1 SINGLE PIECE STANDARD ECMAIR HANDLERSFOR USE WITH SPLIT-SYSTEMCOOLING & HEAT PUMPSMODELS: AHE18 THRU 60* / 6 ELE(6-9) / 6 ELF(0-2)Due to continuous product improvement, specifications are subject to change without us on the web Additional rating information can be found 5-year limited parts 10-year limited parts warranty when product isregistered online within 90 days of purchase for replace-ment or closing for new home 9001 Certified QualityManagement SystemFOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALETECHNICALGUIDE TECHNICALGUIDE 697886-BTG-G-0314 DESCRIPTIONThe AHE Air Handler line offers the ultimate in comfort.
2 Soundand application flexibility. This unit may be used for upflow, down-flow, horizontal right, or horizontal left applications. No special kits arerequired to install this deluxe JCI Unitary Products air handlers and coils use a TXV to pro-vide our customers with the optimum performance and refriger-ant control. Air handlers are shipped with Flex-coils without afactory installed metering device. For added flexibility, an R-22or R-410A TXV or orifice can be field installed to meet yourrefrigerant Expansion Valve - Provides the ultimate refrigerantcontrol required for today s high efficient product.
3 The UPG bolt-on TXV provides easy installation to convert the air handler tothe required refrigerant, which is a true bolt-on design that doesnot require brazing to replace or Cabinet - All air handler cabinets are thermally insu-lated with 3/4 foil faced insulation to prevent Sealed - Achieves 2% or less total airflow leakage rateat duct blaster field test conditions for system airflow Finish Inside and Out - Air handler casings are madeof pre-painted galvanized steel which provides a better paint tosteel bond that resists corrosion and rust creep.
4 All internal coilsheet metal parts are made of G60 galvanized or prepaintedG30 - All models have internal filter racks provided for usewith 1 thick standard size Heat Kits - New 6HK series of field installed electricheat kits are available for installation friendly and easy serviceapplications. These 6HK kits are unique to these new Efficiency Blowers - All models use high efficiencybrushless DC motors to provide cooling SEER rating Controls Unitary Products697886-BTG-G-0314 DIMENSIONS & DUCT CONNECTION DIMENSIONSJDB lowerCompartmentCircuit BreakerPanelDrain Pan Connectionsfor Horizontal ApplicationsRefrigerantConnectionsDrain Connectionsfor UpflowApplications7-11/32 BAKC1-1/2 Top OutletDimensionsFilterAccess18-9/32 EBottom InletDimensions13 FDimensions1 ModelsDimensionsWiring Knockouts2 Refrigerant
5 ConnectionsLine SizeABCDEFJKH eightWidthDepthPowerControlLiquidVaporAH E18B/AHE22B/AHE24B/AHE30B (1 CJZ7/6 ELE6)4617 1/221 1/216 1/213-29/3216 1/27/8 (1/2)1-3/8(1)1-23/32 (1-1/4)7/8 (1/2)3/83/4 AHE34C/AHE36C (1 CKA2/6 ELE9)522121 1/217-13/3220 AHE42D/AHE48D/AHE60D(1 CKA3/6 ELF0/6 ELF1)5724 1/22620-29/3223-1/27/81. All dimensions are in Actual size (conduit size).COIL TECHNICAL DATAM odelsApplicationRefrig. Conn. TypesFace Area(Sq. Ft.)RowsDeepFins Per /Heat (2) 14 x x /Heat (2) 16 x x /Heat (2) 16 x x /Heat (2) 16 x x /Heat (2) 16 x x /Heat (2) 20 x x /Heat (2) 22 x x /Heat (2) 24 x x /Heat (2) 28 x x Controls Unitary Products3697886-BTG-G-0314 COOLING CAPACITY1 ModelsRated CFM2 Entering AirDry/Wet Bulb ( F)MBH@ Evap.
