Modified polyolefin (-CR) or fluoropolymer (-CT) outer jacketTinned-copper braidModified polyolefin inner jacketSelf-regulating conductive coreNickel-plated copper bus wireHeating cable constructionPRODUCT OVERVIEWR aychem XL-Trace is designed for pipe freeze protection and flow maintenance in the following applications: Freeze protection of general water piping (aboveground and buried) Freeze protection of fire sprinkler system piping, including sprinklers Flow maintenance of greasy waste lines (aboveground and buried) Flow maintenance of fuel lines (aboveground)The heating element in the XL-Trace heating cable consists of a continuous core of conductive polymer extruded between two copper bus wires.

Modified polyolefin (-CR) or fluoropolymer (-CT) outer jacket Tinned-copper braid Modified polyolefin inner jacket Self-regulating conductive core

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of XLMTRACE - nventthermal.com

1 Modified polyolefin (-CR) or fluoropolymer (-CT) outer jacketTinned-copper braidModified polyolefin inner jacketSelf-regulating conductive coreNickel-plated copper bus wireHeating cable constructionPRODUCT OVERVIEWR aychem XL-Trace is designed for pipe freeze protection and flow maintenance in the following applications: Freeze protection of general water piping (aboveground and buried) Freeze protection of fire sprinkler system piping, including sprinklers Flow maintenance of greasy waste lines (aboveground and buried) Flow maintenance of fuel lines (aboveground)The heating element in the XL-Trace heating cable consists of a continuous core of conductive polymer extruded between two copper bus wires.

2 The XL-Trace heating cable regulates its power output in response to pipe temperature changes. This self-regulating technology allows XL-Trace heating cable to be overlapped or installed on plastic pipes without total installed costThe XL-Trace heating cable s parallel circuitry allows it to be cut to the exact length required, with no wasted cable. Its flexibility allows it to be wrapped around complex fittings and valves. All of these characteristics simplify and streamline the design of a heat-tracing system.

3 Installation is quick and total operating costBuilding operators are assured of optimal energy efficiency and low maintenance costs when an XL-Trace system is same features that make an XL-Trace system easy to install the first time also simplify additions or changes to the system during building additional information, contact your Thermal Management representative or call (800) NUMBER5XL1-CR/CT5XL2-CR/CT8XL1-CR/CT8XL2 -CR/CT12XL2-CR/CTVOLTAGE120 V208 277 V120 V208 277 V208 277 VMAXIMUM OPERATING TEMPERATURE150 F (65 C)150 F (65 C)150 F (65 C)150 F (65 C)150 F (65 C)MAXIMUM EXPOSURE TEMPERATURE150 F (65 C)150 F (65 C)150 F (65 C) 150 F (65 C) 185 F1 (85 C)1 MINIMUM INSTALLATION TEMPERATURE0 F ( 18 C)0 F ( 18 C)0 F ( 18 C)0 F ( 18 C)0 F ( 18 C)MINIMUM BEND RADIUS1/2 in (12 mm)1/2 in (12 mm)1/2 in (12 mm)1/2 in (12 mm)1/2 in (12 mm)1 When the design requires 185 F (85 C)

4 Exposure temperature, all connections must be installed off the HEATING CABLEFor pipe freeze protection and flow maintenance1 / 5 Raychem-DS-H51349-XLTracePipeFreezeProte ctionCOM-EN-1707 THERMAL MANAGEMENTMAXIMUM CIRCUIT LENGTH IN FEET40 F / 110 F Maintain* Start-up temperature ( F)CB size (A)5XL18XL15XL28XL212XL2120 V120 V208 V240 V277 V208 V240 V277 V208 V240 V277 V 20 F151017617417818313113814611111411720134 1012322372451751841941481511563020115134 9356367262276291223227234402702014654744 783493683882973033120 F151158619920320914915716612012212620153 1152652712791992092211601631683023017239 8406419298314331239244252402702104704905 30370/399390/420420/44331932633620

5 F151341002322372441731821921261291332017 8133309315325231243257169172177302702004 6447348834636538525325826640270210470490 530370/462390/486420/513340/34934435540 F151601192782832922062172291421451502021 4159370378390275290306190194200302702104 70490530370/416390/438420/46228529130040 270210470490530370/554390/584420/616340/ 398360/406380/41950 F15 228240254152155160(buried)20 30432033820320721330 45748150730431032040 60964167640541442765 F15 272286302169172178(indoors grease)20 36238140222523023730 54357260333834535640 610660720430460490* When maximum circuit length is listed in.

