management Sales Manual00809-0100-4860, Rev BDTitle PageOctober 2016 Title Page1 Reference manual 00809-0100-4860, Rev BDIntroductionOctober to use this manualThis manual provides installation, configuration, troubleshooting, and other procedures for the use of the rosemount 8600D Vortex Flowmeter . Specifications and other important information are also 2: Configuration contains information on entering and verifying basic configuration 3: Installation contains mechanical and electrical installation 4: Operation contains information on advanced configuration parameters and functions that can aid in maintaining the 5: Troubleshooting provides troubleshooting techniques, diagnostic information, and transmitter verification and Reference Data provides reference and specification B: Product Certifications provides specific information for approval C: Electronics Verification provides a short procedure for verification of electronic output to assist in meeting the quality standards for ISO 9000 certified manufacturing D.

6 HART Menu Tree provides command tree, and Fast Key Sequence tables for the Field Communicator when used in conjunction with the rosemount 8600D. messagesProcedures and instructions in this manual may require special precautions to ensure the safety of the personnel performing the operations. Refer to the safety messages, listed at the beginning of each section, before performing any descriptionThe rosemount 8600D Vortex Flowmeter consists of a meter body and transmitter and measures volumetric flow rate by detecting the vortices created by a fluid passing by the shedder meter body is installed in-line with process piping. A sensor is located at the end of the shredder bar and creates an alternating sine wave due to the passing vortices. The transmitter measures the frequency of the sine waves and converts it into a manual is designed to assist in the installation and operation of the rosemount 8600D Vortex 1 Introduction2 Reference Manual00809-0100-4860, Rev BDIntroductionOctober 2016 Introduction3 Reference manual 00809-0100-4860, Rev BDConfigurationOctober 2016 ConfigurationSection 2 ConfigurationReview.

7 Page 3 Process variables .. page 3 Basic setup .. page Review the Flowmeter configuration parameters set at the factory to ensure accuracy and compatibility with your particular application of the Flowmeter . Once you have activated the Review function, scroll through the data list to check each variable in the configuration data last step of start-up and commissioning is to check the Flowmeter output to ensure that the Flowmeter is operating properly. rosemount 8600D digital process variables include: primary variable, primary variable as a percent of range, analog output, Vortex shedding rate, pulse frequency, mass flow, volumetric flow, velocity flow, totalizer, electronics temperature, calculated process density, cold junction temperature, and process temperature.

8 VariablesThe process variables for the rosemount 8600D provide the Flowmeter output. When commissioning a Flowmeter , review each process variable, its function and output, and take corrective action if necessary before using the Flowmeter in a process product is intended to be used as a Flowmeter for liquid, gas, or steam applications. Any use other than for which it was intended may result in serious injury or , 5 FastKeys1, 14 Reference Manual00809-0100-4860, Rev BDConfigurationOctober Variable (PV)The measured value of the variable mapped to the primary variable. This can be either Process Temperature (MTA option only) or Flow. Flow variables are available as mass, volume, or velocity. When bench commissioning, the flow values for each variable should be zero and the temperature value should be the ambient the units for the flow or temperature variables are not correct, refer to View other variables on page 4.

9 Use the Process Variable Units function to select the units for your of rangeThe primary variable as a percentage of range provides a gauge as to where the current measurement of the meter is within the configured range of the meter. For example, the range may be defined as 0 gal/min to 20 gal/min. If the current flow is 10 gal/min, the percent of range is 50 outputThe analog output variable provides the analog value for the primary variable. The analog output refers to the industry standard output in the 4 20 mA range. Check the analog output value against the actual loop reading given by a multi-meter. If it does not match, a 4 20 mA trim is required. See D/A Trim (Digital-to-Analog Trim). other variablesAllows for the viewing and configuration of other variables such as flow units, totalizer operation, and pulse flowAllows the user to view the current volumetric flow , 1, 1 FastKeys1, 1, 2 FastKeys1, 1, 3 FastKeys1, 1, 4 FastKeys1, 1, 4, 1, 15 Reference manual 00809-0100-4860, Rev BDConfigurationOctober 2016 ConfigurationVolume flow unitsAllows the user to select the volumetric flow units from the available , 1, 4, 1.

10 2 Volumetric UnitLCD DisplayField Gallons per secondGAL/ Gallons per minuteGAL/ Gallons per hourGAL/ Gallons per dayGAL/Dgal/dActual Cubic Feet per secondACFSACFSA ctual Cubic Feet per minuteACFMACFMA ctual Cubic Feet per hourACFHACFHA ctual Cubic Feet per dayACFDACFDS tandard Cubic Feet per minuteSCFMN/AStandard Cubic Feet per hourSCFHN/ABarrels per secondBBL/Sbbl/sBarrels per minuteBBL/Mbbl/minBarrels per hourBBL/Hbbl/hBarrels per dayBBL/Dbbl/dImperial Gallons per secondIGAL/SImpgal/sImperial Gallons per minuteIGAL/MImpgal/minImperial Gallons per hourIGAL/HImpgal/hImperial Gallons per dayIGAL/DImpgal/dLiters per secondL/SL/sLiters per minuteL/MINL/minLiters per hourL/HL/hLiters per dayL/DL/DActual Cubic Meters per secondACMSACMSA ctual Cubic Meters per minuteACMMACMMA ctual Cubic Meters per hourACMHACMHA ctual Cubic Meters per dayACMDACMDM illion Actual Cubic Meters per dayMACMDMACMDN ormal Cubic Meters per minuteNCMMN/ANormal Cubic Meters per hourNCMHN/ANormal Cubic Meters per dayNCMDN/A6 Reference Manual00809-0100-4860, Rev BDConfigurationOctober 2016 ConfigurationStandard/Normal flow unitsStdCuft/minSCFHNCMMNmlCum/hNCMDNote When configuring Standard or Normal Flow units to the volumetric flow, a density ratio must be provided.