1 User Manual English APC smart -UPS XL. 2200/3000 VA XL. 120/208/230 VAC. Tower/Rack-Mount 5U. Uninterruptible Power Supply 990-2975 09/2006. Introduction About this UPS. The American Power Conversion (APC ) Uninterruptible Power Supply (UPS) provides protection for electronic equipment from utility power blackouts, brownouts, sags and surges. The UPS filters small utility line fluctuations and isolates electronic equipment from large disturbances by internally disconnecting from utility line power. The UPS provides continuous power from the internal battery until utility power returns to safe levels or the battery is fully discharged. Unpack Read the Safety Guide before installing the UPS. Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The packaging is recyclable; save it for reuse or dispose of it properly. Check the package contents: UPS. Front bezel Literature kit containing: EPO connector Eight snap-on speed nuts Serial cable Additional contents for Two rail cleats (required for four post 230 V models: USB cable rack only).
2 Eight ornamental screws for Two rack-mount brackets APC power cable securing the unit in the rack Product documentation Alternate input power cord Eight 5/16 in (.8 cm) pan-head (UK customers). smart -UPS User Manuals CD. screws for attaching cleats to the IEC Power cord chassis rails PowerChute Business Edition CD. IEC jumper cables (required for four post rack only) Safety information Eight 5/8 in ( cm) pan-head Warranty information screws for attaching rack-mount brackets to the unit Specifications Temperature This unit is intended for indoor use Operating 32 to 104 F (0 to 40 C) only. Select a location sturdy enough Storage 5 to 86 F (-15 to 30 C) charge the UPS battery every six months to handle the weight. Do not operate the UPS where there 86 to 113 F (30 to 45 C) charge the UPS battery every three months is excessive dust or the temperature or humidity are outside the specified Maximum limits.
3 Elevation Environmental factors impact battery Operating 10,000 ft (3,000 m) life. High temperatures, poor utility Storage 50,000 ft (15,240 m) power, and frequent, short duration discharges will shorten battery life. Humidity 0 to 95% relative humidity, non-condensing Weight 142 lbs (64 kg) with battery module 142 lbs (64 kg). 89 lbs (40 kg) without battery module 27 lbs (12 kg) each battery module Maximum Number of External Battery Packs Supported by the 10. smart -UPS XL. NOTE: The model and serial numbers are located on a small, rear panel label. For some models, an additional label is located on the chassis under the front bezel. smart -UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual 3. Installation The UPS is shipped in tower configuration. Tower Configuration Connect the battery. After the battery has been connected, tuck the battery cables in between the battery and the battery door.
4 This will ensure a secure fit of the bezel to the unit. 4 smart -UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual Rack-Mount Configuration This unit is intended for mounting in a two post rack. To order a four post rack-mount kit contact your dealer or refer to the APC Web site, Tower to rack-mount conversion procedure The UPS and the battery modules are heavy. Remove the battery modules to lighten the UPS during installation. Pull the battery disconnect strap attached to the battery connector. DO NOT pull the battery cables to disconnect the battery. Disconnect Battery Battery Disconnect Strap Foam Spacer Remove the top cover and . Remove and rotate the display panel . Four post rack-mount Two post rack-mount bracket position bracket position x4. 5/8 in cm A four post rack configuration requires installation of two brackets in the forward position (see diagram above), two cleats (supplied with this unit), and the four post rails.
5 The rails can be ordered through the APC Web site smart -UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual 5. Install unit in rack Ensure rack stability prior to installing devices in the rack. The UPS should be installed at or near the bottom of the rack. If external battery packs are to be installed in the rack, the UPS must be the top unit in the configuration. Connect Battery x4. Ornamental Foam Spacer After all of the batteries have been connected, tuck the battery cables in between the batteries and the battery doors. This will ensure a secure fit of the bezel to the unit. Accessories This UPS is equipped with an accessory SmartSlot. Refer to the APC Web site, for available accessories. If a standard accessory, such as a Network Management card is to be installed on this UPS, refer to the Utility CD for user documentation. Install accessories prior to connecting power to the UPS.
