1 BA 001 N/08/ Version for NMS53xProservoNMS53x SeriesOperating ManualEndress+HauserSystems & GaugingSakura Endress1 Proservo NMS53xTable of ContentsTable of ContentsGeneral Notes .. 21 Safety Instructions .. 32 System Configuration .. 53 Specifications and Dimensions .. Typical Specifications .. Dimensions .. 94 Necessary Tools for Installation .. 105 Application drawings for tanks .. Mounting without Guide System .. Mounting with Stilling Well .. Mounting with Guide Wire .. 146 Mounting Preparations .. Electrostatic Charge .. 167 Cable Connection .. Cabling .. Input and output .. Cable Gland .. 248 Displacer and Measuring Wire .. Shape, Diameter, and Material .. 259 Touch Control and Programming Matrix .. Display and Operating Elements .. Functions of the Operating Elements.
2 HOME Position .. Access Code .. Description of the Programming Matrix .. Programming Matrix .. Description of the Programming Matrix .. 4010 Setting/installation of the wire drum Installation of the Displacer .. 62 Wire drum setting .. 6411 Initial Settings .. Setting the System Date and Time .. Initial Settings of Density Measurement .. Setting the Tank Height .. 6712 Initial Weight Calibration .. Displacer Weight Calibration .. Weight Table .. 7213 Operation of the Displacer .. 7314 Level Measurement .. 7415 On-site Level Calibration .. Before On-Site Level Calibration .. On-Site Level Calibration 7616 Density Measurement .. Preliminary settings .. Density Measurement .. 7817 Interface Measurement .. Upper Interface Measurement .. Lower Interface 7918 Remote Communication.
3 Serial Pulse Output (V1/022 protocol) .. Rackbus RS 485 .. 8119 Setting for Alarm Outputs (4 contacts) .. Alarm Setting .. Setting Level and Temperature Alarms .. Alarm History Display .. List of Alarm Messages .. 8420 Setting for Analogue mA Outputs(2 channels) .. Setting for Output Type .. Settings for Current OutputWhen Error 8621 Settings for Operation Inputs .. 8722 Settings for Prothermo NMT535/6 8823 Settings for Promonitor NRF560 Connections .. 8924 Diagnosis and Troubleshooting .. Selection of Diagnostic Code and History .. Error and Status Messages .. 91 Appendix A: Settings after Resetting .. 93 Appendix B: Intelligent Function .. 95 Appendix C: Calculation of Levels 96 Appendix D: Sealing of the Proservo .. 98 Appendix E: Technical Criteria of the Gas VaporExplosion-Proof Structure.
4 99 Appendix F: Protection Class (IEC529) .. 101 Appendix G: Operation Commands andNew Operation Status .. 102 Appendix H: Whessoe Matic 550 (WM550) Communication Board Setting .. 103 Appendix I: Mark / Space (M/S)Communication Board setting .. 104 Appendix J: ENRAF Bi Phase MarkCommunication Board Setting .. 105 Glossary .. 1112 Sakura EndressProservo NMS53xGeneral NotesInstruction Manual: This instruction manual applies to the Proservo NMS53x with or later softwareinstalled. Please read this manual carefully and make sure you understand its contents beforeusing the product. This manual is solely intended to describe product functions and should not be usedfor any other purpose. No part of this manual may be reproduced or reprinted without permission. This manual may be subject to change without prior notice.
5 This manual was prepared with the highest degree of care. However, should you findany errors or have any questions, contact one of our service offices or your localsales safety and improper use:Follow the safety guidelines presented in this manual when using this product. This isimportant for ensuring the safe operation of the system to be controlled by the the user does not follow these instructions properly, we cannot guarantee the safetyof the NotesTo maintain a high level of safety and to ensure correct operation, the operator shouldat all time observe the safety notes given in this operating manual. They are indicatedby the following pictograms:Observe this note to prevent serious personal or material this note to prevent serious material this note to achieve the specified performance of the RequirementsProduct RequirementsProduct RequirementsProduct RequirementsProduct Requirements Power sourceCheck the voltage of the power supply before connecting it to the product.
