INSTALLATION INSTRUCTIONS69-2770 EFS-03 TrueZONE Bypass (CPRD)APPLICATIONThe TrueZONE Bypass constant pressure regulating damper (CPRD) is a round static pressure relief damper. It is used in forced-air Bypass applications to relieve excess static pressure when some of the zone dampers are closed. The damper is installed in a duct that delivers air to the return or a dump zone. The damper automatically opens and closes to maintain a desired static CPRD uses a calibrated spring to regulate the Bypass air accurately when any number or combination of zones is calling. Conventional, weighted arm, Bypass dampers may operate properly when one zone is calling; however, when different combinations of zones are calling, they Bypass too much or too little. This can cause callbacks when homeowners complain of air the Correct the Bypass damper by subtracting the cfm of the smallest zone from the cfm of the Table 1 to determine the CPRD to : Bypass CFM = Total System CFM - Smallest Zone CFMSPECIFICATIONSC onstruction:Galvanized steel, see Table 2 Temperature Range:Ambient: 0F 165F (-17C 73C)Storage: 30F 150F (-1C 65C) Table 1.

Secure the damper to sheet metal ductwork with screws or to flex-duct with tape. If ducting with flex-duct, the outer layer of plastic can be taped to the damper mounting flange to fully insulate the damper. Alternatively, the CPRD can dump air from the supply to a non-critical temperature area such as a hallway, basement, or false ceiling.

Tags:

  Sheet, Bypass, Honeywell, Truezone bypass, Truezone

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of TrueZONE Bypass (CPRD) - Honeywell

1 INSTALLATION INSTRUCTIONS69-2770 EFS-03 TrueZONE Bypass (CPRD)APPLICATIONThe TrueZONE Bypass constant pressure regulating damper (CPRD) is a round static pressure relief damper. It is used in forced-air Bypass applications to relieve excess static pressure when some of the zone dampers are closed. The damper is installed in a duct that delivers air to the return or a dump zone. The damper automatically opens and closes to maintain a desired static CPRD uses a calibrated spring to regulate the Bypass air accurately when any number or combination of zones is calling. Conventional, weighted arm, Bypass dampers may operate properly when one zone is calling; however, when different combinations of zones are calling, they Bypass too much or too little. This can cause callbacks when homeowners complain of air the Correct the Bypass damper by subtracting the cfm of the smallest zone from the cfm of the Table 1 to determine the CPRD to : Bypass CFM = Total System CFM - Smallest Zone CFMSPECIFICATIONSC onstruction:Galvanized steel, see Table 2 Temperature Range:Ambient: 0F 165F (-17C 73C)Storage: 30F 150F (-1C 65C) Table 1.

2 Damper SizingDIMENSIONST able 2. CPRD DamperReplacement RegulatorMaximum AirflowCPRD8 CPR8600 CFMCPRD10 CPR101000 CFMCPRD12 CPR121400 CFMCPRD14 CPR141700 CFMM odelABCDEG augeinmminmminmminmminmmCPRD8 Bypass (CPRD)Automation and Control SolutionsHoneywell International Douglas Drive NorthGolden Valley, MN Registered Trademark 2012 Honeywell International 03 Rev. 12-12 Printed in United StatesINSTALLATIONS elect Damper LocationInstall the CPRD onto a starting collar or in duct that loops from supply to return. The supply side take-off must be before any zone dampers. It is best to install the return side of this loop as far a practical from the air CPRD can be mounted in vertical or horizontal ductwork, or at any angle. The damper may also be rotated to be installed with the regulator on either side, top or at any angle the damper to sheet metal ductwork with screws or to flex-duct with tape.

3 If ducting with flex-duct, the outer layer of plastic can be taped to the damper mounting flange to fully insulate the , the CPRD can dump air from the supply to a non-critical temperature area such as a hallway, basement, or false Regulator to the regulator with the "D" shaft on the damper (see Fig. 1). the regulator onto the "D" shaft and push down while turning counterclockwise until it snaps into place (see Fig. 2).Setting the RegulatorThe CPRD is factory set to open at approximately .5"WC." This setting is satisfactory for most installations. Some systems have higher static this by: all zones call fan, heat, or cool; whichever has the highest CFM. that the damper position indicator points to it does not point to closed: Flip the adjustment crank out (see Fig. 3) Push down on the adjustment crank with gentle pressure. Caution: Do not rotate the adjustment crank without first pushing it down Turn the adjustment crank clockwise until the indicator points to closed When done, flip the adjustment crank back into the locked only the smallest zone call for fan, heat, or cool.

