Transcription of Quick Start Guide: 4088A MultiVariable Transmitter …
1 Quick Start Guide00825-0100-4088, Rev CAApril 2019 Rosemount 4088A MultiVariable Transmitterwith Modbus output ProtocolSafety messagesNOTICEThis guide provides basic guidelines for the Rosemount 4088 MultiVariable Transmitter . It does notprovide instructions for diagnostics, maintenance, service, or troubleshooting. Reference the 4088 MultiVariable Transmitter Reference Manual for more instruction. All documents are availableelectronically at and instructions in this section may require special precautions to ensure the safety of thepersonnel performing the operation. Information that raises potential safety issues is indicated with awarning symbol ( ). Refer to the following safety messages before performing an operationpreceded by this symbol. WARNINGE xplosions could result in death or serious of this Transmitter in an explosive environment must be in accordance with theappropriate local, national, and international standards, codes, and practices.
2 Review theapprovals section of the 4088 MultiVariable Transmitter Reference Manual for any restrictionsassociated with a safe installation. Before connecting a Field Communicator in an explosive atmosphere, ensure the instrumentsin the loop are installed in accordance with intrinsically safe or non-incendive field wiringpractices. In an Explosion-proof/Flameproof installation, do not remove the Transmitter covers whenpower is applied to the leaks may cause harm or result in and tighten process connectors before applying shock can result in death or serious contact with the leads and terminals. High voltage that may be present on leads can causeelectrical entries Unless marked, the conduit/cable entries in the Transmitter housing use a 1/2 14 NPT threadform. Entries marked M20 are M20 x thread form. On devices with multiple conduitentries, all entries will have the same thread form.
3 Only use plugs, adapters, glands, orconduit with a compatible thread form when closing these entries. When installing in a hazardous location, use only appropriately listed or Ex certified plugs,adapters, or glands in cable/conduit required for Quick the 4 Consider housing the and power up ..14 Verify device the 25 Product Start GuideApril 20192 Rosemount 4088A MultiVariable Transmitter Quick Start Guide1 Steps required for Quick installation Start > Mount the Transmitter : Mount the Transmitter Consider housing rotation: Consider Housing Rotation Set the switches: Set the Switches Wiring and power up : Wiring and Power Up Verify device configuration: Verify Device Configuration Trim the Transmitter : Trim the Transmitter > FinishApril 2019 Quick Start GuideQuick Start Guide32 Mount the flow applicationsProcedure1.
4 Place taps to the side of the Mount beside or below the Mount the Transmitter so that the drain/vent valves are Direction of flow applicationsProcedure1. Place taps in the top or side of the Mount beside or above the Direction of flowQuick Start GuideApril 20194 Rosemount 4088A MultiVariable Transmitter Quick Start flow applicationsProcedure1. Place taps to the side of the Mount beside or below the Fill impulse lines with Direction of bracketsFigure 2-1: Mounting Bracket Coplanar FlangePanel mountPipe mount April 2019 Quick Start GuideQuick Start Guide5 Figure 2-2: Mounting Brackets Traditional FlangePanel mountPipe mount Figure 2-3: Mounting Brackets In-linePanel mountPipe mount considerationsIf the Transmitter installation requires assembly of a process flange,manifold, or flange adapters, follow these assembly guidelines to ensure atight seal for optimal performance characteristics of the Transmitter .
5 Onlyuse bolts supplied with the Transmitter or sold by Emerson as spare 2-4 illustrates common Transmitter assemblies with the bolt lengthrequired for proper Transmitter Start GuideApril 20196 Rosemount 4088A MultiVariable Transmitter Quick Start GuideFigure 2-4: Common Transmitter AssembliesA4 (44 mm)D4 (44 mm)4 (57 mm)C4 (44 mm)4 (38 mm)B4 (73 mm)A. Transmitter with coplanar flangeB. Transmitter with coplanar flange and optional flange adaptersC. Transmitter with traditional flange and optional flange adaptersD. Transmitter with coplanar flange and optional Rosemount ConventionalManifold and flange adaptersNoteFor all other manifolds, contact Customer Central technical are typically carbon steel or stainless steel. Confirm the material byviewing the markings on the head of the bolt and referencing Table 2-1.
