7/367 Lighting TechnologyEmergency light FittingsSeries EXLUX 6008 VCan be used in Zone 1 and Zone 2 VAs pendant orpole-mounting fittingsVFor single- andtwo-pin fluorescent lampsVWith electronic ballast andintegral emergency light unitV2-lamp version:18 W, 36 WVCentral lockingVAll-pole disconnection via N/Cswitch when opening fitting orbattery enclosureVEnclosure in polyester resin;cover in polycarbonateVMaintained emergency h or 3 hVIn non-maintained operationor non-maintained operationwith switchable emergencylight blockingVWith or without self-test functionZone 1 and Zone 2 Series EXLUX 6008 the emergency light fittings can be used forsafety light Fittings for fluorescent LampsSeries EXLUX 6008 Selection tableVersionLampBatteryEmergency light Self-testOrdering codeWeightcapacitydurationfunction Standard fitting Pole-mountingfitting[kg]with electronic ballasts, for two-pin fluorescent lamps2 x 18 W7 Ah1,5 / 3 hwith6008/522-90m7 6008/822-908710,8/13,0without6008/522-90 m8 6008/822-908810,8/13,02 x 36 W7 Ah1,5 h / 3 hwith6008/542-9mm7 6008/842-908713,5/15,7without6008/542-9m m8 6008/842-908813,5/15,7with electronic ballasts, for single-pin fluorescent lamps2 x 18 W7 Ah1,5 h / 3 hwith6008/222-90m7 6008/722-908710,8/13,0without6008/222-90 m8 6008/722-9088

7/38 7 Emergency Light Fittings for Fluorescent Lamps Series EXLUX 6008 Technical data Explosion protection with 1-pole EEx emd IIC T4 with 2-pole II 2G / Ex edms IIC T4 …

Tags:

  Light, Fitting, Fluorescent, Light fittings

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Zone 1 and Zone 2 - Mega Ex

1 7/367 Lighting TechnologyEmergency light FittingsSeries EXLUX 6008 VCan be used in Zone 1 and Zone 2 VAs pendant orpole-mounting fittingsVFor single- andtwo-pin fluorescent lampsVWith electronic ballast andintegral emergency light unitV2-lamp version:18 W, 36 WVCentral lockingVAll-pole disconnection via N/Cswitch when opening fitting orbattery enclosureVEnclosure in polyester resin;cover in polycarbonateVMaintained emergency h or 3 hVIn non-maintained operationor non-maintained operationwith switchable emergencylight blockingVWith or without self-test functionZone 1 and Zone 2 Series EXLUX 6008 the emergency light fittings can be used forsafety light Fittings for fluorescent LampsSeries EXLUX 6008 Selection tableVersionLampBatteryEmergency light Self-testOrdering codeWeightcapacitydurationfunction Standard fitting Pole-mountingfitting[kg]with electronic ballasts, for two-pin fluorescent lamps2 x 18 W7 Ah1,5 / 3 hwith6008/522-90m7 6008/822-908710,8/13,0without6008/522-90 m8 6008/822-908810,8/13,02 x 36 W7 Ah1,5 h / 3 hwith6008/542-9mm7 6008/842-908713,5/15,7without6008/542-9m m8 6008/842-908813,5/15,7with electronic ballasts, for single-pin fluorescent lamps2 x 18 W7 Ah1,5 h / 3 hwith6008/222-90m7 6008/722-908710,8/13,0without6008/222-90 m8 6008/722-908810,8/13,02 x 36 W7 Ah1,5 h / 3 hwith6008/242-9mm7 6008/742-908713,5/15,7without6008/242-9m m8 6008/742-908813,5/15,7 Add.

