990-297509/2006 APC smart -UPS XL 2200/3000 VA XL120/208/230 VACT ower/Rack-Mount 5 UUninterruptible power SupplyUser ManualEnglishSmart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U user Manual3 IntroductionAbout this UPSThe American power Conversion (APC ) Uninterruptible power Supply (UPS) provides protection for electronic equipment from utility power blackouts, brownouts, sags and surges. The UPS filters small utility line fluctuations and isolates electronic equipment from large disturbances by internally disconnecting from utility line power . The UPS provides continuous power from the internal battery until utility power returns to safe levels or the battery is fully the Safety Guide before installing the the UPS upon receipt. Notify the carrier and dealer if there is packaging is recyclable; save it for reuse or dispose of it the package contents:SpecificationsNOTE: The model and serial numbers are located on a small, rear panel label.

Smart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual 7 Start-Up Connect Equipment and Power to the UPS 1. The UPS features a transient voltage surge-suppression (TVSS) screw located on the rear panel, for connecting the ground lead on surge suppression devi ces such as telephone and network line protectors.

Tags:

  Manual, User, Power, Smart, English, User manual english

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of User Manual English - - APC USA

1 990-297509/2006 APC smart -UPS XL 2200/3000 VA XL120/208/230 VACT ower/Rack-Mount 5 UUninterruptible power SupplyUser ManualEnglishSmart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U user Manual3 IntroductionAbout this UPSThe American power Conversion (APC ) Uninterruptible power Supply (UPS) provides protection for electronic equipment from utility power blackouts, brownouts, sags and surges. The UPS filters small utility line fluctuations and isolates electronic equipment from large disturbances by internally disconnecting from utility line power . The UPS provides continuous power from the internal battery until utility power returns to safe levels or the battery is fully the Safety Guide before installing the the UPS upon receipt. Notify the carrier and dealer if there is packaging is recyclable; save it for reuse or dispose of it the package contents:SpecificationsNOTE: The model and serial numbers are located on a small, rear panel label.

2 For some models, an additional label is located on the chassis under the front bezel. UPS Front bezel Literature kit containing: EPO connector Serial cable USB cable Eight ornamental screws for securing the unit in the rack Eight 5/16 in (.8 cm) pan-head screws for attaching cleats to the chassis rails(required for four post rack only) Eight 5/8 in ( cm) pan-head screws for attaching rack-mount brackets to the unit Eight snap-on speed nuts Two rail cleats (required for four post rack only) Two rack-mount brackets Product documentation smart -UPS user Manuals CD PowerChute Business Edition CD Safety information Warranty informationAdditional contents for 230 V models: APC power cable Alternate input power cord (UK customers) IEC power cord IEC jumper cablesTemperatureOperatingStorage32 to 104 F (0 to 40 C)5 to 86 F (-15 to 30 C) charge the UPS battery every six months86 to 113 F (30 to 45 C) charge the UPS battery every three monthsThis unit is intended for indoor use only.

3 Select a location sturdy enough to handle the not operate the UPS where there is excessive dust or the temperature or humidity are outside the specified factors impact battery life. High temperatures, poor utility power , and frequent, short duration discharges will shorten battery ElevationOperatingStorage10,000 ft (3,000 m)50,000 ft (15,240 m)Humidity0 to 95% relative humidity, non-condensingWeight142 lbs (64 kg) with battery module89 lbs (40 kg) without battery module27 lbs (12 kg) each battery module142 lbs (64 kg) Maximum Number of External Battery Packs Supported by the smart -UPS XL104 smart -UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U user ManualInstallationThe UPS is shipped in tower ConfigurationConnect the the battery has been connected, tuck the battery cables in between the battery and the battery door.

4 This will ensure a secure fit of the bezel to the 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U user Manual5 Rack-Mount ConfigurationThis unit is intended for mounting in a two post rack. To order a four post rack-mount kit contact your dealer or refer to the APC Web site, to rack-mount conversion procedureThe UPS and the battery modules are heavy. Remove the battery modules to lighten the UPS during the top cover and . Remove and rotate the display panel .A four post rack configuration requires installation of two brackets in the forward position (see diagram above), two cleats (supplied with this unit), and the four post rails. The rails can be ordered through the APC Web site the battery disconnect strap attached to the battery connector. DO NOT pull the battery cables to disconnect the battery.

