Transcription of Operating Guide VLT® Soft Starter MCD 600 - Danfoss
1 Operating GuideVLT soft Starter MCD Description8 Document Version8 Additional Resources8 Approvals and Certifications8 Safety9 Safety Symbols9 Qualified Personnel9 Safety Precautions9 System Design12 Feature List12 Type Code13 Selection of soft Starter Size13 Current Ratings (IEC Ratings)14 Current Ratings (NEMA Ratings)17 Dimensions and Weight19 Physical Installation/Cooling Clearances20 Accessories21 Expansion Cards21 Smart Card21 Communication Expansion Cards21 Ground Fault Protection21 Remote LCP 60121 Finger Guard Kit22 soft Starter Management Software22 Main Contactor22 Circuit Breaker22 External Bypass Contactor22 Power Factor Correction22 Short-circuit Protection Devices23 Type 1 Coordination23 Type 2 Coordination23 IEC Coordination with Short-circuit Protection Devices24UL Coordination with Short-circuit Protection Devices25 Standard Fault Short Circuit25AQ262141844215en-000401/175R117 4 | 3 Danfoss A/S soft Starter MCD 600 Operating MCD6-0020B~MCD6-0579B25 Models MCD6-0654B~MCD6-1250B & MCD6-0590C~MCD6-1134C26 High Fault Short-circuit Current Ratings26 Specifications29 Supply29 Short-circuit Capability29 Electromagnetic Capability (Compliant with EU Directive 2014/35/EU)
2 29 Inputs29 Outputs29 Environmental29 Heat Dissipation30 Motor Overload Protection30 Certification30 Operational Life (Internal Bypass Contacts)30 Installation31 Safety Instructions31 Command Source31 Setting up the soft Starter31 Inputs32 Input Terminals32 Motor Thermistor32 Start/Stop33 Reset/ Starter Disable33 Programmable Inputs33 USB Port33 Outputs34 Output Terminals34 Analog Output34 Main Contactor Output34 Bypass Contactor Output35 Programmable Outputs36 Control Voltage36 Control Voltage Terminals36 Power Terminations36 Wiring Connectors38 Models MCD6-0144B~MCD6-0579B38 Models MCD6-0654B~MCD6-1250B & MCD6-0590C~MCD6-1134C39AQ262141844215en- 000401/175R11744 | Danfoss A/S soft Starter MCD 600 Operating Bypass Contactor39 Motor Connection39In-line Installation, Internally Bypassed40In-line Installation, Externally Bypassed40 Inside Delta Installation, Internally Bypassed41 Inside Delta Installation.
3 Externally Bypassed41 Ground Terminations42 Typical Installations42 Internally Bypassed Installation42 Externally Bypassed Installation44 Quick Set-up46 Set-up Tools48 Introduction48 Setting Date and Time48 Command Source31 Commissioning48 Run Simulation48 Load/Save Settings49 USB Save & Load50 Save and Load Procedure50 File Locations and Formats50 Auto-start/Stop51 Network Address51 Setting a Network Address51 Digital I/O State52 Analog I/O State53 Serial Number & Rating53 Software Versions53 Thermistor Reset53 Reset Thermal Model54 Logs55 Introduction55 Event Log55 Counters55 Viewing the Counters55QR Code55AQ262141844215en-000401/175R1174 | 5 Danfoss A/S soft Starter MCD 600 Operating and Feedback56 Local LCP and Feedback56 Remote LCP56 Adjusting the Display Contrast57 soft Starter Status LEDs58 Displays58 soft Starter Information58 Configurable Feedback Screens58 Operating Feedback Screens58 Performance Graph59 Operation60 Start, Stop.
4 And Reset Commands60 Command Override60 Auto-start/Stop60 Clock Mode60 Timer Mode60 PowerThrough60 Emergency Mode61 Auxiliary Trip61 Typical Control Methods61 soft Start Methods63 Constant Current63 Constant Current with Current Ramp63 Constant Current with Kickstart64 Timed Voltage Ramp64 Adaptive Control for Starting65 Fine-tuning Adaptive Control66 Stop Methods66 Coast to Stop66 Timed Voltage Ramp66 Adaptive Control for Stopping67DC Brake68 soft Brake69 Pump Clean70 Reverse Direction Operation70 Jog Operation71 Inside Delta Operation72AQ262141844215en-000401/175R1 1746 | Danfoss A/S soft Starter MCD 600 Operating Motor Set72 Programmable Parameters74 Main Menu74 Changing Parameter Values74 Adjustment Lock74 Parameter List74 Parameter Group 1-** Motor Details82 Parameter Group 2-** Motor Start/Stop83 Parameter Group 3-** Motor Start/Stop-286 Parameter Group 4-** Auto-Start/Stop89 Parameter Group 5-** Protection Levels92 Parameter Group 6-** Protection Action94 Parameter Group 7-** Inputs100 Parameter Group 8-** Relay Outputs104 Parameter Group 9-** Analog Output106 Parameter Group 10-** Display106 Parameter Group 11-** Pump Clean110 Parameter Group 12-** Communication Card111 Parameter Group 20-** Advanced114 Parameter Groups 30-** to 36-**116 Parameter Group 40-** Ground Fault116 Troubleshooting118 Protection Responses118 Trip Messages118 General Faults129 Appendix132 Symbols and Abbreviations132AQ262141844215en-000401/ 175R1174 | 7 Danfoss A/S soft Starter MCD 600 Operating Guide 1 Product DescriptionThe VLT soft Starter MCD 600 is an advanced digital soft start solution for 11 1400 kW motors.