6 Black type, the value is for applications with a 40 F maintain red type, the value is for applications with a 110 F maintainXL-TRACE2 / 5 THERMAL MANAGEMENTR aychem-DS-H51349-XLTracePipeFreezeProtec tionCOM-EN-1707 MAXIMUM CIRCUIT LENGTH IN METERS4 C / 43 C Maintain* Start-up temperature ( C)CB size (A)5XL18XL15XL28XL212XL2120 V120 V208 V240 V277 V208 V240 V277 V208 V240 V277 V 29 C153123535456404244343536204131717275535 6594546483061461061081128084896869714082 61142145149106112118909295 18 C153526616264454851363738204735818385616 4674950513070521211241289196101737477408 264143149162 113 /122 119 /128 128 /1359799102 7 C154131717274535659393941205441949699707 4785152543082611411441491061111177779814 08264143149162 113 /141 119 /148 128 /156 104 /1061051084

7 C154936858689636670434446206548113115119 848893585961308264143149162 113 /127 119 /134 128 /141878991408264143149162 113 /169 119 /178 128 /188 104 /121 110 /124 116 /12810 C15 70 73 77 46 47 49(buried grease)20 93 98 103 62 63 6530 139 147 155 93 95 9840 186 195 206 124 126 13018 C15 83 87 92 52 53 54(indoors grease)20 110 116 123 69 70 7230 166 174 184 103 105 10840 186 201 220 131 140 149* When maximum circuit length is listed in.

8 Black type, the value is for applications with a 40 F maintain red type, the value is for applications with a 110 F maintainNOMINAL POWER OUTPUT ON METAL PIPES AT 120 V/208 VPipe temperature Power W/ft5XL1-CR and 5XL1-CT (120 V)5XL2-CR and 5XL2-CT (208 V)8XL1-CR and 8XL1-CT (120 V)8XL2-CR and 8XL2-CT (208 V)12XL2-CR and 12XL2-CT (208 V)50(10)30( 1)40(5)60(15)70(21)80(27)90(32)100(38)11 0(43)120(49)130(54) F( C) 10 8 14 12 6 4 2 0 XL-TRACE3 / 5 THERMAL MANAGEMENTR aychem-DS-H51349-XLTracePipeFreezeProtec tionCOM-EN-1707 BUS WIRES16 AWG nickel-plated copperBRAID/OUTER JACKETT inned-copper braid with modified polyolefin jacket (-CR) or fluoropolymer jacket (-CT).

9 DIMENSIONS5XL AND 8XL12 XLMaximum in (14 mm) in (16 mm)Maximum in (6 mm) in (6 mm)NOMINAL WEIGHT92 lb/1000 ft104 lb/1000 ftCONNECTION KITSR aychem RayClic or FTC connection kits must be used with XL-Trace heating cables. Refer to the Pipe Freeze Protection and Flow Maintenance Design Guide (H55838) for proper connection kit to the Pipe Freeze Protection and Flow Maintenance Design Guide (H55838) and the Fire Sprinkler Freeze Protections Design Guide (H58489) for specific product approval PROTECTIONTo minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed, and to comply with the requirements of Thermal Management, agency certifications, and national electrical codes, ground-fault equipment protection must be used on each heating cable branch circuit.

10 Arcing may not be stopped by conventional circuit protection. Many Raychem control and monitoring systems meet the ground-fault protection Pipe Heating Cable-w-wXL-TRACE4 / 5 THERMAL MANAGEMENTR aychem-DS-H51349-XLTracePipeFreezeProtec tionCOM-EN-1707 NORTH AMERICA Tel: + : + : + : is owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice. 1997 2017 / 5 THERMAL MANAGEMENTR aychem-DS-H51349-XLTracePipeFreezeProtec tionCOM-EN-1707