4 That the airflow into that zone is not objectionable. If it is, then set the regulator to a lower the RegulatorIf you need to remove the regulator from the damper, do so by pressing the red release button. See Fig. 4. It is easier to remove the regulator after turning the pressure down to a lower 1. Fig. 2. Fig. 3. Fig. 4. CPRD regulatorM34208M34209M34210M34211 ADJUSTMENTCRANKRELEASE BUTTON (RED)DAMPER POSITIONINDICATORPRESSURE SETTINGINDICATORNOTICE D INSTALLATIOND rivation TrueZONE (CPRD)APPLICATIONLe registre de r gulation de pression constante (CPRD) de d rivation TrueZONE est un registre de pression statique rond. Il est utilis dans les applications de d rivation air puls pour limiter la pression statique en exc s lorsque certains registres de zone sont ferm s. Le registre s'installe dans une gaine fournissant de l'air la zone de retour ou d' vacuation. Le registre s'ouvre et se ferme automatiquement pour maintenir la pression statique d sir CPRD utilise un ressort talonn pour r guler avec pr cision l'air de d rivation en cas d'appel de diverses zones ou combinaisons de zones.

5 Les registres de d rivation bras lest conventionnels peuvent fonctionner ad quatement en cas d'appel d'une seule zone; toutefois, lorsque diverses combinaisons de zones lancent un appel, la d rivation est insuffisante ou excessive. Ceci peut causer des retours de produits lorsque les propri taires se plaignent du bruit caus par l' lection du CPRD le registre de d rivation en soustrayant la superficie de la zone la plus petite de la capacit du sys-t le Tableau 1 pour d terminer le CPRD : Superficie d rivation = Capacit totale du syst me - Superficie de la zone la plus petiteCARACT RISTIQUESC onstruction : Acier galvanis , voir le Tableau 2 Plage de temp rature : Ambiante : 0 F-165 F (-17 C-73 C)Stockage : 30 F-150 F (-1 C-65 C)Tableau 1. Dimensionnement du 2. Dimensions du CPRDR egistre de d rivationR gulateur de rechangeD bit d'air maximumCPRD8 CPR8600 CFMCPRD10 CPR101000 CFMCPRD12 CPR121200 CFMCPRD14 CPR141400 CFMMod leABCDEC alibrepo mmpo mmpo mmpo mmpo mmCPRD8 8203,2 9,652451,503811,54 292,84 4,6511826 CPRD10 1025411,42 2901,503813,50 3434,6511826 CPRD12 1230513,18 2351,503815,47 392,84 4,6511824 CPRD14 1435514,96 3801,503817,36 4414,6511822MF34207 DEBCAR gulateurRegistreD RIVATION TrueZONE (CPRD)69-2770 EFS 032 INSTALLATIONS lection de l'emplacement du registreInstaller le CPRD sur un collet de d part ou dans une gaine faisant une boucle de l'alimentation au retour.

6 L'appel c t alimentation doit tre situ avant tout registre de zone. Il est recommand d'installer le c t retour de cette boucle aussi loin que possible d'un niveau pratique du syst me de traitement de l' CPRD peut tre mont dans une gaine horizontale ou verticale, ou tout autre angle. Le registre peut aussi tre tourn pour tre install avec le r gulateur d'un c t ou de l'autre, en haut, ou tout angle interm le registre sur une gaine en t le avec des vis ou sur des tuyaux flexibles avec du ruban conduits . Si des tuyaux flexibles sont pr sents, la couche externe du plastique peut tre coll e sur la bride de montage du registre avec du ruban conduits pour isoler compl tement le CPRD peut aussi vacuer l'air de l'alimentation vers une zone de temp rature non critique telle qu'un couloir, un sous-sol ou un du r gulateur au le r gulateur sur l'arbre D du registre (voir la Fig.)