6 Ifbolt material is not shown in Table 2-1, contact the local Emersonrepresentative for more the following bolt installation procedure:Procedure1. Carbon steel bolts do not require lubrication and the stainless steelbolts are coated with a lubricant to ease installation. However, noadditional lubricant should be applied when installing either type Finger-tighten the Torque the bolts to the initial torque value using a crossing Table 2-1 for initial torque Torque the bolts to the final torque value using the same crossingpattern. See Table 2-1 for final torque 2019 Quick Start GuideQuick Start Guide75. Verify the flange bolts are protruding through the sensor modulebefore applying pressure (see Figure 2-5).ExampleTable 2-1: Torque Values for the Flange and Flange Adapter BoltsBolt materialHead markingsInitial torqueFinal torqueCarbon Steel(CS)B7M 300 in-lb650 in-lbStainless Steel(SST)316316316SW316 STM316RB8M 150 in-lb300 in-lbFigure 2-5: Proper Bolt InstallationABA.
7 BoltB. Sensor moduleQuick Start GuideApril 20198 Rosemount 4088A MultiVariable Transmitter Quick Start with flange adapters WARNINGF ailure to install proper flange adapter O-rings may cause process leaks,which can result in death or serious injury. Only use the O-ring that isdesigned for its specific flange Flange adapterB. O-ringC. PTFE-based profile (square)D. Elastomer profile (round)Whenever the flange or adapters are removed, visually inspect the them if there are any signs of damage, such as nicks or cuts. If the O-rings are replaced, re-torque the flange bolts and alignment screws afterinstallation to compensate for seating of the seal for housingThread sealing (PTFE) tape or paste on male threads of conduit is required toprovide a water/dust tight conduit seal and meets requirements of NEMA Type 4X, IP66, and IP68.
8 Consult factory if other Ingress Protection ratingsare required. For M20 threads, install conduit plugs to full threadengagement or until mechanical resistance is gage Transmitter orientationThe low side pressure port (atmospheric reference) on the in-line gagetransmitter is located under the sensor module neck label. (See Figure 2-6)Keep the vent path free of any obstruction, including but not limited topaint, dust, and lubrication by mounting the Transmitter so that anycontaminants can drain 2019 Quick Start GuideQuick Start Guide9 Figure 2-6: In-line Gage TransmitterAA. Low side pressure port (under neck label) Quick Start GuideApril 201910 Rosemount 4088A MultiVariable Transmitter Quick Start Guide3 Consider housing rotationTo improve field access to wiring or to better view the optional LCD display:Procedure1.
9 Loosen the housing rotation set Turn the housing up to 180 left or right of its original (as shipped) Re-tighten the housing rotation set 3-1: Transmitter Housing Set ScrewA. LCD displayB. Housing rotation set screw (3/32-in.) CAUTIONDo not rotate the housing more than 180 without first performing adisassembly procedure. Over-rotation may sever the electricalconnection between the sensor module and the the LCD displayTransmitters ordered with the LCD display will be shipped with the addition to housing rotation, the optional LCD display can be rotated in90 increments by squeezing the two tabs, pulling out, rotating andsnapping back into LCD display pins are inadvertently removed from the electronics board,carefully re-insert the pins before snapping the LCD display back into the following procedure and Figure 3-2 to install the LCD display:Procedure1.
10 If the Transmitter is installed in a loop, then secure the loop anddisconnect 2019 Quick Start GuideQuick Start Guide112. Required: Remove the Transmitter cover on the electronics boardside (opposite the field terminals side). Do not remove instrumentcovers in explosive environments when circuit is Engage the four-pin connector into the electronics board and snapLCD display into Required: In order to meet explosion-proof requirements, reinstallthe housing cover and tighten so the cover is fully seated with metalto metal contact between the housing and cover. After the cover isseated properly, replace the flathead screw located on the bottom ofthe housing 3-2: Optional LCD DisplayBCAA. Electronics boardB. LCD displayC. Display coverQuick Start GuideApril 201912 Rosemount 4088A MultiVariable Transmitter Quick Start Guide4 Set the switchesProcedure1.