5 DisconnectBatteryBatteryDisconnectStrapF oamSpacerx45/8 cmFour post rack-mount bracket positionTwo post rack-mount bracket position6 smart -UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U user ManualInstall unit in rackEnsure rack stability prior to installing devices in the UPS should be installed at or near the bottom of the rack. If external battery packs are to be installed in the rack, the UPS must be the top unit in the UPS is equipped with an accessory SmartSlot. Refer to the APC Web site, for available a standard accessory, such as a Network Management card is to be installed on this UPS, refer to the Utility CD for user accessories prior to connecting power to the all of the batteries have been connected, tuck the battery cables in between the batteries and the battery doors.

6 This will ensure a secure fit of the bezel to the SpacerConnectBatterySmart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U user Manual7 Start-UpConnect Equipment and power to the UPS1. The UPS features a transient voltage surge-suppression (TVSS) screw located on the rear panel, for connecting the ground lead on surge suppression devices such as telephone and network line to connecting the grounding cable, ensure that the UPS is NOT connected to utility or battery Connect equipment to the UPS. NOTE: This UPS is equipped with an external battery connector on the rear panel of the unit. Where appropriate use an APC extension battery cable. For ordering details contact your dealer or APC through the Web site Add optional accessories to the SmartSlot located on the rear Plug the UPS into a two-pole, three-wire, grounded receptacle only.

7 Avoid using extension cords. 230 V models: The utility power cord is supplied in the UPS literature kit. Prior to connecting the utility power , connect the ground lead (optional) to the TVSS V models: Check the SITE WIRING FAULT LED located on the rear panel. The LED will be illuminated if the UPS is plugged into an improperly wired utility power outlet, (see Troubleshooting).6. To use the UPS as a master on/off switch be sure all connected equipment is switched PanelsStart the UPS1. Press the button on the front panel to start the UPS. The battery charges to 90% capacity during the first four hours of normal operation. Do not expect full battery run capability during this initial charge period. Refer to the APC Web site, for battery For optimal computer system security, install PowerChute smart -UPS monitoring VA3000 VA230 VAC2200 VA120 VAC3000 VA208 VAC3000 VA120 VAC8 smart -UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U user ManualCommunication PortsEmergency power OffThe emergency power off (EPO) feature is user configurable.

8 EPO provides immediate de-energizing of connected equipment from a remote location, without switching to battery Use the EPO connector supplied with the Use a normally-open contact to connect the +24 terminal to the IN terminal. External voltage is not Wire the four-pin connector to the EPO EPO interface is a Safety Extra Low Voltage (SELV) circuit. Connect it only to other SELV circuits. The EPO interface monitors circuits that have no determined voltage potential. Such closure circuits may be provided by a switch or relay properly isolated from the utility. To avoid damage to the UPS, do not connect the EPO interface to any circuit other than a closure type one of the following cable types to connect the UPS to the EPO switch. CL2: Class 2 cable for general use.

9 CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air. CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft. CLEX: Limited use cable for use in dwellings and for use in raceways. For installation in Canada: Use only CSA certified, type ELC, (extra-low voltage control cable). For installation in other countries: Use standard low-voltage cable in accordance with national and local PORTUSB PORTUse only the supplied cable to connect to the serial port. A standard serial interface cable is incompatible with the and USB ports cannot be used PORT (located on rear panel)EPO ConnectorSmart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U user Manual9 OperationDisplay PanelsDisplay Panel Indicators and Function Buttons IndicatorLEDI ndicator TitleDescriptionOn LineThe UPS is supplying utility power to the connected equipment,(see Troubleshooting).

10 AVR TrimThe UPS is compensating for a high utility voltage. Refer to the APC Web site, for AVR BoostThe UPS is compensating for a low utility voltage. Refer to the APC Web site, for AVR BatteryThe UPS is supplying battery power to the connected connected equipment is drawing more than the UPS power rating allows, (see Troubleshooting).Replace Battery/Battery DisconnectedThe battery is disconnected or must be replaced, (see Troubleshooting).BatteryCharge120/208 V230 V120/208 V models230 V models10 smart -UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U user ManualIndicatorLEDI ndicator TitleDescriptionDiagnostic Utility VoltageThe UPS has a diagnostic feature that indicates the utility UPS starts a self-test as part of this procedure. The self-test does not affect the voltage and hold the button to view the utility voltage bar graph indicator.