VR8200; VR4200 Combination Gas Controls

Rev. 1-94 Honeywell Inc. 1994 Form Number 68-0046 4 CONTENTSS pecifications .. 2 Ordering Information .. 2 Installation .. 4 Startup and Checkout .. 9 Maintenance .. 12 Operation .. 12 Service .. 15VR8200; VR4200 Combination Gas ControlsVR4200VR8200(TRADELINE)The VR8200 Continuous Pilot Dual AutomaticValve Combination Gas Controls are used in gas-fired, standing pilot appliances. They include safetyshutoff, a manual valve, two automatic operators, apressure regulator, a pilot adjustment, and a conduitcover ( VR4200 only).nVR8200 for use with 24 Vac heating appliances andVR4200 for use with 120 Vac heating appliancesthat burn natural or liquefied petroleum (LP) rated at 130 feet3/hour at 1 inch wc pres-sure drop [ m3/hr at kPa]. Maximum regu-lated capacity is 200 feet3/hour [ meter3/hour].Minimum regulated capacity is 20 feet3/hour[ meter3/hour].nSolenoid-operated first automatic valve opens onthermostat call for heat and closes when call forheat second automatic valve opensunder control of the regulator and closes if gas orpower supply is manual gas control knob has ON,OFF, and PILOT reset button must be held down to permitgas flow while lighting pilot; can be pushed downonly in PILOT adjustments, wiring connections and pilot out-let are accessible from the top of the gas body pattern; right angle adaptersavailable for inlet and outl

thermostat call for heat and closes when call for heat ends. Diaphragm-operated second automatic valve opens under control of the regulator and closes if gas or power supply is interrupted. Three-position manual gas control knob has ON, OFF, and PILOT positions. Separate reset button must be held down to permit

Tags:

  Thermostats

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of VR8200; VR4200 Combination Gas Controls

1 Rev. 1-94 Honeywell Inc. 1994 Form Number 68-0046 4 CONTENTSS pecifications .. 2 Ordering Information .. 2 Installation .. 4 Startup and Checkout .. 9 Maintenance .. 12 Operation .. 12 Service .. 15VR8200; VR4200 Combination Gas ControlsVR4200VR8200(TRADELINE)The VR8200 Continuous Pilot Dual AutomaticValve Combination Gas Controls are used in gas-fired, standing pilot appliances. They include safetyshutoff, a manual valve, two automatic operators, apressure regulator, a pilot adjustment, and a conduitcover ( VR4200 only).nVR8200 for use with 24 Vac heating appliances andVR4200 for use with 120 Vac heating appliancesthat burn natural or liquefied petroleum (LP) rated at 130 feet3/hour at 1 inch wc pres-sure drop [ m3/hr at kPa]. Maximum regu-lated capacity is 200 feet3/hour [ meter3/hour].Minimum regulated capacity is 20 feet3/hour[ meter3/hour].nSolenoid-operated first automatic valve opens onthermostat call for heat and closes when call forheat second automatic valve opensunder control of the regulator and closes if gas orpower supply is manual gas control knob has ON,OFF, and PILOT reset button must be held down to permitgas flow while lighting pilot; can be pushed downonly in PILOT adjustments, wiring connections and pilot out-let are accessible from the top of the gas body pattern; right angle adaptersavailable for inlet and outletn1/2 in.

2 Inlet and 1/2 inch outlet; adapters availablefor 3/8 or 3/4 servo regulator effectively maintainsalmost constant gas output pressure under widefluctuation in gas supply and outlet screens filter terminal block color-coded beige to identifystanding pilot be installed at any angle between 0 and 90 degreesfrom the upright position, including male quick-connect terminals for electri-cal connections. Combination screw and quick-connect terminals on TRADELINE F to +175 F [-18 C to +79 C] temperaturerange standard; -40 F to +175 F [-40 C to 79 C] connector included with some models: alsoavailable as and outlet pressure taps included; both tapsaccessible from top of gas , slow- and step-opening models to LP gas conversion kit included withTRADELINE standard and slow-opening to LP gas conversion kit available for non-TRADELINE standard and slow-opening to natural gas conversion kit available for stan-dard and slow-opening 42VR8200, VR4200 SPECIFICATIONS ORDERING INFORMATIONS pecificationsIMPORTANT: The specifications given in this publica-tion do not include normal manufacturing toler-ances.

