Rosemount 0065/0185 Sensor Assembly - Emerson

Quick Start Guide00825-0200-2654, Rev GBSeptember 2020 Rosemount 0065/0185 SensorAssemblyNOTICEThis guide provides basic guidelines for Rosemount 0065 and 0185 Sensor models. It does not provideinstructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof,Flameproof, or intrinsically safe ( ) the Rosemount 0065 and 0185 ordered was assembled to a temperature transmitter, see theappropriate Quick Start Guide for information on configuration and hazardous locations certifications. WARNINGE xplosions could result in death or serious of this transmitter in an explosive environment must be in accordance with the appropriatelocal, national, and international standards, codes, and entriesUnless marked, the conduit/cable entries in the housing use a 14 NPT thread form. Entries marked M20 are M20 thread form. On devices with multiple conduit entries, all entries will have thesame thread form. Only use plugs, adapters, glands, or conduit with a compatible thread form whenclosing these accessUnauthorized personnel may potentially cause significant damage to and/or misconfiguration of endusers equipment.

December 2017 2 Quick Start Guide NOTICE This guide provides basic guidelines for Rosemount 0065 and 0185 Sensor models. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof,

Tags:

  Rosemount, 6500, Assembly, Sensor, 8051, Rosemount 0065 0185 sensor assembly

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Rosemount 0065/0185 Sensor Assembly - Emerson

1 Quick Start Guide00825-0200-2654, Rev GBSeptember 2020 Rosemount 0065/0185 SensorAssemblyNOTICEThis guide provides basic guidelines for Rosemount 0065 and 0185 Sensor models. It does not provideinstructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof,Flameproof, or intrinsically safe ( ) the Rosemount 0065 and 0185 ordered was assembled to a temperature transmitter, see theappropriate Quick Start Guide for information on configuration and hazardous locations certifications. WARNINGE xplosions could result in death or serious of this transmitter in an explosive environment must be in accordance with the appropriatelocal, national, and international standards, codes, and entriesUnless marked, the conduit/cable entries in the housing use a 14 NPT thread form. Entries marked M20 are M20 thread form. On devices with multiple conduit entries, all entries will have thesame thread form. Only use plugs, adapters, glands, or conduit with a compatible thread form whenclosing these accessUnauthorized personnel may potentially cause significant damage to and/or misconfiguration of endusers equipment.

2 This could be intentional or unintentional and needs to be protected security is an important part of any security program and fundamental to protecting yoursystem. Restrict physical access by unauthorized personnel to protect end users assets. This is true forall systems used within the Assembly of 21 Quick Start GuideSeptember diagramsFigure 1-1: Rosemount Series 65 RTD Lead Wire ConfigurationSeries 65 RTD flying leads and spring-loaded adapter-termination codes 0 or 3onlySingle elementDual elementWhtWhtRedRed Series 65 RTD terminal block termination code 2 Single elementDual element(1)RedRedWhtWht43161346 RedRedWht321 RedRedWht654123456 (1)The color of the terminal posts in the terminal block may not match the color ofthe lead wires connected to the 2020 Quick Start GuideQuick Start Guide3 NoteFor 3-wire systems use one white and two red leads. Do not connect thewhite leads. Insulate or terminate the unused white lead in a manner thatprevents shorting to the ground.

3 For 2-wire systems, connect both sets 1-2: Rosemount Series 185 Thermocouple Lead WireConfigurationThermocouple terminal blockSingle elementDual element Table 1-1: Rosemount Series 185 Thermocouple CharacteristicsTypeAlloys (wirecolor)SheathmaterialTemperaturerang e ( C)Limits of errorinterchangeabilityDIN EN 60584-2 ToleranceclassJFe (+ black),Cu-Ni ( white) (321 SST) 40 to 375,375 to C, t1 KNi-Cr (+ green),Ni-Al ( white) (Alloy600) 40 to 375,375 to 10001 NNi-Cr-Si (+pink),Ni-Si ( white)1 ENi-Cr (+violet),Cu-Ni ( white) (321 SST) 40 to 375,375 to 8001 TCu (+brown),Cu-Ni ( white) 40 to 125,125 to C, t1 NoteTo distinguish the two sensors in Rosemount Dual 185 Sensors (flying leador spring loaded styles), the lead wires of one Sensor will be longer than theother Start GuideSeptember Assembly Assembly without thermowell40 mmRosemount 314425 mm16 mm11 mmLLLN N N ABCDR osemount 644 with LCD display meterRosemount 644 Rosemount 248 A.

