Transcription of Multi-Measuring-Interface MMI 7000
1 multi - measuring -InterfaceMMI 7000 ManualVersion EEBEHAKO electronic GmbHcosjMMI 7000 multi MeasuringInterfaceUniversalmessger t!- 1 -CAUTIONS !1. High voltage !2. The MMI7000 must not be operated without protective earth conductor connected!3. The measuring device is suitable only for usage in low-voltage switchgear systems. The maximum permissible input voltages (see technical data) must not be exceeded!4. The device must only be operated by qualified staff!Version E , May 2010- 2 -CONTENTSS ection 1 Generalp.
2 3 Section 2 Installation and important notesp. 4 Section 3 Appearance and controlp. 5 Section 4 Connection p. 6 Section 5 MENU-functions / DISPLAY-MODEp. 7 Section 6 HELP-Functionp. 8 Section 7 PROGRAM-MODEp. 9 Section 8 Discontinuation of recordingSection 13 DISPLAY-EDITOR / 15 Software for evaluation of grid the WINDOWS operating systemSection 16 Maintenance and Tables:Annex 2 Technical 4 Operation E , May 2010 Section 1: GENERALThe measuring device MMI7000 has been developed for three-phase measuring , display, and storage of electric parameters in low-voltage range.
3 RMMI7000-BBasic versionRMMI7000-Sadditional two independent potential free interfaces RS485 RMMI7000 Technical features:ROperating voltage: (+/- 15%)RMeasuring voltage: 3x (L-N); (L-L)RMeasuring current:3x X:5A / X:1 ARIlluminated graphic display 128x64 dotR3-phase display of several grid-parameters (V, I, f, Q, P, S, W, THD-V, THD-I, ..)RDisplay and internal storage of minimum and maximum values with time stampRDisplay of date and timeRDisplay of harmonics, bar diagram availableRLarge number of display options rotating display and adjustment of font sizeRERRE quipped with a SD memory card slot for data storage and easy passing on without online connection*RRComfortable programming of recording interval and duration via timers*Easy to use Windows-based software included in delivery*.
4 RWindows-based software for evaluation of recorded grid parametersRSeveral pre-configured graphical display of standard valuesRLarge number of configuration optionsRGraphical display of selected grid valuesRComfortable editing of parametersRComfortable editing of recording time intervallRDisplay as line graph or bar diagramRSimultaneous display of several diagramsRZoom-functionsRCopy into clipboard and print function available*MMI7000-E onlyIn order to allow a simple handling, the concept of graphical menu navigation has consistently been used.
5 An integrated help (HELP-button) is available to make handling graphical display permits the display of different font sizes, bar charts and interfaces as well as a data storage (changeable SD-card) and an processing software for PC are available-Eextended version: 1 interface RS485, 1 switching input (programmable)4 relay outputs (programmable), 1 impulse output (transistor)1 card slot for SD-card (storage of grid values)1 CD with Windows-based evaluation softwarexternal input as well as 4 freely programmable relay outputs*RProgramming as operation-hours-counter possible(Transistor-) impulse output for energy impulse*Recording up to 720 days in one data file possible (at interval 15 min.)
6 *- 3 -Version E , May 2010- 4 -Section 2: INSTALLATION AND IMPORTANT NOTESThe measuring device MMI7000 has been designed for three-phase measuring , display, and storage of electrical measuring values in a is designed to be incorporated into the front panel of a switchboard and requires a switchboard section of 138 x 138 mm to DIN 43700/ IEC61554. The device must only be operated by qualified personnel and must only be operated according to the given safety instructions. In addition, the relevant legal and safety regulations for live operation have to be measurement can be used for single and three phase systems with or without neutral conductor.
7 The maximum measuring voltage is 3 x 440 V ~ (L-N) or 3 x 760 V ~ (L-L). The supply voltage is 110 .. 230 V +/- 15 %.The connection wires that are used have to be suitable for the particulars voltages. Feed lines have to be protected by an over-voltage-protection device. The supply voltage has to be protected by a fuse and it must be sure that it can be switched off by a separating connection clamps may only be plugged at zero-voltage state!The MMI7000 must not be operated without protective earth conductor connected!
8 Before the device is connected up, all leads and cables must be checked to ensure that no current is flowing through them and the current converter must be short-circuited. Care should be taken to ensure that the measuring voltage and current are in the correct phase 2position. The measuring -current circuit must be wired with copper leads of The connection should be set up as shown in next section. The specified safety regulations must be measuring device is only designed for the usage in low-voltage switchgear !
9 Connection to over voltage may result in the destruction of the device!!!!!Version E , May 2010- 5 -Section 3: APPEARANCE AND CONTROLMMI7000: Front viewOperating Mode:- Automatic- In-/Out-Mode- Record-Mode- Service- Expert-Mode- Osci-Mode- Display EditorENTER/OKConfirmation/storage ofvaluesIncrease selected parameterHELP opens help-pagesReduceselectedparameterEscapep reviouspage/valuein the display HELPHELPESCESC Multi-Measuring-Interface multi - measuring -InterfaceType: MMI7000-SType: : 30 - 440 VAC 50 : 30 - 440 VAC 50/60 HzSupply voltage.
10 85 - 265 VAC 50/60 HzSupply voltage: 85 - 265 VAC 50 L1 L1 ~Supply ~Interface1 (RS485) interface 2 (RS485)Interface1 (RS485) inputExt. inputRelay-outputsMeasuring voltage30 .. 440V L-N50 .. 760V .. 440V L-N50 .. 760V L2 L2 L3 L3 lL1 NL1 NGnd B A PEGnd B A PE 1 2 1 2 1 2 K1 K2 K3 K4 comL1 L2 L3 NL1 L2 L3 NPEPENNL2 (S)L2 (S)L3 (T)L3 (T)L1 (R)L1 (R)( L1) ( N )( L1) ( N )L1 L2 L3 N(PE)*L1 L2 L3 N(PE)