LNL-1320 Dual Reader Interface Module Quick Reference Guide Introduction The Dual Reader Interface Module board contains the following components (Refer to Figure 1): A. eight (8) supervised/non-supervised alarm inputs B. one (1) RS-485 interface C. two (2) reader interfaces D. six (6) relay outputs E. one (1) power input F. one (1) cabinet tamper G. five (5) jumpers H. eight (8) DIP switches I. two (2) status LEDs Specifications The Dual Reader Interface Module is for use in low voltage, class 2 circuit only. Figure 1: LNL-1320 Power DC input 12 to 24 VDC +10%, 550 mA maximum (plus reader current) 12 VDC @ 450 mA 24 VDC @ 270 mA Communication Ports Port 1 RS-485 (2-wire or 4-wire), 2400 to 38400 bps async Inputs Eight (8) supervised, EOL resistors, 1k/1k ohm standard Two (2) non-supervised Power 1 twisted pair, 18 AWG RS-485 24 AWG twisted pair(s) with shield, 4000 ft (1200 m) maximum Wire Requirements Inputs twisted pair per input, 30 ohms maximum Outputs 5 A 28 VDC Reader Power Output Regulated Mode 125 mA maximum each reader Temperature +32 F to +158 F (0 C to +70 C), operating -67 F to +185 F (-55 C to +85 C), storage Environmental Humidity 0% to 95% RHNC Dimension (HxWxD) 1 i

LNL-1320 Dual Reader Interface Module Quick Reference Guide 1.0 Introduction The Dual Reader Interface Module board contains the following components (Refer to

Tags:

  Guide, Reference, Quick, Quick reference guide

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Quick Reference Guide - Bosch Security Systems

1 LNL-1320 Dual Reader Interface Module Quick Reference Guide Introduction The Dual Reader Interface Module board contains the following components (Refer to Figure 1): A. eight (8) supervised/non-supervised alarm inputs B. one (1) RS-485 interface C. two (2) reader interfaces D. six (6) relay outputs E. one (1) power input F. one (1) cabinet tamper G. five (5) jumpers H. eight (8) DIP switches I. two (2) status LEDs Specifications The Dual Reader Interface Module is for use in low voltage, class 2 circuit only. Figure 1: LNL-1320 Power DC input 12 to 24 VDC +10%, 550 mA maximum (plus reader current) 12 VDC @ 450 mA 24 VDC @ 270 mA Communication Ports Port 1 RS-485 (2-wire or 4-wire), 2400 to 38400 bps async Inputs Eight (8) supervised, EOL resistors, 1k/1k ohm standard Two (2) non-supervised Power 1 twisted pair, 18 AWG RS-485 24 AWG twisted pair(s) with shield, 4000 ft (1200 m) maximum Wire Requirements Inputs twisted pair per input, 30 ohms maximum Outputs 5 A 28 VDC Reader Power Output Regulated Mode 125 mA maximum each reader Temperature +32 F to +158 F (0 C to +70 C), operating -67 F to +185 F (-55 C to +85 C), storage Environmental Humidity 0% to 95% RHNC Dimension (HxWxD) 1 in.

2 X 6 in. x 8 in. (25 mm x 152 mm x 203 mm) Mechanical Weight 10 oz. (290 g) nominal Table 1: LNL-1320 Specifications LNL-1320 LNL-1320 Quick Reference Guide 49309C Page 2 2006 Bosch Security Systems , Inc. Wiring Supervised Alarm Inputs - Standard wiring configuration is as follows (Alarm Contacts 1-4 are for Door #1, Alarm Contacts 5-8 are for Door #2), see Figure 3. Wire the IN1 IN8 inputs using a twisted pair cable, 30 ohms maximum. Terminate each of these inputs with two (2) 1000-ohm resistors (1% tolerance watt) for supervised inputs. (See Figure 2) 1K, 1%NCSupervisedUnsupervisedNCNONO1K, 1%1K, 1%1K, 1% Figure 2: Supervised/Unsupervised In 1In 2In 3In 4In 5In 6In 7In 8In 9 GNDIn 10 Door 1 Door ContactDoor 1 REXDoor 1 Aux 1 Door 1 Aux 2 Door 2 Door ContactDoor 2 REXDoor 2 Aux 1 Door 2 Aux 2 Cabinet TamperPower Failure Figure 3: DRI Alarm Input Contact Wiring Upstream Controller Communication The RS-485 is asynchronous, half-duplex, using 1 start bit, 8 data bits, 1 stop bit.