4 Head or field mount transmittersB. IP68 ir IP65 connection headsC. Sensor with flying leads, terminal block, or spring-loaded adapterD. ExtensionsN dimensions measures from thread engagement pointSeptember 2020 Quick Start GuideQuick Start thermowell Sensor assembly40 mm25 mmNNNUUUUNAMURNAMURGBGN ABCDR osemount 644 with LCD display meterRosemount 644 Rosemount 248 A. Head or field mount transmitterB. IP68 or IP65 connection headsC. Sensor with flying leads or terminal blockD. Threaded and flanged tubular thermowells For straight threading, N dimension reference bottom of hex. Fortapered threading, N dimension reference thread engagement point(bottom of thread).Quick Start GuideSeptember thermowell Sensor assemblyNoteThe Rosemount 644 is available with or without an LCD mm25 mmLLL11 mm11 mm11 mm11 mm16 mmTUU60 mm60 mmU40 mmU60 mm UN N N Rosemount 3144 Rosemount 644 with LCD display meterRosemount 644 Rosemount 248 ABCDEA. Head or field mount transmitterB.

5 IP65 or IP65 connection headsC. Sensor with flying leads, terminal block, or spring-loaded adapterD. Stand-alone extensionsE. Weld-in, threaded, or flanged barstock thermowells N dimension measures from thread engagement point. This dimension is 80 mm for Class 1500 and Class 2500 flangesSeptember 2020 Quick Start GuideQuick Start Guide73 Product certificationsRev Directive informationA copy of the EU Declaration of Conformity can be found at the end of theQuick Start Guide. The most recent revision of the EU Declaration ofConformity can be found at Location CertificationAs standard, the transmitter has been examined and tested to determinethat the design meets the basic electrical, mechanical, and fire protectionrequirements by a nationally recognized test laboratory (NRTL) as accreditedby the Federal Occupational Safety and Health Administration (OSHA). AmericaThe US National Electrical Code (NEC) and the Canadian Electrical Code(CEC) permit the use of Division marked equipment in Zones and Zonemarked equipment in Divisions.

6 The markings must be suitable for the areaclassification, gas, and temperature class. This information is clearly definedin the respective locations FM Explosion-proof and Dust-Ignition-proofCertificateFM17US0170 XStandardsFM Class 3600: 2011; FM Class 3611: 2004; FM Class 3615:2006; FM Class 3810: 2005; ANSI/NEMA 250: 1991 MarkingsXP CL I, Div 1, GP B, C, D; DIP CL II/III, Div 1, GP E, F, G; T5 ( 50 C Ta + 85 C); Type CSA Explosion-proof and Dust-Ignition-proofCertificate1063635 StandardsCSA No. 0-M91; CSA No. 25-1966; CSA ; CSA No. 94-M91; CSA No. 142-M1987; CSA No. 213-M1987 MarkingsXP CL I, Div 1, GP B, C, D; DIP CL II/III, Div 1, GP E, F, G; CL I, Div2, GP A, B, C, D; ( 50 C Ta + 85 C)Quick Start GuideSeptember ATEX FlameproofCertificateFM12 ATEX0065 XStandardsEN 60079-0:2012+A11:2013; EN 60079-1: 2014 MarkingsII 2 G Ex db IIC Gb, T6( 50 C Ta + 40 C), ( 50 C Ta + 60 C)See Process temperature limits for process Conditions for Safe Use (X)1.

