Example: dental hygienist

B9512G Control Panels - Bosch Security

Intrusion Alarm Systems | B9512G Control PanelsB9512G Control Panels uFully integrated intrusion, fire, and access controlallows users to interface with one system instead ofthreeuProvides up to 599 points using a combination ofhardwired or wireless devices for installationflexibility, and up to 32 areas and 32 doors for up to2,000 usersuOn-board Ethernet port for Conettix IP alarmcommunication and remote programming,compatible with modern IP networks including IPv6/IPv4, Auto-IP, and Universal Plug and PlayuInstaller-friendly features for simple installation andcommunications, including plug-in PSTN and cellularcommunication modulesuRemote Security Control app which allows users tocontrol their Security systems - and view systemcameras - remotely from mobile devices such asphones and tabletsThe B9512G Control Panel and the B8512G ControlPanel are the new premier commercial Control panelsfrom Bosch .

Intrusion Alarm Systems | B9512G Control Panels B9512G Control Panels www.boschsecurity.com u Fully integrated intrusion, fire, and access control allows users to interface with one system instead of three u Provides up to 599 points using a combination of hardwired or wireless devices for installation

Tags:

  Control, Panels, B9512g control panels, B9512g, B9512g control panels b9512g control panels

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of B9512G Control Panels - Bosch Security

1 Intrusion Alarm Systems | B9512G Control PanelsB9512G Control Panels uFully integrated intrusion, fire, and access controlallows users to interface with one system instead ofthreeuProvides up to 599 points using a combination ofhardwired or wireless devices for installationflexibility, and up to 32 areas and 32 doors for up to2,000 usersuOn-board Ethernet port for Conettix IP alarmcommunication and remote programming,compatible with modern IP networks including IPv6/IPv4, Auto-IP, and Universal Plug and PlayuInstaller-friendly features for simple installation andcommunications, including plug-in PSTN and cellularcommunication modulesuRemote Security Control app which allows users tocontrol their Security systems - and view systemcameras - remotely from mobile devices such asphones and tabletsThe B9512G Control Panel and the B8512G ControlPanel are the new premier commercial Control panelsfrom Bosch .

2 B9512G Control Panels integrateintrusion, fire, and access Control providing one simpleuser interface for all the ability to adapt to large and smallapplications, the B9512G provides up to 599individually identified points that can be split into Control panel can communicate through its built-inEthernet port (not applicable to E Control Panels ), orthrough compatible plug-in modules that can sendevents over the public switched telephone network(PSTN) or over cellular network users, programmable keypad shortcuts, situationsensitive on-screen help, and a bilingual user interfacemake system operation simple and the B9512G Control Panel, you can: Monitor alarm points for intruder, gas, or fire alarms. Program all system functions local or remote usingRemote Programming Software (RPS) or the InstallerServices Portal programming tool (available inEurope, Middle East, Africa, and China) or by usingbasic programming through the keypad.

3 Add up to 32 doors of access Control using theoptional B901 Access Control Module. Optionally usethe D9210C Access Control Interface Module for upto eight of the 32 B9512G is a direct replacement for previouscontrol panel models D9412GV4, D9412GV3,D9412GV2, and outputs Four alarm-output patterns Programmable bell testPoint response Selectable point response time Selectable EOL values and configuration Cross point capability Fire alarm verification Dangerous gas indicator includes carbon monoxide(NFPA 720) Watch mode 63 point profilesUser interface Supervision of up to 32 keypads Custom keypad text is fully programmable throughRPS or the Installer Services Portal programming tool(available in Europe, Middle East, Africa, and China)

4 Full function menu including customizable shortcuts Authority by area and 32 character name for eachuser 14 custom authority levels to restrict system featuresthat each user can access Programmable primary and secondary language byuser and keypad 9 available languagesUser interface languagesThe following table shows the available languages perkeypad type. B915/B915IB920B921CB930B942/B942 WEnglish Chinese French Greek Hungarian Italian Polish Portuguese Spanish Area configurationsLink multiple areas to a shared area such as a lobby orcommon entryway. The shared area then automaticallyturns On (arms) when all associate areas are armedand turns Off (disarms) when any one associate areais disarmed.