3 TR2+GNDTR3+TR3-TR2-GNDLNL-500TR+R+R-TR-G ND Figure 4: RS-485 2-Wire Communication TR2+TR2-GNDTR3+TR3-GNDTR+TR-R+R-SGLNL-50 0 Figure 5: RS-485 4-Wire Communication LNL-1320 LNL-1320 Quick Reference Guide 2006 Bosch Security Systems , Inc. Page 3 49309C Power Wire the power input with an 18 AWG (minimum) twisted pair cable. VINGND12 to 24 VDC+- Figure 6: Power Input Wiring Relay Outputs Control Output Wiring DC SOURCEAC SOURCENCCNONCCNOFUSE+-LOADLOADMOVFUSE Figure 7: Control Output Wiring Relay Outputs NCCNONCCNONCCNONCCNONCCNONCCNORLY 1 RLY 2 RLY 3 RLY 4 RLY 5 RLY 6 Door 1 StrikeRelayDoor 1 Aux 1 Door 1 Aux 2 Door 2 StrikeRelayDoor 2 Aux 1 Door 2 Aux 2 Figure 8: DRI Alarm Output Contact Wiring Reader Communications Wire the J1 interface using a 24 AWG (minimum) cable. VOLEDBZRD1/CLKD0/DATGNDREDBRNORGWHTGRNBL K0123456789*# Figure 9: Reader Wire Connections Configuration The Dual Reader Interface Module board contains (8) DIP switches and (3) jumpers that must be configured for your system.

4 Setting DIP Switches The default positions for DIP switches is: Address 00; 38,400 bps (switches 6 and 7 are on, others are off). 12345678 Figure 10: DIP Switch Settings DIP Switch(es) Used to configure: 1, 2, 3, 4, 5 Device Communication address (0-31) 6, 7 Communication baud rate (38400, 19200, 9600 bps) 8 Not used Table 2: DIP Switch explanations Communication Baud Rate To configure the communication baud rate, set DIP switches 6 and 7 according to Table 3. DIP SWITCH Baud Rate (bps) 6 7 38400 ON ON 19200 OFF ON 9600 ON OFF 0 OFF OFF Table 3: Setting Baud Rate 2006 Bosch Security Systems , Inc. 130 Perinton Parkway, Fairport, NY 14450-9199 USA Customer Service: (800) 289-0096; Technical Support: (888) 886-6189 49309C Quick Reference Guide 10/06 LNL-1320 Page 4 of 4 Device Addresses To configure the device communication address, set DIP switches 1, 2, 3, 4, and 5 according to Table 4.

5 DIP SWITCH DIP SWITCH ADDRESS 5: 4: 3: 2: 1: ADDRESS 5: 4: 3: 2: 1: 0 OFF OFF OFF OFF OFF 16 ON OFF OFF OFF OFF 1 OFF OFF OFF OFF ON 17 ON OFF OFF OFF ON 2 OFF OFF OFF ON OFF 18 ON OFF OFF ON OFF 3 OFF OFF OFF ON ON 19 ON OFF OFF ON ON 4 OFF OFF ON OFF OFF 20 ON OFF ON OFF OFF 5 OFF OFF ON OFF ON 21 ON OFF ON OFF ON 6 OFF OFF ON ON OFF

6 22 ON OFF ON ON OFF 7 OFF OFF ON ON ON 23 ON OFF ON ON ON 8 OFF ON OFF OFF OFF 24 ON ON OFF OFF OFF 9 OFF ON OFF OFF ON 25 ON ON OFF OFF ON 10 OFF ON OFF ON OFF 26 ON ON OFF ON OFF 11 OFF ON OFF ON ON 27 ON ON OFF ON ON 12 OFF ON ON OFF OFF 28 ON ON ON OFF OFF 13 OFF ON ON OFF ON 29 ON ON ON OFF ON 14 OFF ON ON ON OFF 30 ON ON ON ON OFF 15 OFF ON ON ON ON 31 ON ON ON ON ON Table 4: DIP Switch Device Addresses Installing Jumpers 2W4WJ3 2-Wire 2W4WJ3 4-Wire RS-485 Type Jumper J3 is used to configure the RS-485 type for Port 1 on the READYKEYPRO Dual Reader Interface Module board.

7 There are two possible configuration options that can be used to install this jumper: 2-wire configuration, and 4-wire configuration. Figure 11: RS-485 configuration for Jumper J3 J4 J4 in ON position (5 volts) J4 J4 in OFF position (12 volts) Jumpers J4 need to be configured. J4 controls Reader 1 and Reader 2 voltage output. Figure 12: Jumper J4 configuration J2 J2 in regulated mode (default) J2 J2 in unregulated mode With unregulated mode, the supply voltage is passed through the readers with no regulation. Figure 13: Jumper J2 configuration EOL Termination ON Configuration for J5, J6 J6J5 EOL Termination Not ON Configuration for J5, J6 J5J6 RS-485 EOL Terminator Status Figure 14: Jumper J5 & J6 Configuration