2 To ordering codeThrough wiringwithout6008/.. -90m7with 6-cores6008/.. -96m7 Cable entriesStandard6008/.. -9m17 Special6008/.. -9m97 Specify when orderingRemarksMaintained operation ist standard on delivery, by removing a jumper and connecting an external switch this can be changed toswitchable confirmed light fittings are supplied without tubes. These accessories must be ordered mounting fitting , 18/20 W, cable entry: only lateral entries 6008for use inZone 1and Zone 2GG7/387 Emergency light Fittings for fluorescent LampsSeries EXLUX 6008 Technical dataExplosion protectionwith 1-poleEEx emd IIC T4with 2-poleII 2G / Ex edms IIC T4 Test certificatewith 1-pin socket6008/.2. (20 W): PTB No. (40 W): PTB No. 2-pin socket6008/.5.:PTB 97 ATEX 2032other certificates: BKI (Hungary), FTZU (Czech Republic), ISSeP (Belgium),SEV (Switzerland), T V Vienna (Austria), VNIIEF (Russia)Versions2 x 18/20 W or 2 x 36/40 W, as standard or pole-mounting fitting , electronic ballastwith integral emergency light electronics in switchable maintained or non-maintainedconnectionMaterialEnclosur ePolyester, glass fibre reinforced, Colour: white, similar to RAL 9010 CoverPolycarbonateGasketPolyurethane, to foamed into coverRated voltage220 V - 10%.

3 254 V + 6%, AC (50/60 Hz)Lamps2 x 18 / 20 W, 2 x 36 / 40 WFitting efficiencybroad bowl2 x 18 / 20 W 2 x 36 / 40 W76%76%Protection classI (with internal PE terminal)Degree of protectionIP 65 / IP 67 Ambient temperatureStandard operation 20 C .. + 50 CBattery operation 5 C .. + 50 C charge 20 C .. + 50 C dischargeConnectionTerminals L1, L2, L3, N, PE, L for 2 x 6 mm2 solid; 2 x 4 mm2 flexible;L = charging phase must be connected at all timesThrough wiringFitting available with internal through wiring, 4- or 6-core (not possible for 18/20 W)Retro- fitting possible; cross section 2,5 mm2 for max. 16 entriesStandard fittingStandard:Connection side: 1 cable gland M25 x 1,5 and 1 plug M25 x 1,5;Opposite side: 1 plug M25 x 1,5 Special:M20 in plastic or metaldrilled holes options: 2 x NPT 1/2" or 1 x NPT 3/4"Pole-mounting fittingWith factory-fitted pole sleeve18/20 W: entry as for standard fitting36/40 W: cable is brought into fitting through sleeveCable entry is sealed by a gland M32 x 2, pole sleeve is retro-fitted (possible with fittings 18 / 20 W and 36 / 40 W),entry as for standard lockCentral locking using for socket spanner M8/SW13; Cover hinged for light fitting on opening Central locking device with safety interlock; switch 8080 with N/C contacts;when central lock is opened, voltage to ballast is disconnected on both poles.

4 A safety interlock in switching mechanism prevents fitting from being reconnected while coverand central lock are lampIf lamp is faulty power supply is automatically switched off by electronic ballastLight guideStandard: broad bowl, inside of light fitting painted : signal white, RAL 9003; anti-glare provision on : additional broad deep-bowl reflector (easily mounted) semi-polished technical dataas for EXLUX 6000 Continuation R7/397 Emergency light Fittings for fluorescent LampsSeries EXLUX 6008 Technical data (Continuation)Emergency light electronicsIncorporated in one enclosure with electronic ballast unitOptionsEmergency lighting electronics are available;with or without automatic self-test function;in maintained operation or maintained operation with switchable emergency lighting blockingInterference suppressionto DIN EN 55015 Test functionsSelf-test functionEXLUX 6008 is available with or without self-test function.

5 The built-in self-test functionsare activated as soon as light is connected to mains and automatically repeated aftertime has testWeekly test of emergency light function; battery and lamp faults are determinated and indicatedvia red light duration test Testing of battery capacity at intervalls of 3 months; operating of fitting in emergency lightmode for of rated operation time. If the fitting is switches off by discharge protectionbefore time has elapsed. Battery cannot be used for emergency is indicated via red indicators1 red LED and 1 green LEDincorporated in reflector; can be seen from outside through coverDisplaysLEDI ndicationFunctionOnCharging current flowing; everything okflashingEmergency light duration test runninggreen1 : 1twinklingAutomatic function test running1 : 10 OnRechargeable battery capacity insufficient;Battery replacement necessaryredflashingBattery discharged; not operational1 : 1twinklingBattery defective1 : 10 Maintained operationWhen delivered the light fitting is wired for maintained operation.