6 6 smart -UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual Start-Up Connect Equipment and Power to the UPS. 1. The UPS features a transient voltage surge-suppression (TVSS) screw located on the rear panel, for connecting the ground lead on surge suppression devices such as telephone and network line protectors. Prior to connecting the grounding cable, ensure that the UPS is NOT connected to utility or battery power. 2. Connect equipment to the UPS. NOTE: This UPS is equipped with an external battery connector on the rear panel of the unit. Where appropriate use an APC extension battery cable. For ordering details contact your dealer or APC. through the Web site 3. Add optional accessories to the SmartSlot located on the rear panel. 4. Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords. 230 V models: The utility power cord is supplied in the UPS literature kit.
7 Prior to connecting the utility power, connect the ground lead (optional) to the TVSS screw. 5. 120 V models: Check the SITE WIRING FAULT LED located on the rear panel. The LED will be illuminated if the UPS is plugged into an improperly wired utility power outlet, (see Troubleshooting). 6. To use the UPS as a master on/off switch be sure all connected equipment is switched on. Rear Panels 3000 VA 3000 VA. 120 VAC 208 VAC. 2200 VA 2200 VA. 3000 VA. 120 VAC. 230 VAC. Start the UPS. 1. Press the button on the front panel to start the UPS. The battery charges to 90% capacity during the first four hours of normal operation. Do not expect full battery run capability during this initial charge period. Refer to the APC Web site, for battery runtimes. 2. For optimal computer system security, install PowerChute smart -UPS monitoring software. smart -UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual 7.
8 Communication Ports SERIAL PORT USB PORT Use only the supplied cable to connect to the serial port. A standard serial interface cable is incompatible with the UPS. Serial and USB ports cannot be used simultaneously. Emergency Power Off The emergency power off (EPO) feature is user configurable. EPO provides immediate de-energizing of connected equipment from a remote location, without switching to battery operation. 1. Use the EPO connector supplied with the UPS. 2. Use a normally-open contact to connect the +24 terminal to the IN terminal. External voltage is not required. 3. Wire the four-pin connector to the EPO system. EPO PORT EPO. (located on rear panel) Connector The EPO interface is a Safety Extra Low Voltage (SELV) circuit. Connect it only to other SELV circuits. The EPO interface monitors circuits that have no determined voltage potential. Such closure circuits may be provided by a switch or relay properly isolated from the utility.
9 To avoid damage to the UPS, do not connect the EPO interface to any circuit other than a closure type circuit. Use one of the following cable types to connect the UPS to the EPO switch. CL2: Class 2 cable for general use. CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air. CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft. CLEX: Limited use cable for use in dwellings and for use in raceways. For installation in Canada: Use only CSA certified, type ELC, (extra-low voltage control cable). For installation in other countries: Use standard low-voltage cable in accordance with national and local regulations. 8 smart -UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual Operation Display Panels 120/208 V models 120/208 V. Battery Charge 230 V models 230 V. Display Panel Indicators and Function Buttons Indicator Indicator Title Description LED.
10 On Line The UPS is supplying utility power to the connected equipment, (see Troubleshooting). AVR Trim The UPS is compensating for a high utility voltage. Refer to the APC Web site, for AVR settings. AVR Boost The UPS is compensating for a low utility voltage. Refer to the APC Web site, for AVR settings. On Battery The UPS is supplying battery power to the connected equipment. Overload The connected equipment is drawing more than the UPS power rating allows, (see Troubleshooting). Replace Battery/Battery The battery is disconnected or must be replaced, (see Troubleshooting). Disconnected smart -UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual 9. Indicator Indicator Title Description LED. 208 V. Diagnostic The UPS has a diagnostic feature that indicates the utility voltage. 120 V. Utility Voltage The UPS starts a self-test as part of this procedure. The self-test does not affect the voltage display.