Modbus Register Map - - APC USA

Modicon Standard Register NumberAbsolute Starting Register Address, (Hexadecimal)Absolute Starting Register Address, (Decimal)BitData PointLength# registersData TypeScale (Divide ReadingBy)DescriptionPermissionUnit40001 00000 Status Word 01 ReadOnlyNone0 BOOLEANUPS turning on*1 BOOLEANUPS in bypass due to an internal fault (indicated through Register 0002 or 0003) *2 BOOLEANUPS going to bypass due to command*3 BOOLEANUPS in bypass due to command*4 BOOLEANUPS returning from bypass*5 BOOLEANUPS in bypass mode as a result of manual bypass control*6 BOOLEANUPS ready to power load upon user command7 BOOLEANUPS ready to power load upon return of normal line or upon user command8 BOOLEANR eserved9 BOOLEANR eserved10 BOOLEANR eserved11 BOOLEANR eserved12 BOOLEANR eserved13 BOOLEANR eserved14 BOOLEANR eserved15 BOOLEANR eservedPart number: 990-5702 Notes:1.

Modicon Standard Register Number Absolute Starting Register Address, (Hexadecimal) Absolute Starting Register Address, (Decimal) Bit Data Point

Tags:

  Registers

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Modbus Register Map - - APC USA

1 Modicon Standard Register NumberAbsolute Starting Register Address, (Hexadecimal)Absolute Starting Register Address, (Decimal)BitData PointLength# registersData TypeScale (Divide ReadingBy)DescriptionPermissionUnit40001 00000 Status Word 01 ReadOnlyNone0 BOOLEANUPS turning on*1 BOOLEANUPS in bypass due to an internal fault (indicated through Register 0002 or 0003) *2 BOOLEANUPS going to bypass due to command*3 BOOLEANUPS in bypass due to command*4 BOOLEANUPS returning from bypass*5 BOOLEANUPS in bypass mode as a result of manual bypass control*6 BOOLEANUPS ready to power load upon user command7 BOOLEANUPS ready to power load upon return of normal line or upon user command8 BOOLEANR eserved9 BOOLEANR eserved10 BOOLEANR eserved11 BOOLEANR eserved12 BOOLEANR eserved13 BOOLEANR eserved14 BOOLEANR eserved15 BOOLEANR eservedPart number: 990-5702 Notes:1.

2 16-bit registers are transmitted MSB first ( big-endian). Serial RTU is supported on NMC model AP9635, and Modbus TCP is supported on NMC models AP9635, AP9630, AP9631 and bits are atomic within a single Modbus Register . User should not look for consistency across multiple registers , only within a single Register reads of reserved or undefined registers will return an error. Block reads that begin with a valid Register will not return an error but will return zeros for undefined are one word in Signednumbers are two's are one character per number0 is least significant Type column.

3 "INT16" = signed 16-bit integer, "UINT16" = unsigned 16-bit integer, "INT32" = signed 32-bit integer, "UINT32"= unsigned 32-bit integer, "ENUM" is a UINT16 valuethatmaps to a defined list of states, "ASCII" = the printable ASCII subset from 0x20 - 0x7E, "BOOLEAN" = a single bit, 0 or "Absolute Starting Register Address" = 0 (the column heading used in this table) is equivalent to " Register 40001" in Modicon terminology, which is address zero when transmitted over the Modbus Register Map also supports the three-phase Smart-UPS VT and MGE Galaxy 3500 UPS :Most UPS models with the prefix SRC are supported by this Modbus Register Map.

4 For SRC models SRC2 KUXI, SRC3 KUXI, and SRC3 KUXIX709, use the Modbus Register Map entitled Modbus Register Map for Smart-UPS Models with prefix SMT, SMX, SURTD, and SRT , available on : Temperature and Humidity sensors attached to the UIO port(s) of the AP9631 and AP9635 NMC models are not supported via more information on the Modbus protocol, Modbus data formats, and Modbus troubleshooting, see Application Note #168 Modbus Installation and Troubleshooting for AP9635 Network Management Card , available on For detailed Modbus configuration settings, see the AP9635 User Guide, and the Modbus Documentation Addendum on the APC website, Register Map - MGE Galaxy 3500, Smart-UPS VT, and Smart-UPSE xcluding UPS models with prefix SMT, SMX, SURTD, and SRT1990-570208/2018 Modicon Standard Register NumberAbsolute Starting Register Address.

5 (Hexadecimal)Absolute Starting Register Address, (Decimal)BitData PointLength# registersData TypeScale (Divide ReadingBy)DescriptionPermissionUnit40002 00011 Status Word 11 ReadOnlyNone0 BOOLEANUPS output not powered due to low battery shutdown1 BOOLEANUPS unable to transfer to on-battery operation due to overload2 BOOLEANUPS fault - main relay malfunction*3 BOOLEANUPS in sleep mode4 BOOLEANUPS in shutdown mode5 BOOLEANUPS fault - battery charger failure6 BOOLEANR eserved7 BOOLEANUPS fault - internal temperature has exceeded nominal limits*8 BOOLEANR eserved9 BOOLEANR eserved10 BOOLEANR eserved11 BOOLEANR eserved12 BOOLEANR eserved13 BOOLEANR eserved14 BOOLEANR eserved15 BOOLEANR eserved4000300022 Status Word 21