3 Therefore, this unit may not exactly match thelisted specifications. Also, this product is tested andcalibrated under closely controlled conditions, andsome minor differences in performance can be ex-pected if those conditions are TRADELINE MODELSSUPER TRADELINE Controls offer features not avail-able on TRADELINE or standard models, and are designedto replace a wide range of Honeywell and TRADELINE model specifications are thesame as those of standard models except as noted TRADELINE MODEL AVAILABLE: VR8200 AContinuous Pilot Dual Automatic Combination GasControl. Models for natural or LP FEATURES: Combination 1/4 inch quick-connect and screw ter-minals (includes convenience terminals). One 3/8 inch bushing. One 3/4 inch straight flange assembly (with O-ringand screws). One tool for flange hex screws. One pilot compression fitting. One Q340A 36-inch thermocouple with adapters MODELSTRADELINE models are selected and packaged toprovide ease of stocking, ease of handling and maximumreplacement value.

4 TRADELINE model specificationsare the same as those of standard models except as MODEL AVAILABLE: VR8200A Con-tinuous Pilot Dual Automatic Combination Gas Con-trol. Models for natural or LP FEATURES: Combination 1/4 inch quick-connect and screw ter-minals (includes convenience terminals) One 3/8 inch bushing One 3/4 inch straight flange assembly (with O-ringand screws) One tool for flange hex screws One pilot compression fittingSTANDARD MODELSMODEL: VR8200 and VR4200 Continuous Pilot DualAutomatic Valve Combination Gas Controls . For usein standing pilot appliances. See Table 1 for VOLTAGE: VR4200 : 120 Vac, 60 : 24 Vac, 60 Hz.(50/60 Hz models available on request.)POWER UNIT:Hold-in current: 300 mA current: 250 to 90 :Nominal output: 30 mV ( ohms).Open Circuit Turndown Voltage: 2 CONNECTIONS (2): 1/4 inch male quick-connects. Two convenience terminals on top of control(optional). Terminal block color-coded HEAT ANTICIPATOR SETTING: VR4200 : : OF GAS: VR8200 and VR4200 set up for naturalgas includes a 393691 LP Conversion Kit.

5 Kit forconversion from LP to natural gas is available for stan-dard and slow opening models. See : 130 feet3/hour [ meters3/hour]. Capacity isbased on 1000 Btu/feet3, specific gravity natural gasat 1 inch water column pressure drop [ MJ/meters3, specific gravity natural gas at kPa pressuredrop].Maximum regulated capacity is 200 feet3/hour[ meters3/hour]. Minimum regulated capacity is20 feet3/hour [ meters3/hour]. Use conversion factorsin Table 2 to convert to capacities for other regulated capacity is 40 feet3/hour InformationWhen purchasing replacement and modernization products from your TRADELINE wholesaler or your distributor, refer to theprice sheets for complete ordering number, or specify 1. Order number, SUPER TRADELINE or4. Convenience terminals, if if Accessories, if Natural or LP Order separately: pilot burner, thermocouple, transformer,3. Step pressure on step-opening controller, and thermostat or controller as you have additional questions, need further information, or would like to comment on our products or services, please write or phone:1.

6 Your local Honeywell Residential and Building Controls Sales Office (check white pages of your phone directory).2. Residential and Building Controls Division Customer SatisfactionHoneywell Inc., 1885 Douglas Drive NorthMinneapolis, Minnesota 55422-4386 (612) 951-1000In Canada Honeywell Limited/Honeywell Limit e, 740 Ellesmere Road, Scarborough, Ontario M1P 2V9. International Salesand Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan,Mexico, Netherlands, Spain, Taiwan, United Kingdom, , VR4200 SPECIFICATIONS368-0046 4 TABLE 2 GAS CAPACITYCONVERSION ListedGasGravityCapacity PATTERN: Straight-through with 1/2 inch inlet and1/2 inch outlet. Flanges available for 3/8, 1/2 and 3/4 inchstraight and 90 angle connection. See Table 1 MODEL FactoryOptional FactoryRange of FieldSuffixCharac-ofSettingsRegulator SettingsAdjustmentLetterteristicGasin. wckPain. wckPain. wckPaVR8200A, to to to to , to 122 to 38 to 122 to 3VR8200C, PStep-Natural Step , Step , Step , Step , Step none; Step none;VR4200C, , or , or , or , or Full Rate Full Rate , , to Rate Full Rate Full Rate Full Rate to to , Step , Step , Step , Step none; Step none; , or , or , or , or Full Rate Full Rate , , , , as8-122 to 3orderedaorderedaorderedaorderedaFull Rate Full Rate Full Rate Full Rate to 122 to to to to to to 122 to 38 to 122 to 3VR8200 JDelayed and to to to to to 122 to 38 to 122 to 3a Step pressure not 1 VR8200, VR4200 dimensions in in.

