Transcription of NI 9472 Datasheet - National Instruments
1 DATASHEETNI 94728 DO, 6 V to 30 V, Sourcing, 100 s DSUB, screw-terminal, or spring-terminalconnectivity CompactDAQ counter compatibility 250 Vrms, CAT II, channel-to-earth isolation(screw and spring terminal); 60 VDC, CAT I,channel-to-earth isolation (DSUB)The NI 9472 is a digital output module for CompactDAQ and CompactRIO systems. Eachchannel is compatible with 6 V to 30 V signals and features 2,300 Vrms of transientovervoltage protection between the output channels and the backplane. Each channel also hasan LED that indicates the state of that channel. With the NI 9472, you can connect directly to avariety of industrial devices such as motors, actuators, and are three connector options for the NI 9472 a 10-position screw-terminal connector, a10-position spring-terminal connector, and a 25-position DSUB connector.
2 This industry-standard 25-position DSUB connector provides for low-cost cabling to a wide variety ofaccessories available from NI or other vendors. A number of vendors with custom DSUB cable fabrication services can deliver cables with a pinout that matches your exact ContentsRequiredAccessories NI 9472 NI 9472 Getting Started Guide NI 9927 Backshell Connector Kit (screw terminal) NI 9981 Backshell Connector Kit (spring terminal) NI 9924 Screw-Terminal Block (DSUB)Screw-Terminal, 25-Pin DSUB, Spring-Terminal750 mA/ch100 s830 VSourcingOutputNI 9472 Screw-Terminal,Spring-Terminal1 A/ch1 s830 VSourcingOutputNI 947425-Pin DSUB1 A/ch1 s860 VSourcingOutputNI 9475250 mA/ch500 s3236 VSourcingOutputNI 94761 A/ch(20 A/module)
3 8 s32 SinkingOutputNI A/ch7 s16 SinkingOutputNI 947837-Pin DSUB37-Pin DSUB37-Pin DSUB60 V60 VConnectivityContinuous UpdateChannelsMaximumModuleProductCurren tRateOutputTypeNameScrew-Terminal,37-Pin DSUB100 mA/ch7 s1630 VDCS ourcingOutputNI 9375C SERIES DIGITAL OUTPUT MODULE COMPARISONNI C Series OverviewNI provides more than 100 C Series modules for measurement, control, and communicationapplications. C Series modules can connect to any sensor or bus and allow for high-accuracymeasurements that meet the demands of advanced data acquisition and control applications. Measurement-specific signal conditioning that connects to an array of sensors and signals Isolation options such as bank-to-bank, channel-to-channel, and channel-to-earth ground -40 C to 70 C temperature range to meet a variety of application and environmentalneeds Hot-swappableThe majority of C Series modules are supported in both CompactRIO and CompactDAQplatforms and you can move modules from one platform to the other with no | | NI 9472 DatasheetCompactRIOC ompactRIO combines an open- embedded architecturewith small size, extreme ruggedness.
4 And C Seriesmodules in a platform powered by the NI LabVIEW reconfigurable I/O (RIO) architecture. Each systemcontains an FPGA for custom timing, triggering, andprocessing with a wide array of available modular I/O tomeet any embedded application is a portable, rugged data acquisition platformthat integrates connectivity, data acquisition, and signalconditioning into modular I/O for directly interfacing to anysensor or signal. Using CompactDAQ with LabVIEW, youcan easily customize how you acquire, analyze, visualize,and manage your measurement Professional Development System for Windows Use advanced software tools for large project development Generate code automatically using DAQ Assistant and InstrumentI/O Assistant Use advanced measurement analysis and digital signal processing Take advantage of open connectivity with DLLs, ActiveX,and.
5 NET objects Build DLLs, executables, and MSI installersNI LabVIEW FPGA Module Design FPGA applications for NI RIO hardware Program with the same graphical environment used for desktop andreal-time applications Execute control algorithms with loop rates up to 300 MHz Implement custom timing and triggering logic, digital protocols, andDSP algorithms Incorporate existing HDL code and third-party IP including Xilinx IPgenerator functions Purchase as part of the LabVIEW embedded Control and MonitoringSuiteNI 9472 Datasheet | National Instruments | 3NI LabVIEW Real-Time Module Design deterministic real-time applications with LabVIEW graphical programming Download to dedicated NI or third-party hardware for reliableexecution and a wide selection of I/O Take advantage of built-in PID control, signal processing.