6 ReadOnlyNone0 BOOLEANR eserved1 BOOLEANR eserved2 BOOLEANR eserved3 BOOLEANR eserved4 BOOLEANUPS fault - UPS in bypass; or DC imbalance in inverter*5 BOOLEANUPS commanded out of bypass with no batteries attached; or No batteries attached*6 BOOLEANB oost or trim relay fault*7 BOOLEANI nverter fault; or Output overvoltage*8 BOOLEANR eserved9 BOOLEANR eserved10 BOOLEANR eserved11 BOOLEANR eserved12 BOOLEANR eserved13 BOOLEANR eserved14 BOOLEANR eserved15 BOOLEANR eserved4000400033 Status Word 31 ReadOnlyNone0 BOOLEANP erforming battery calibration discharge1 BOOLEANS mart trim*2 BOOLEANS mart boost*3 BOOLEANOn line4 BOOLEANOn battery5 BOOLEANO verload6 BOOLEANLow battery (runtime remaining <= low battery duraton)

7 7 BOOLEANR eplace battery8 BOOLEANR eserved9 BOOLEANR eserved10 BOOLEANR eserved11 BOOLEANR eserved12 BOOLEANR eserved13 BOOLEANR eserved14 BOOLEANR eserved15 BOOLEANR eserved2990-570208/2018 Modicon Standard Register NumberAbsolute Starting Register Address, (Hexadecimal)Absolute Starting Register Address, (Decimal)BitData PointLength# registersData TypeScale (Divide ReadingBy)DescriptionPermissionUnit40005 00044 Line Quality1 ENUM00FF = acceptable utility line quality0000 = unacceptable utility line qualityReadOnlyNone4000600055% Battery State of Charge (0-100)1 UINT161 ReadOnly%4000700066 Runtime Remaining1 UINT161 ReadOnlyMinutes4000800077 Battery Voltage1 UINT161 ReadOnlyV4000900088 UPS Internal Temperature1 UINT161 Internal operating temperature or battery temperatureReadOnly C4001000099 Amps Drawn by Load*1 UINT161 ReadOnlyA40011000A10 Quantity of battery packs with bad batteries*1 UINT161 ReadOnlyEach40012000B11 Quantity of battery packs1 UINT161 ReadOnlyEach40013000C12% Power drawn by load1 UINT161 ReadOnly%40014000D13 Nominal Output Voltage1 UINT161 ReadOnlyV40015000E14 Actual Output Voltage1 UINT161 ReadOnlyV40016000F15 Maximum Input Voltage

8 Since Last Reading1 UINT161 ReadOnlyV40017001016 Minimum Input Voltage Since Last Reading1 UINT161 ReadOnlyV40018001117 Input Voltage1 UINT161 ReadOnlyV40019001218 Input Frequency1 UINT161 ReadOnlyHz40020001319 Measure-UPS Temperature Reading (Probe 1)1 UINT161 Measure-UPS refers to the discontinued Environmental Monitoring Card AP9612 THReadOnly C40021001420 Measure-UPS Humidity Reading (Probe 1) 1 UINT161 Measure-UPS refers to the discontinued Environmental Monitoring Card AP9612 THReadOnly%40022001521 Measure-UPS Temperature Reading (Probe 2) 1 UINT161 Measure-UPS refers to the discontinued Environmental Monitoring Card AP9612 THReadOnly C40023001622 Measure-UPS Humidity Reading (Probe 2)

9 1 UINT161 Measure-UPS refers to the discontinued Environmental Monitoring Card AP9612 THReadOnly%40024001723 Measure-UPS Contact Position1 UINT161 Measure-UPS refers to the discontinued Environmental Monitoring Card AP9612 THReadOnlyNone40025001824 Reserved1 ReadOnly40026001925 Reserved1 ReadOnly40027001A26 Minimum Return Battery Capacity1 UINT161 ReadOnly%40028001B27 Lower Transfer Point1 UINT161 ReadOnlyV40029001C28 Upper Transfer Point1 UINT161 ReadOnlyV40030001D29 Nominal Output Voltage1 UINT161 ReadOnlyV40031001E30 Shutdown Delay1 UINT161 ReadOnlySeconds40032001F31 Low Battery Duration1 UINT161 ReadOnlyMinutes40033002032 Turn On Delay1 UINT161 ReadOnlySeconds40034002133 Sensitivity*1 ENUM'H' = highest (normal) sensitivity to utility voltage fluctuations'M' = medium (reduced)

10 Sensitivity to utility voltage fluctuations'L' = lowest sensitivity to utility voltage fluctuations0 = not supported by this UPSReadOnlyNone40035002234 UPS ID Character #11 ASCIIReadOnlyNone40036002335 UPS ID Character #21 ASCIIReadOnlyNone40037002436 UPS ID Character #31 ASCIIReadOnlyNone40038002537 UPS ID Character #41 ASCIIReadOnlyNone40039002638 UPS ID Character #51 ASCIIReadOnlyNone40040002739 UPS ID Character #61 ASCIIReadOnlyNone40041002840 UPS ID Character #71 ASCIIReadOnlyNone40042002941 UPS ID Character #81 ASCIIReadOnlyNone40043002A42 Status Word 4*1 ReadOnlyNone0 BOOLEANR eserved1 BOOLEANR eserved2 BOOLEANR eserved3 BOOLEANRun time below alarm threshold4 BOOLEANXR frame fault5 BOOLEANO utput voltage out of range6 BOOLEANS ystem not synchronized7 BOOLEANNo batteries8 BOOLEANB attery voltage high9 BOOLEANF ault found in Register 0049, 004A, 004B or 004C10 BOOLEANSite wiring fault11 BOOLEANR eserved12 BOOLEANR eserved13 BOOLEANR eserved14 BOOLEANR eserved15 BOOLEANR eserved3990-570208/2018 Modicon Standard Register NumberAbsolute Starting Register Address, (Hexadecimal)Absolute Starting Register Address, (Decimal)BitData PointLength# registersData TypeScale (Divide ReadingBy)