6 It should bethe exact voltage required for proper operation of the product. Use in hazardous areasWhen using the product in the first or second-class hazard location (Zone 1 or Zone 2)be sure to use an intrinsically safe or pressure and explosion-proof apparatus. Take theutmost care during the installation, wiring, and piping of such apparatus to ensure thesafety of the system. For safety reasons, maintenance or repairs on the product while itis being used with such apparatus should only be performed by qualified personnel. External connectionWhen an external connection is required, the product should be protectively groundedbefore it is connected to a measurement object or an external control NotesSakura Endress3 Proservo NMS53x1. Safety InstructionsWarning!Observe the following notes to prevent serious physical or material supply Check that voltage and frequency of the local power supply are in the range of thetechnical data of the instrument before turning on the power.
7 Please refer to supply cable Use the power supply cable attached to the instrument when it is ordered from themanufacturer, or the cable specified in the instruction. The power source should have a ground terminal, and the power supply cableshould have a ground line. Please refer to Do not remove the grounding of the instrument when the power supply is turned may set the instrument in a dangerous condition. Please refer to Make sure the grounding of the instrument before connecting input and output toanother of the instrumentThe Proservo NMS53x series is designed for level measurement of a liquid in a storagetank or similar facilities. It is possible to connect auxiliary instruments in the specification described in thismanual. However, the performance of the connected instruments is not refer to the instructions attached to the individual instruments when they areconnected.
8 A hazardous situation may occur if the instrument is used for a purpose that is notdesigned for or any other improper ways. The instrument has the IEC class 1(ground terminal).Use in explosion hazardous areas Please use the explosion-proof type for measurement in explosion-hazardous areas. Instruments used in explosion hazardous areas should be mounted and wiredaccording to the explosion-proof regulations. Instruments mounted in explosion hazardous areas must not be opened when thepower supply is turned on. Tighten the cable gland firmly. The maintenance and repair of the instrument are limited to fulfill the explosionproof Safety Instructions4 Sakura EndressProservo NMS53xElectrostatic chargeMounting with a stilling well (also called pipe) is recommended for use in a tank thatcontains a flammable liquid with low case of installation without pipe, the first measurement or the measurement afterhoisting the displacer must be carried out after a certain stilling time.
9 This is shown inthe following table (according to TIIS recommendation 1988).With pipe, the stilling time is the same as for !Observe the following notes to prevent serious material of the measuring wireThe instrument detects the buoyancy force on the light displacer, and the thin wire isused for the transmission of forces as well as for the length measurement. Do not kink or twist the measuring wire. It is easily damaged by careless handling. Do not hoist the displacer by pulling the wire by hand. Do it by operation of theinstrument. Do not touch the wire during operation. Do not bend the wire to a radius of less than 50 do not guarantee the lifetime of the measuring wire if it is treated of the displacerFor the delivery of the instrument, the small displacer is either shipped mounted on thegauge or separately.
10 In case of the all-in-one type, refer to the attached instruction for the removal of thestuffing material. In case of separate shipment, install the displacer to the measuring wire beforemounting the gauge onto the mounting nozzle of the tank. Use a spacing stand orother approved procedures to level the Proservo NMS53x installation of thedisplacer. Make sure that the measuring wire is correctly located in the groove ofthe wire drum after mounting of the condition If turbulent conditions are expected at the liquid surface, use a stilling well, or hoistthe displacer during turbulence If the measurement is carried out under turbulent condition, consultEndress+Hauser before turbulent condition may influence the accuracy of the readingor damage the measuring Safety InstructionsTable 1(according to recommendation 1988)Flammable liquidconductivityRecommendation value of stilling timeFlammable liquid volume(S/cm)(minute)(m )<10 10~50 50~100 >5000 >10-810~ 10-12-12 10~ 10-14<10-8-14>1>1>1 >2 >2>3>10 >30 >4>10>10>120 >120>60>5>240 Sakura Endress5 Proservo NMS53xLocalProthermoNMT535/6 (AC &DC)Power (AC)