6 Temp. and Corresponding R-410A Pressure ( F/PSIG)35 and notes on next Controls Unitary Products697886-BTG-G-0314 AHE36C73085 Actual capacity varies with the outdoor AC or HP that is used with the Airflow is calculated for each system CAPACITY1 (Continued)ModelsRated CFM2 Entering AirDry/Wet Bulb ( F)MBH@ Evap. Temp. and Corresponding R-410A Pressure ( F/PSIG)35 Controls Unitary Products5697886-BTG-G-0314 APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM% Of Rated Airflow (CFM)80%90%100%110%120%Capacity & ELECTRICAL DATA - COOLING ONLYM odelsAHE18B(6 ELE6)AHE22 BAHE24B(6 ELE7)AHE30B(6 ELE8)AHE34 CAHE36C(6 ELE9)AHE42D(6 ELF0)AHE48D(6 ELF1)AHE60D(6 ELF2)
7 Blower - Diameter x Width10 x 810 x 810 x 810 x 811 x 1011 x 1011 x 1011 x 1011 x 10 MotorHP1/3 HP1/3 HP1/3 HP 1/3 HP1/2 HP1/2 HP1/2 HP3/4 HP3/4 HPNominal RPM105010501050105010501050105010501050 Voltage208/230208/230208/230208/230208/2 30208/230208/230208/230208/230 Full Load Amps OR PERMANENTSize16 x 20 x 116 x 20 x 116 x 20 x 116 x 20 x 120 x 20 x 120 x 20 x 122 x 20 x 122 x 20 x 122 x 20 x 1 Permanent Type Kit1PF0601BK1PF0601BK1PF0601BK1PF0601BK1 PF0602BK1PF0602BK1PF0603BK1PF0603BK1PF06 03 BKShipping / Operating Weight (lbs.)115/103120/105120/105120/105152/13 7152/137168/150171/153174/1561.
8 Field & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENTFor a power distribution voltage that is different than the provided nominal voltage, multiply the kW and MBH data from the table bythe conversion factor in the following POWERNOMINAL VOLTAGECONVERSION DATA - COOLING ONLY ModelsMotor FLA1 Minimum Circuit AmpacityMOP2 Minimum Wire Size (AWG)3 AHE18B / AHE22B /AHE24B / / AHE36C / / FLA = Full Load Amps2. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay 75 C, copper wire only.
9 If wire other than non-plated, 75 C ambient, copper wire is used, consult applicable tables of the NEC and local HEAT: MINIMUM FAN SPEED1 Heater Kit Models2,3 Nom. kW@240 VAir Handler ModelsAHE18 BAHE22 BAHE24 BAHE30 BAHE34 CAHE36 CAHE42 DAHE48 DAHE60D6HK(0,1) Low #2 Med Low #2 Low #1 Med #3 Low #1 Med Low #2 Med Low #26HK(0,1) Low #2 Med Low #2 Med Low #2 Med Low #2 Med #3 Med #3 Med Low #26HK(0,1) High #4 Med High #4 Med #3 Med #3 Med #3 Med #3 Med Low #26HK(0,1) High #4 Med High #4 Med High #4 Med High #4 Med High #4 Med High #4 Med #36HK(1,2) High #4 Med High #4 Med High #4 Med High #4 Med High #4 Med #36HK(1,2)
10 #5 High #5 Med High #4 Med High #4 Med High #4 Med #36HK(1,2) #5 High #5 High #5 Med High #46HK(1,2) #5 High #5 High #5 High #56HK(1,2)65025066HK1650252524kW------Hi gh #51. The referenced letter in this table is for the heat jumper (0,1) - 0 = no circuit breaker OR 1 = with circuit (1,2) - 1 = with circuit breaker, no breaker jumper bar OR 2 = with circuit breaker & breaker jumper Controls Unitary Products697886-BTG-G-0314 ELECTRIC HEAT PERFORMANCE DATA: 208/230-1-60 & 208/230-3-60 Heater Models1,2 Nominal kW @240 VTotal Heat3kW StagingkWMBHW1 OnlyW1 + W2208V230V208V230V208V230V208V230V1PH6HK (0,1) (0,1) (0,1) (0,1) (1,2) (1,2) (1,2) (1,2) (1,2) (0,1) - 0 = no circuit breaker OR 1 = with circuit (1,2) - 1 = with circuit breaker, no breaker jumper bar OR 2 = with circuit breaker & breaker jumper For different power distributions, see conversion table on Page DATA FOR SINGLE SOURCE POWER SUPPLY.