7 See certificate for ambient temperature The non-metallic label may store an electrostatic charge and becomea source of ignition in Group III Guard the LCD display cover against impact energies greater than Flameproof joints are not intended for A suitable certified Ex d or Ex tb enclosure is required to be connectedto temperature probes with Enclosure option N .6. Care shall be taken by the end user to ensure that the externalsurface temperature on the equipment and the neck of DIN StyleSensor probe does not exceed 130 Non-standard paint options may cause risk from electrostaticdischarge. Avoid installations that cause electrostatic build-up onpainted surfaces, and only clean the painted surfaces with a dampcloth. If paint is ordered through a special option code, contact themanufacturer for more ATEX Intrinsic SafetyCertificateBaseefa16 ATEX0101 XStandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012 Markings II 1 G Ex ia IIC T5/T6 Ga (see certificate for schedule)Thermocouples; Pi = 500 mWT6 -60 C Ta + 70 CRTDs; Pi = 192 mWT6 -60 C Ta + 70 CRTDs; Pi = 290 mWT6 -60 C Ta + 60 CT5 -60 C Ta + 70 CSeptember 2020 Quick Start GuideQuick Start Guide9 Special Condition for Safe Use (X)1.

8 The equipment must be installed in an enclosure which affords it adegree of ingress protection of at least ATEX Type nCertificateBAS00 ATEX3145 StandardsEN 60079-0:2012+A11:2013, EN 60079-15:2010 Markings II 3 G Ex nA IIC T5 Gc ( 40 C Ta + 70 C)ND ATEX DustCertificateFM12 ATEX0065 XStandardsEN 60079-0:2012+A11:2013; EN 60079-31: 2014 Markings II 2 D Ex tb IIIC T130 C Db ( 40 C Ta + 70 C)See Process temperature limits for process Conditions for Safe Use (X)1. See certificate for ambient temperature The non-metallic label may store an electrostatic charge and becomea source of ignition in Group III Guard the LCD display cover against impact energies greater than Flameproof joints are not intended for A suitable certified Ex d or Ex tb enclosure is required to be connectedto temperature probes with Enclosure option N .6. Care shall be taken by the end user to ensure that the externalsurface temperature on the equipment and the neck of DIN StyleSensor probe does not exceed 130 Non-standard paint options may cause risk from electrostaticdischarge.

9 Avoid installations that cause electrostatic build-up onpainted surfaces, and only clean the painted surfaces with a dampcloth. If paint is ordered through a special option code, contact themanufacturer for more IECEx FlameproofCertificateIECEx FMG Start GuideSeptember :2011, IEC60079-1:2014-06 MarkingsEx db IIC Gb, T6( 50 C Ta + 40 C), ( 50 C Ta + 60 C)See Process temperature limits for process Conditions for Safe Use (X)1. See certificate for ambient temperature The non-metallic label may store an electrostatic charge and becomea source of ignition in Group III Guard the LCD display cover against impact energies greater than Flameproof joints are not intended for A suitable certified Ex d or Ex tb enclosure is required to be connectedto temperature probes with Enclosure option N .6. Care shall be taken by the end user to ensure that the externalsurface temperature on the equipment and the neck of DIN StyleSensor probe does not exceed 130 Non-Standard Paint options may cause risk from electrostaticdischarge.

10 Avoid installations that cause electrostatic build-up onpainted surfaces, and only clean the painted surfaces with a dampcloth. If paint is ordered through a special option code, contact themanufacturer for more INMETRO FlameproofCertificateUL-BR NBR IEC 60079-0: 20013; ABNT NBR IEC 60079-1: 2016;ABNT NBR IEC 60079-31:2014 MarkingsEx db IIC * Gb *: ( 50 C Ta + 40 C), *:( 50 C Ta + 60 C) Ex tb IIIC T130 C Db ( 40 C Ta + 70 C)Special Conditions for Safe Use (X)1. See product description for ambient temperature limits and processtemperature The non-metallic label may store an electrostatic charge and becomea source of ignition in Group III 2020 Quick Start GuideQuick Start Guide113. Guard the LCD display cover against impact energies greater than Consult the manufacturer if dimensional information on theflameproof joints is A suitable certified Ex d or Ex tb enclosure is required to be connectedto temperature probes with Enclosure option N.