7 1). glisser le r gulateur sur l'arbre D et le pousser vers le bas tout en tournant dans le sens antihoraire jusqu' ce qu'il s'enclenche en position (voir la Fig. 2).R glage du r gulateurLe CPRD est r gl en usine pour s'ouvrir environ 0,5 po Ce r glage satisfait la plupart des installations. Certains syst mes ont une pression statique sup rieure. V rifier cela de la fa on suivante : un appel de ventilateur, chauffage ou refroid-issement sur toutes les zones; noter celle qui a la plus grande rifier que l'indicateur de position du registre pointe sur la position de 'il ne pointe pas sur la position de fermeture D gager le bras de r glage (voir la Fig. 3). Pousser le bras de r glage vers le bas en appliquant une l g re pression. Mise en garde : Ne pas faire tourner le bras de r glage sans l'avoir abaiss au pr alable. Tourner le bras de r glage dans le sens horaire jusqu' ce que l'indicateur pointe sur la position de fermeture.

8 Une fois ceci termin , faire pivoter le bras de r glage en position de lancer un appel de ventilateur, chauffage ou refroid-issement que pour la zone la plus petite. rifier que le d bit d'air dans cette zone ne pose pas de probl me. Si c'est le cas, r gler le r gulateur une pression inf du r gulateurS'il est n cessaire de retirer le r gulateur du registre, appuyer sur le bouton de lib ration rouge pour ce faire. Voir la Fig. 4. Il est plus facile de retirer le r gulateur apr s avoir r duit la 1. Fig. 2. Fig. 3. Fig. 4. R gulateur CPRDM34208MF34209M34210MF34211 BRAS DE R GLAGEBOUTON DE LIB RATION (ROUGE)INDICATEUR DE POSITION DU REGISTREINDICATEUR DE R GLAGE DE PRESSIOND RIVATION TrueZONE (CPRD)Solutions de r gulation et d automatisationHoneywell International Douglas Drive NorthGolden Valley, MN Marque de commerce d pos e aux tats-Unis 2012 Honeywell International Inc.

9 Tous droits r serv s69-2770 EFS 03 Rev. 12-12 Imprim aux tats-UnisINSTRUCCIONES PARA LA INSTALACI NDesviador de paso TrueZONE (CPRD)APLICACI NEl desviador de paso TrueZONE del regulador para el control de la presi n constante (CPRD) es un regulador circular para el alivio de la presi n est tica. Se utiliza en aplicaciones de derivaci n de aire forzado para aliviar el exceso de presi n est tica cuando algunos de los reguladores de zona est n cerrados. El regulador se instala en un conducto que suministra aire al conducto de retorno o a una zona de descarga. El regulador se abre y se cierra autom ticamente para mantener la presi n est tica CPRD utiliza un resorte calibrado para regular la derivaci n del aire de forma precisa cuando se produce cualquier cantidad o combinaci n de demanda de zonas. Los reguladores de derivaci n convencionales, con brazo de contrapeso, pueden funcionar adecuadamente cuando una zona emita una demanda; sin embargo, cuando se emiten diferentes combinaciones de demandas en las zonas, estas derivar n demasiado o muy poco aire.

10 Esto puede ocasionar llamadas al servicio t cnico cuando los propietarios residenciales se quejan del ruido causado por el mo seleccionar el CPRD el regulador de derivaci n restando los PCM de la zona m s peque a de los PCM del la tabla 1 para determinar el CPRD que debe : Derivaci n PCM = PCM total del sistema - PCM de la zona m s peque n: Acero galvanizado, consulte la tabla 2. Rango de temperatura:Ambiente: 0 F a 165 F (-17 C a 73 C)Almacenaje: 30 F a 150 F (-1 C a 65 C)Tabla 1. C mo dimensionar el 2. Dimensiones CPRDR egulador de desviaci n Controlador de reemplazo M ximo flujo de aire CPRD8 CPR8600 PCMCPRD10 CPR101000 PCMCPRD12 CPR121200 PCMCPRD14 CPR141400 PCMM odeloABCDEC alibrepo mmpo mmpo mmpo mmpo mmCPRD8 DE PASO TrueZONE (CPRD)69-2770 EFS 032 INSTALACI NSelecci n de la ubicaci n del reguladorInstale el CPRD en un anillo de arranque o en un conducto que vaya del suministro al retorno.