Are you in compliance with the new 2017 NEC …

Are you in compliance with the new 2017 NEC SCCR requirements ?What has changed?The 2017 National Electrical CodeT (NEC) requires marking the available fault current for more equipment within the power distribution system than previously mandated. At the location where the equipment is installed, the available short-circuit current A must be marked/documented and dated. These markings now need to be applied to equipment such as industrial control panels, HVAC, elevator control panels, motor control centers and industrial is affected?How are they affected?Inspectors and approversEasier to confirm proper short-circuit current rating (SCCR) protectionContractors and installersWill likely need to label the available fault current on the equipment being installedEquipment manufacturersMust be made aware of the available fault currentEnd usersMust comply with NEC by

Are you in compliance with the new 2017 NEC SCCR requirements? What has changed? The 2017 National Electrical CodeT (NEC) …

Tags:

  With, 2017, Requirements, Compliance, Crsc, Compliance with the new 2017 nec sccr requirements, Compliance with the new 2017 nec

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Are you in compliance with the new 2017 NEC …

1 Are you in compliance with the new 2017 NEC SCCR requirements ?What has changed?The 2017 National Electrical CodeT (NEC) requires marking the available fault current for more equipment within the power distribution system than previously mandated. At the location where the equipment is installed, the available short-circuit current A must be marked/documented and dated. These markings now need to be applied to equipment such as industrial control panels, HVAC, elevator control panels, motor control centers and industrial is affected?How are they affected?Inspectors and approversEasier to confirm proper short-circuit current rating (SCCR)

2 ProtectionContractors and installersWill likely need to label the available fault current on the equipment being installedEquipment manufacturersMust be made aware of the available fault currentEnd usersMust comply with NEC by ensuring all equipment is marked with the available fault current and the equipment SCCR is equal to or greater than the available fault currentNew label showing available fault current at the compressor is to be applied by the elevator control panel has an SCCR rating of 5 kA. Under the 2017 NEC, the equipment SCCR must be equal to or greater than the available fault current.

3 Because the available fault current is 65 kA, this panel is not compliant under the new The available short-circuit current (also known as available fault current) is the amount of current that is available during a short-circuit event and is unique to the installed equipment s Company CompressorSerial No: 1234567 123 Main St, City, ST 01234 Volts 480/277 Model: XZY123 Phase 3 Frequency 60Hz FLA 124 Max HP 50 UL SCCR SYM: 65 kA WHEN FED BY 200 AMP CLASS J ABC Company Elevator controlSerial No: 1234567 123 Main St, City, ST 01234 Volts 480/277 Model: XZY123 Phase 3 Frequency 60Hz FLA 124 Max HP 50 UL SCCR SYM: 5 kA Project Name:Fault Name:System:Avail.

4 Fault Current L-L-L (Amps):Voltage L-L (Volts):Calculation Performed On:Brazing LineX2 Three-Phase65,000480 Oct 24, 2016 Calculation performed via the Eaton Available Fault Current Calculator faultcurrent calculator2 Project Name:Fault Name:System:Avail. Fault Current L-L-L (Amps):Voltage L-L (Volts):Calculation Performed On:Brazing LineX2 Three-Phase65,000480 Oct 24, 2016 Calculation performed via the Eaton Available Fault Current Calculator faultcurrent calculator2 New label showing available fault current at the elevator control panel is to be applied by the drives and enclosed control2017 NEC SCCR changesEaton is a registered other trademarks are property of their respective Eaton BoulevardCleveland, OH 44122 United 2017 EatonAll Rights ReservedPrinted in USAP ublication No.

5 PA040022EN / Z19028 January 2017 Eaton enclosed drives and enclosed control provide SCCR protection levels up to 100 kA to ensure system compliance with the 2017 NECC omponent typeEaton solutionMaximum kA rating with fuseMaximum kA rating with breakerEnclosed variable frequency drivesLow harmonic drives100100 Industrial drives100100 HVAC drives100100 Enclosed controlNEMAT starter100100 IEC starter100100 Enclosed soft startersSoft starter100100 Eaton provides tools for analysis, component selection and calculationEasily calculateQuickly findValidate and sustainFC2 Available Fault Current CalculatorEasily calculates available fault current anytime, anywhereOur FC2 mobile and web-based app quickly delivers fault current calculations in the palm of your hand.

6 The program: Calculates both single- and three-phase system fault current levels Generates NEC compliant labels, one-line diagrams and documents Features fuse sizing guide for main, feeder and branch circuitsFC2 considers transformer size, conductors and conduit in calculating the fault current. For more information, visit and search for FC2 .SCCR Protection SuiteQuickly finds components with the SCCRs you needWith just a few simple selections from drop-down lists, you can easily find all the available Eaton components and their respective SCCRs based on your system needs.

7 You can reduce the number of results by setting various component preferences. SCCR Protection Suite also allows the application of an upstream current limiting device to determine if the branch circuit SCCR can be raised. To access SCCR Protection Suite, go to and documents assembly SCCR for a control panelEaton s OSCAR software allows you to enter a one-line diagram of a control panel circuit, identify the components in that circuit and calculate the SCCR for the entire assembly. OSCAR contains over 60,000 part numbers and thousands of component SCCRs. The program also applies current limiting rules per ULT 508A that permit the SCCR of branch circuits to be raised.

8 What s more, you can view, print and save SCCR analysis reports. For more information, please go to us on social media to get the latest product and support information.