6 By removing the bridge betweenor maintained operation with terminals 1 and 2 and connecting external switch F, the fitting is converted to maintained operationswitchable emergency lighting with switchable emergency lightingMaintained operationOn failure of supply to general lighting, fitting is supplied from the battery;(Function)irrespective of the light switch operationOn failure of power supply to tgeneral lighting, fitting switches to emergencywith switchable emergency lighting operation only if external switch F is closed. To switch emergency lighting centrallylightingto ready or not-ready , depending on plant operation external switch has a potential-free NO chargingCurrent-regulated constant current charging,duration 20 h, then changeover to trickle chargingExhaustive dischargeat UBatt = 1 V/cell (3 V);protectionthe emergency light electronics automatically switches light off (DIN VDE 0108)Emergency light operatingBattery capacityEmergency light operation timeperiod7 Ah1,5 h / 3 hChangeover voltagefrom mainsto battery operationat U < 0,6 x UNfrom batteryto mains operationat U > 0,9 x UNMaintained operation withswitchable emergency lightingTerminals emergencylighting electronicsTerminals emergencylighting electronicsBridgeMaintained operationZ2803KZ2804 KExternalswitch F7/407 Emergency light Fittings for fluorescent LampsSeries EXLUX 6008 Technical data (Continuation)

7 Emergency light electronicsContinuationLighting power on emergency operationEmergency lightEmergency light poweroperation time18/20 W 36/40 W1,5 h90%45%3 h45%25%Battery setbuilt at light fitting in a separate battery enclosureTypeNiCd battery, gas tightCapacity7 AhOperating voltage6 VChanging battery setWhen the central lock is opened the battery set is de-energized; it can be removedfrom the housing by unplugging its removable (in mm)M1015 KDimensionsLight fitting18/20 W36/40 WL8061416 Emergency light fitting EXLUX 6008, EXLUX 6408 Pole-mounting fittingEmergency light fitting EXLUX 6008, EXLUX 6408 Standard fittingDimensionsLight fitting18/20 W36/40 WL17821392L2 1)400800L3 2)312 .. 465670 .. 8651) fixed mounting distance2) variable mounting distanceM1224K7/417 Emergency light Fittings for fluorescent LampsSeries EXLUX 6008 Accessories and spare partsDesignationIllustrationDescriptionO rdering codeWeight[kg] fluorescent tubeSingle-pin socketx 38 mm Colour of light : whiteTL-X 20 W/33 1000 lm512 602 00,16TL-X 40 W/33 2350 lm512 603 00,30 Two-pin socketx 26 mm Colour of light : whiteL 18 W/251100 lm461 722 00,10L 36 W/252600 lm461 721 00,20 Wall-mountingfor pole-mounting fitting .

8 461 717 02,30bracketwith conduit length 400 mm, x 42 mmPlastic coverfor light fitting18/20 W60 000 27 05 01,2036/40 W60 000 28 05 02,1258/65 W60 000 29 05 02,70 Pole-mountingfor retro- fitting to lights 18/20 W and 36/40 W,60 008 01 75 02,20sleevecomplete with mounting accessoriesSwitchfor light fitting (2 piece)80 800 06 60 00,025 Switch element 8080/1-3-L 2 NOfor battery set80 820 02 01 00,025 Switch element 8082/1-2-00 1 NCFuseto protect battery circuit6,3 A85 600 19 01 00,035 Mounting kitEmergency light fittingfor through wiringL + L1 + L2 + L3 + N + PE DV6 36 W/40 W60 088 04 87 00,3(6 x 2,5 mm2; max. 16 A)Reflectorsfor retro- fitting , broad deep-bowlfor two lamp fittings18 W/20 W60 009 07 58 00,1236 W/40 W60 009 08 58 00,2658 W/65 W60 009 09 58 00,32 Socket spannerfor use with central lock81 980 05 40 00,13M8/SW 13 Adapter platesfor earth continuity1 x M20 x 1,560 008 15 55 00,07when using metal glands1 x M25 x 1,560 008 16 55 00,071 x NPT 1/2"60 008 17 55 00,071 x NPT 3/4"60 008 18 55 00,072 x M20 x 1,560 008 19 55 00,062 x M25 x 1,560 008 20 55 00,062 x NPT 1/2"60 008 21 55 00,06 Battery set7 Ah Battery capacity60 448 05 74 01,15 Mounting material see EXLUX 6000, page 7/16S0083PS0099PS0613PS0482PS0653PS0799P S0884PS0656PS0478aPSZ03S0902PS0672P