6 Andanalysis functions Automatically take advantage of multicore CPUs or setprocessor affinity manually Take advantage of real-time OS, development and debuggingsupport, and board support Purchase individually or as part of a LabVIEW suiteNI 9472 CircuitryCOMDONI 9472 VsupDevice+ The DO channels are internally referenced to COM. The NI 9472 has sourcing outputs. Sourcing outputs drive current from Vsup to DO whenthe channel is For more information about sourcing outputs, visit and enter theInfo Code 9472 SpecificationsThe following specifications are typical for the range -40 C to 70 C unless otherwise voltages are relative to COM unless otherwise Do not operate the NI 9472 in a manner not specified in this misuse can result in a hazard.
7 You can compromise the safety protectionbuilt into the product if the product is damaged in any way. If the product isdamaged, return it to NI for | | NI 9472 DatasheetOutput CharacteristicsNumber of channels8 digital output channelsOutput typeSourcingPower-on output stateChannels offExternal power supply voltage range(Vsup)6 VDC to 30 VDCO utput impedance (R0) Continuous output current (I0), per A maximumOutput voltage (V0)Vsup - (I0 R0)I/O protectionVoltage30 VDC maximumReversed voltageNoneShort circuit trip time10 s at 14 ATable 1. Short-circuit BehaviorCurrentChannel BehaviorModule Protection Less than.
8 75 AChannel does not tripModule is not A to A for 100 ms maximum,repeatable after 1 s1 Channel does not tripModule is not A to AChannel does not tripModule may be A to 14 AChannel may tripModule may be damagedGreater than 14 AChannel tripsModule is not damaged1 One channel at a 9472 Datasheet | National Instruments | 5 Figure 1. Short-circuit BehaviorChannelCurrent100 ms1 AD0xD0y100 ms1 sTimeOutput delay time (full load)100 s maximumMTBF1,113,301 hours at 25 C; Bellcore Issue 2,Method 1, Case 3, Limited Part Stress MethodPower RequirementsPower consumption from chassisActive mode230 mW maximumSleep mW maximumThermal dissipation (at 70 C)Active W maximumSleep mode55 mW maximum6 | | NI 9472 DatasheetPhysical CharacteristicsIf you need to clean the module, wipe it with a dry For two-dimensional drawings and three-dimensional models of the C Seriesmodule and connectors, visit and search by module mm2 to mm2 (26 AWG to 14 AWG)copper conductor wireWire strip length13 mm ( in.)
9 Of insulation stripped fromthe endTemperature rating90 C minimumTorque for screw N m to N m( lb in. to lb in.)Wires per screw terminalOne wire per screw terminal; two wires perscrew terminal using a 2-wire mm2 to mm2 Spring-terminal mm2 to mm2 (30 AWG to 12 AWG)copper conductor wireWire strip length10 mm ( in.) of insulation stripped fromthe endTemperature rating90 C minimumWires per spring terminalOne wire per spring terminal; two wires perspring terminal using a 2-wire mm2 to mm2 Connector securementSecurement typeScrew flanges providedTorque for screw N m ( lb in.)
10 WeightNI 9472 with screw terminal150 g ( oz)NI 9472 with spring terminal139 g ( oz)NI 9472 with DSUB145 g ( oz)NI 9472 Datasheet | National Instruments | 7NI 9472 with Screw Terminal and Spring TerminalSafety VoltagesConnect only voltages that are within the following VDC maximumIsolationChannel-to-channelNoneCh annel-to-earth groundContinuous250 Vrms, Measurement Category IIWithstand2,300 Vrms, verified by a 5 s dielectricwithstand testMeasurement Category II is for measurements performed on circuits directly connected to theelectrical distribution system. This category refers to local-level electrical distribution, such asthat provided by a standard wall outlet, for example, 115 V for or 230 V for Do not connect the NI 9472 to signals or use for measurements withinMeasurement Categories III or 9472 with DSUB Safety VoltagesConnect only voltages that are within the following VDC maximumIsolationChannel-to-channelNoneCh annel-to-earth groundContinuous60 VDC, Measurement Category IWithstand1,000 Vrms.