5 For higher Security applications, the AreaRe-Arm feature guarantees that areas are alwaysrearmed, and are disarmed for no longer than aspecific, configurable, amount of time (for example,service time).Custom functionsFor added convenience, the installer can programcustom functions that allow customers to completecomplex tasks with one simple action. For example, acustom function can bypass a group of points and armthe system, allowing the user to perform thesefunctions with one easy command. Users can activatecustom functions with a keypad, keyfob, token, orcard, or the Control panel can activate a function inreaction to a faulted point, or automatically through ascheduled event (SKED).Passcode Security Two-man rule.

6 Requires two people with two uniquepasscodes to be present at the time of opening. Early ambush. Allows users to verify that the facility issafe by requiring two passcodes. The Control panelsends a duress event if the user does not enter thepasscode a second time after inspecting thepremises. Dual authentication. Requires two forms ofidentification before processing certain systemcommands, including turning off the system andopening doors. A standard system user must have apasscode, a credential (token or card), andappropriate command authority controlUsing the B901 Access Control Module or D9210 CAccess Control Interface Module, the Control panelprovides a fully supervised access Control solution offers 14 programmable levels of accessauthority.

7 Authority for door access is controlled bythe user level, the group of the user, the time of day,the door state, and the area armed (On/Off) exit controlThe Control panel changes from one On (armed) stateto another without turning off (disarming) the example, if you change the state from Part On(Perimeter Arm) to All On (Master Arm), the controlpanel complies and reports the change. Easy exitcontrol reduces the number of keystrokes, simplifyingsystem passcode-controlled menu listPasscode-controlled shortcuts provide users only withthe options and information pertinent to them,simplifying system controlThe system provides the flexibility to choose addedconvenience or high Security . For example, you canrestrict to a keypad's immediate local area turning on(arming) and turning off (disarming) the system with apasscode, even if the user has access to other is particularly useful for high Security areas,where a user may have access to the area, but wouldprefer to only turn off (disarm) the area individuallyrather than with the rest of the Delay/Delayed ResponseCreate a special point profile that delays the reactionof a point for a specified time (up to 1 hour in minutesand seconds).

8 This delay provides time for thespecified condition to reset before activating anyannunciation. The system can annunciate locally andsend a report, if desired. When the system is armed,the point can respond like a normal point - providing2 | B9512G Control Panelsdual functionality. Use this feature to ensure thatperimeter doors have not been propped open, or tomonitor critical areas such as computer rooms andsafes, for usersThe system supports up to 2,000 users. Each user canhave a personalized passcode, a wireless keyfob, andan access credential to Control the system. You canassign passcodes to one of 14 customized authoritylevels in each area that can be restricted to operateonly during certain times. You can program a primaryand secondary language for each user and by keypad(select from English, Chinese, French, Greek,Hungarian, Italian, Polish, Portuguese, and Spanish).

9 The keypad changes to the user s programmedlanguage when the user enters his passcode or holdsthe Help formatsThe Control panel prioritizes and sends reports to fourroute groups. Network and phone communications canuse either Modem4 or Contact ID communicationformat. Each group has a programmable primary andbackup Control panel provides flexible communications formost central stations with reporting capabilities suchas: Individual point numbers Opening or closing reports by user and area number Remote programming attempts Diagnostic reportsNoticeFor premises equipment used in thecommunication path, such as routers, use only ULlisted communicationThe Control panel can use IP to communicate with aConettix D6600 or a Conettix D6100 IPv6 Communications Receiver/Gateway.

10 Use one of thefollowing for IP: The on-board Ethernet connection (not applicable to E Control Panels ) Ethernet Communication Module: B426 Plug-in cellular communicator: B442/B443/B444 Conettix IP communication provides a secure path thatincludes anti-replay/anti-substitution features, andenhanced Security with up to AES 256-bit encryption(using Cipher Block Chaining (CBC)).The Control panel supports Domain Name System(DNS) for both remote programming and centralstation communication. DNS provides ease of use,eliminating the need to use static IP addresses as yourreporting destination, and accommodates a simplesolution for central station disaster recovery. Thecontrol panel supports both IPv6 and IPv4 pathsThe Control panel accommodates up to four separatephone and four separate network paths to the centralstation receiver.