5 The soft starters provide a completerange of motor and system protection features and are designed for reliable performance in the most demanding installation Document VersionThis manual is regularly reviewed and updated. All suggestions for improvement are 1: Document VersionVersionRemarksAQ262141844215, version 0401 Updated with information about S3 Additional ResourcesOther resources are available to understand advanced soft Starter functions and guides for operation with optional guides for installing various Design Tool to help with selecting the right soft Starter for an publications and manuals are available from under the sections Service and Approvals and CertificationsAQ262141844215en-000401 / 175R11748 | Danfoss A/S soft Starter MCD 600 Operating Guide -2 Safety SymbolsThe following symbols are used in this manual:D A N G E RIndicates a hazardous situation which, if not avoided, will result in death or serious A R N I N GIndicates a hazardous situation which, if not avoided, could result in death or serious A U T I O NIndicates a hazardous situation which, if not avoided, could result in minor or moderate O T I C EIndicates a property damage Qualified PersonnelCorrect and reliable transport, storage, installation, operation, and maintenance are required for the trouble-free and safe operationof the soft Starter .
6 Only qualified personnel are allowed to install or operate this personnel are defined as trained staff, who are authorized to install, commission, and maintain equipment, systems, andcircuits in accordance with pertinent laws and regulations. Also, the qualifed personnel must be familiar with the instructions andsafety measures described in this Safety PrecautionsSafety precautions cannot cover every potential cause of equipment damage, but can highlight common causes of damage. It is theinstaller's responsibility to:Read and understand all instructions in this manual before installing, Operating , or maintaining the good electrical practice including applying appropriate personal protective advice before Operating this equipment in a manner other than described in this O T I C EThe VLT soft Starter MCD 600 is not user serviceable. The unit should only be serviced by authorized service personnel.
7 Unau-thorized tampering with the unit voids the product A R N I N GPROPER GROUNDINGIt is the responsibility of the installer of the soft Starter to provide proper grounding and branch circuit protection according tolocal electrical safety codes. Not providing proper grounding and branch circuit protection may lead to death, personal injury, orequipment the soft Starter from mains voltage before carrying out repair / 175R1174 | 9 Danfoss A/S soft Starter MCD 600 Operating Guide ------------W A R N I N GUNINTENDED STARTWhen the soft Starter is connected to AC mains, DC supply, or load sharing, the motor can start at any time. Unintended startduring programming, service, or repair work can result in death, serious injury or property damage. The motor can start with anexternal switch, a fieldbus command, an input reference signal from the LCP, or after a cleared fault [Off/Reset] on the LCP before programming the soft Starter from the wire and assemble the soft Starter , motor, and any driven equipment before connecting the soft Starter to ACmains, DC supply, or load the power supply to the soft Starter with an isolating switch and a circuit-breaking device (for example a power contactor)controllable through an external safety system (for example an emergency stop or a fault detector).
8 C A U T I O NPOWER FACTOR CORRECTIONC onnecting power factor correction capacitors to the output side will damage the soft not connect power factor correction capacitors to the output of the soft Starter . If static power factor correction is em-ployed, it must be connected to the supply side of the soft A U T I O NSHORT CIRCUITThe VLT soft Starter MCD 600 is not circuit severe overload or short circuit, the operation of the MCD 600 should be fully tested by an authorized service A U T I O NMECHANICAL DAMAGE FROM UNEXPECTED RESTARTThe motor could restart after the causes of a shutdown are rectified, which may be dangerous for certain machines or that appropriate arrangements are made against restarting after unscheduled stops of the A R N I N GSAFETY OF PERSONNELThe soft Starter is not a safety device and does not provide electrical isolation or disconnection from the isolation is required, the soft Starter must be installed with a main not rely on the start and stop functions for safety of personnel.
9 Faults occurring in the mains supply, the motor connec-tion, or the electronics of the soft Starter can cause motor starts or faults occur in the electronics of the soft Starter , a stopped motor may start. A temporary fault in the mains supply or loss ofmotor connection can also cause a stopped motor to provide safety of personnel and equipment, control the isolation device through an external safety O T I C EBefore changing any parameter settings, save the current parameter set to a file using MCD PC Software or the Save User / 175R117410 | Danfoss A/S soft Starter MCD 600 Operating Guide -N O T I C EUse the Auto-start feature with caution. Read all the notes related to auto-start before examples and diagrams in this manual are included solely for illustrative purposes. The information contained in this manual issubject to change at any time and without prior notice.
10 Responsibility or liability is never accepted for direct, indirect, or consequen-tial damage resulting from the use or application of this / 175R1174 | 11 Danfoss A/S soft Starter MCD 600 Operating Guide 3 System Feature ListStreamlined set-up processConfiguration profiles for common metering and interfaceMulti-language menus and option names and feedback performance energy efficiencyIE3 energy efficient when start technology avoids harmonic range of models20 1250 A (nominal).200 525 V 690 V or continuous or inside delta input and output optionsRemote control inputs (2 x fixed, 2 x programmable).Relay outputs (2 x fixed, 2 x programmable).Analog starting and stopping optionsScheduled voltage ramp soft to protectionMotor start / 175R117412 | Danfoss A/S DesignVLT soft Starter MCD 600 Operating Guide ------ Input features for advanced applicationsSmart fault Type Code0960 Control voltageCV1 = 24 V AC/V DCCV2 = 110~120 V AC or 220~240 V ACProtection00 = IP00 (open frame)20 = IP20 (enclosed)Frame sizeS1X = Frame size 1S2X = Frame size 2S3X = Frame size 3 Mains voltageT5 = 200~525 V ACT7 = 380~690 V ACBypassB = Internally bypassedC = Non-bypassed (continuousconnection)Nominal current BT5S1X20CV1 Illustration 1.