7 [mm].NOTE: Flange Kits include one flange with attached O-ringand four mounting screws. TRADELINE kits include9/64 in. hex wrench, as GAS OUTLET: Compression fitting for 1/4 in. 3 FLANGE PART NumberInlet/Outlet FlangeLess HexWith HexPipe SizeTypeWrenchWrench3/8 in. NPTS traight393690-1393690-11 Elbowa393690-2393690-121/2 in. NPTS traight393690-6393690-16 Elbowa393690-3393690-133/4 in. NPTS traight393690-4393690-14 Elbowa393690-5393690-15aElbow (angle) flanges cannot provide right hand inletwhen the ECO connector is [89]1 21 [43]11 1611 162 [69]1 [25]1 2[13]1 84 [104]3-5/8 [91] SWING RADIUSCONVENIENCE TERMINALSCONDUIT COVERVR42003 [89]1 21 [43]11 1611 162 [69]1 43 [83]1 [25]1 2[13]1 84 [104]3-5/8 [91] SWING RADIUS1/4 INCH QUICK-CONNECT TERMINALSCONVENIENCE TERMINALSVR82001 SCREW TERMINALS ON TRADELINE MODELS , VR4200 SPECIFICATIONS INSTALLATION68-0046 44 PRESSURE TAPPING: Inlet and outlet pressure taps acces-sible from top of gas control.

8 Taps are 1/8 inch NPT withplug containing recess for 3/16 inch Allen RATING: rating 1/2 psi [ kPa] REGULATION: See Table 1. Regulator ad-justment accessible from top of gas : Can be mounted 0 to 90 degrees in anydirection from the upright position of the gas controlknob, including RATING:VR8200A,C,H,J; VR4200A,C,H: 0 F to +175 F [-18 Cto +79 C].VR8200M,P; VR4200M,P: -40 F to +175 F [-40 C to+7 9 C].DIMENSIONS: See Fig. :American Gas Association design certificate: Gas Association design certificate: Gas Association design certificate: for Delta C SPECIFICATIONS: Convenience : Flanges, see Table 3. 393200-1 ECO Connector. 393691 Natural to LP Conversion Kit. 394588 LP to Natural Conversion Kit. 394349 9/64 inch hex tool for flange assembly : These gas Controls are shipped with pro-tective seals over inlet and outlet tappings. Do notremove seals until ready to connect the appliance manufacturer instructions if avail-able; otherwise, use the instructions provided INSTALLING THIS Read these instructions carefully.

9 Failure to fol-low them could damage the product or cause a Check the ratings given in the instructions and on theproduct to ensure the product is suitable for your Ensure installer is a trained, experienced After installation is complete, use these instructions tocheck out product OR EXPLOSION HAZARD,CAN CAUSE PROPERTY DAMAGE,SEVERE INJURY, OR these warnings exactly:1. Disconnect power supply before wiring to pre-vent electrical shock or equipment To avoid dangerous accumulation of fuel gas,turn off gas supply at the appliance service valvebefore starting installation, and perform GasLeak Test after completion of Do not bend pilot tubing at gas control or pilotburner after compression fitting has been tight-ened, or gas leakage at the connection may Always install sediment trap in gas supply lineto prevent contamination of gas Do not force the gas control knob. Use only yourhand to push down the reset button or turn thegas control knob.

10 Never use any tools. If the gascontrol knob or reset button will not operate byhand, the gas control should be replaced by aqualified service technician. Force or attemptedrepair may result in fire or apply a jumper across or short the valve coilterminals. This may burn out the heat anticipator inthe thermostat.!CONVERTING BETWEEN NATURAL AND LP GASWARNINGFIRE OR EXPLOSION HAZARD,CAN CAUSE PROPERTY DAMAGE,SEVERE INJURY, OR Do not use a gas control set for natural gas onan LP gas system or a gas control set for LPgas on a natural gas When making conversion, main pilot burnerorifices must be changed to meet appliancemanufacturer and VR4200 gas Controls can be convertedfrom one gas to another. To convert from natural gas to LP,use the 393691 LP Conversion Kit that is included with thegas control. To convert from LP to natural gas, use the394588 Natural Gas Conversion Kit (ordered separately).VR8200C,P and VR4200C,P gas Controls cannot be convert control from one gas to another:1.