Transcription of Phase-Adaptive Power Module SPEC (369835)
1 Phase-Adaptive Power Module Power Interfaces 369835g 1 Phase-Adaptive Power Module Provides dimming control for 1 zone of a full 16 A. lighting load. May be used to dim incandescent, halogen, electronic low-voltage, magnetic low-voltage, neon / cold cathode. Phase-Adaptive technology automatically selects leading- edge or trailing-edge dimming for low-voltage transformers. Up to 3 Power modules may be controlled by a single dimmer (C5-BMJ- will control only 1 Module ). Use PHPM-WBX- models for 3-wire fluorescent dimmer input and PHPM-PA- models for 2-wire input.
2 PHPM-WBX- models can be used in conjunction with BCI-0-10 for 0 10 V dimming applications. For more information, see Application Note #516 (Lutron P/N 048516). at Models available for control voltage of 120 V~ only or 220 277 V~. Models available for load voltage of 120 V~ only or 120 277 V~. Compatible with 220 / 240 V~, non-CE systems. Contact Lutron for specific system applications. Not for use with non-dim loads. Works with 120 V~ or 220 277 V~ versions of: Lutron in-wall neutral wire dimmers; see approved list in the Dimmers and Switches Specification Guide (Lutron P/N Models and Capacities 3671746) at (see Lighting Load Interfaces Control Load Load section) Model Number 3, 4.
3 Voltage 1, 2 Voltage 1, 2 Capacity GRAFIK Eye QS control units * 120 V~ 120 V~ 16 A PHPM-PA-120-WH. LP, LCP, and GP dimming panels ** 120 V~ 120 277 V~ 16 A PHPM-PA-DV-WH. HomeWorks QS remote Power panels ** 220 277 V~ 120 277 V~ 16 A PHPM-PA-277 / DV. HomeWorks QS in-line dimmer 120 V~ 120 V~ 16 A PHPM-WBX-120-WH. HomeWorks QS DIN-rail Power modules 120 V~ 120 277 V~ 16 A PHPM-WBX-DV-WH. EcoSystem interface C5-BMJ-XXX 220 277 V~ 120 277 V~ 16 A PHPM-WBX-277 / DV. Energi Savr Node PRO LED+ Phase-Adaptive 1 All voltages are phase-to-neutral.
4 Fixture controller 2 For explanation of control voltage and load voltage , see page 5. RadioRA 2 neutral wire dimmers; see approved list 3 Use PHPM-PA- models for incandescent/halogen dimmers and set the in the specification submittal (Lutron P/N 369225) at controller load type to Power Module or incandescent . 4 Use PHPM-WBX- models for 3-wire fluorescent dimmers and set the controller load type to fluorescent . HomeWorks QS neutral wire dimmers; see approved list in the specification submittal (Lutron P/N 369305) at Cas ta Wireless neutral wire dimmers; see approved list in the specification submittal (Lutron P/N 369987) at Vive PowPak phase select dimming modules; see specification submittal (Lutron P/N 3691150) at * For PHPM PA models, set load type to Power Module .
5 ** For PHPM-PA- models, set load type to incandescent . Use only PHPM-WBX models with this product; using PHPM-PA- models is not recommended S P E C I F I C AT I O N S U B M I T TA L Page 1. Job Name: Model Numbers: Job Number: Phase-Adaptive Power Module Power Interfaces 369835g 2 Specifications Power Key Design Features PHPM-PA-120-WH Automatically selects between forward-phase /. PHPM-PA-DV-WH leading edge ( , magnetic low-voltage) and reverse- 120 V~ only phase / trailing edge ( , electronic low-voltage).
6 PHPM-WBX-120-WH. Control voltage dimming / output based on connected load. PHPM-WBX-DV-WH. PHPM-PA-277 / DV Patented RTISS Equipped circuitry compensates in real 220 277 V~ time for incoming line voltage variations: Compensates PHPM-WBX-277 / DV. for + / 2% change in RMS voltage/cycle and + / 2% Hz PHPM-PA-120-WH. 120 V~ only change in frequency/second. PHPM-WBX-120-WH. Provides air-gap off. PHPM-PA-DV-WH. Load voltage Module protects itself during most temporary over-current PHPM-PA-277 / DV. 120 277 V~ and over-voltage conditions.
7 PHPM-WBX-DV-WH. Two LEDs on front of unit provide diagnostic information PHPM-WBX-277 / DV. (visible when faceplate is removed). Capacity: Full 16 A. 120 V~: 1920 W Terminals 120 277 V~: 1920 4432 W Each terminal accepts up to two 12 AWG ( mm2) wires. 220 240 V~: 3520 3840 W Environment Frequency: 50 / 60 Hz 32 to 104 F (0 to 40 C). Relative humidity less than 90%. Load (output) Power : Phase independent of control non-condensing. device / control voltage Indoor use only. Sources / Load Types Maximum heat output of Module : 135 BTU / hour.
8 Operates these sources with a smooth, continuous, Mounting Square Law dimming curve: Surface or recess mount. Incandescent (tungsten) Power Module is UL tested and approved for use in Halogen spaces designed for environmental air handling. Magnetic low-voltage transformer (iron core) Regulatory Approvals Electronic (solid-state) low-voltage transformer (must Models: PHPM PA 120 WH, PHPM PA DV WH, be manufacturer-approved for reverse-phase PHPM WBX 120 WH, PHPM WBX DV WH. control dimming). UL. Neon / Cold cathode RoHS Compliant Incandescent and electronic low-voltage sources may be CSA.
9 Controlled on the same circuit / control zone. Up to 30%. of the capacity of the unit can be used for incandescent NOM. lighting. CIDET. Incandescent and magnetic low-voltage sources may be Complies with requirements for use in other controlled on the same circuit / control zone. Up to spaces used for environmental air (plenums) per 30% of the capacity of the unit can be used for NECR 2014 (C)(3). incandescent lighting. Models: PHPM PA 277 / DV, PHPM WBX 277 / DV. Electronic low-voltage and magnetic low-voltage sources UL.
10 May NOT be controlled on the same circuit / control zone. RoHS Compliant PHPM PA- and PHPM WBX- models are not for use Complies with requirements for use in other with non dim loads. Use switching Power Module spaces used for environmental air (plenums) per (PHPM SW DV WH) for non dim loads. NECR 2014 (C)(3). Minimum load on Power Module is 10 W. Output must be directly connected to the load. Load side switching is not recommended. S P E C I F I C AT I O N S U B M I T TA L Page 2. Job Name: Model Numbers: Job Number: Phase-Adaptive Power Module Power Interfaces 369835g 3 Dimensions and Mounting Mount in 2-gang wallbox, in (89 mm) deep or Mounting Methods 4 4 in (102 102 mm) junction box, in (53 mm) Mount to 2-gang wallbox deep.