CHAPTER 8 INTERIOR FINISHES - eCodes

CHAPTER 8 INTERIOR FINISHESSECTION of this CHAPTER shall govern the use ofmaterials used asinterior FINISHES ,trimanddecorative INTERIOR wall and ceiling provisions of Sec-tion 803 shall limit the allowable fire performance and smokedevelopment ofinterior wall and ceiling finishmaterials basedon occupancy INTERIOR floor provisions of Section 804shall limit the allowable fire performance ofinterior floor fin-ishmaterials based on occupancy classification.[F] Decorative materials and materi-alsandtrimshall be restricted by combustibility and the flamepropagation performance criteria of NFPA 701, in accordancewith Section buildings in flood hazard areas asestablished in Section , INTERIOR FINISHES ,trimanddeco-rative materialsbelow the design flood elevation shall beflood-damage-resistant materials shall be permittedto be used as finish for walls, ceilings, floors and other interiorsurfaces of windows in the exterior walls of thefirststoryabove grade shall be permitted to be of wood or ofunprotected metal Foam plastics shall not be used asinte-rior finishexcept as provided in Section Foam plasticsshall not be used as interiortrimexcept as provided in

CHAPTER 8 INTERIOR FINISHES SECTION 801 GENERAL 801.1Scope.Provisions of this chapter shall govern the use of materials used as interior finishes, trim and decorative materi- als. 801.2Interiorwallandceilingfinish.

Tags:

  Chapter, Finishes, Interior, Chapter 8 interior finishes, Interior finishes

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of CHAPTER 8 INTERIOR FINISHES - eCodes

1 CHAPTER 8 INTERIOR FINISHESSECTION of this CHAPTER shall govern the use ofmaterials used asinterior FINISHES ,trimanddecorative INTERIOR wall and ceiling provisions of Sec-tion 803 shall limit the allowable fire performance and smokedevelopment ofinterior wall and ceiling finishmaterials basedon occupancy INTERIOR floor provisions of Section 804shall limit the allowable fire performance ofinterior floor fin-ishmaterials based on occupancy classification.[F] Decorative materials and materi-alsandtrimshall be restricted by combustibility and the flamepropagation performance criteria of NFPA 701, in accordancewith Section buildings in flood hazard areas asestablished in Section , INTERIOR FINISHES ,trimanddeco-rative materialsbelow the design flood elevation shall beflood-damage-resistant materials shall be permittedto be used as finish for walls, ceilings.

2 Floors and other interiorsurfaces of windows in the exterior walls of thefirststoryabove grade shall be permitted to be of wood or ofunprotected metal Foam plastics shall not be used asinte-rior finishexcept as provided in Section Foam plasticsshall not be used as interiortrimexcept as provided in or This section shall apply both to exposed foamplastics and to foam plastics used in conjunction with a textileor vinyl facing or following words and terms shall, for thepurposes of this CHAPTER and as used elsewhere in this code,have the meanings shown VINYL WALL coveringconsisting of a woven textile backing, an expanded vinyl basecoat layer and a nonexpanded vinyl skin coat. The expandedbase coat layer is a homogeneous vinyl layer that contains ablowing agent. During processing, the blowing agent decom-poses, causing this layer to expand by forming closed cells.

3 Thetotal thickness of the wall covering is approximately inchto inch ( mm to mm).FLAME propagation of flame over a SPREAD comparative measure,expressed as a dimensionless number, derived from visualmeasurements of the spread of flame versus time for a materialtested in accordance with ASTM E 84 or UL finishincludesinterior walland ceiling finishandinterior floor FLOOR exposed floor surfaces ofbuildings including coverings applied over a finished floor orstair, including risers.[F] INTERIOR FLOOR-WALL floor finishtrim used to provide a functional and/or decorative border at theintersection of walls and WALL AND CEILING exposedinterior surfaces of buildings, including but not limited to:fixed or movable walls and partitions; toilet room privacy parti-tions; columns; ceilings.

4 And INTERIOR wainscoting, paneling orother finish applied structurally or for decoration, acousticalcorrection, surface insulation, structural fire resistance or simi-lar purposes, but not including STRETCH system, fab-ricated on site and intended for acoustical, tackable or aestheticpurposes, that is comprised of three elements: (a) a frame (con-structed of plastic, wood, metal or other material) used to holdfabric in place, (b) a core material (infill, with the correct prop-erties for the application), and (c) an outside layer, comprisedof a textile, fabric or vinyl, that is stretched taunt and held inplace by tension or mechanical fasteners via the comparative measure,expressed as a dimensionless number, derived from measure-ments of smoke obscuration versus time for a material tested inaccordance with ASTM E molds, chair rails, baseboards, handrails, doorand window frames and similar decorative or protective mate-rials used in fixed 803 WALL AND CEILING wall and ceiling finishmaterials shallbe classified for fire performance and smoke development inaccordance with Section or.

5 Except as shown inSections through Materials tested in accordancewith Section shall not be required to be tested in accor-dance with Section INTERIOR wall and ceiling finish and ceiling finish materials shall be classified in accor-dance with ASTM E 84 or UL 723. Suchinterior finishmaterials shall be grouped in the following classes in accor-dance with their flame spread A: Flame spread index 0-25; smoke-developedindex OREGON STRUCTURAL SPECIALTY CODE181 1M:\data\CODES\STATE CODES\Oregon\2010\Structural Specialty_Building\Final VP\ , January 08, 2010 12:10:29 PMColor profile: Generic CMYK printer profileComposite Default screenClass B: Flame spread index 26-75; smoke-developedindex C: Flame spread index 76-200; smoke-devel-oped index :Materials tested in accordance with Sec-tion Room corner test for INTERIOR wall or ceiling fin-ish wall or ceiling finishmaterials shallbe permitted to be tested in accordance with NFPA wall or ceiling finish materials tested in accordancewith NFPA 286 shall comply with Section Acceptance criteria for NFPA 40 kW exposure, theinterior finishshall comply withItem 1.

6 During the 160 kW exposure, theinterior finishshall comply with Item 2. During the entire test, theinte-rior finishshall comply with Items 3 and During the 40kW exposure, flames shall notspread to the During the 160 kW exposure, theinterior finishshall comply with the Flame shall not spread to the outer extrem-ity of the sample on any wall or Flashover, as defined in NFPA 286, shallnot The peak rate of heat release throughout the NFPA286 test shall not exceed 800 The total smoke released throughout the NFPA286 test shall not exceed 1,000 Room corner test for textile wall coverings andexpanded vinyl wall wall coverings andexpanded vinyl wall coverings shall meet the criteria of Sec-tion when tested in the manner intended for use inaccordance with the Method B protocol of NFPA 265 usingthe product-mounting system.

7 Including Acceptance criteria for NFPA 40 kW exposure theinterior finishshall comply withItem 1. During the 150 kW exposure, theinterior finishshall comply with Item 2. During the entire test, theinte-rior finishshall comply with Item During the 40 kW exposure, flames shall notspread to the During the 150 kW exposure, theinterior finishshall comply with the Flame shall not spread to the outer extremi-ties of the samples on the 8-foot by 12-foot(203 mm by 305 mm) Flashover, as described in NFPA 265, shallnot The total smoke released throughout the NFPA265 test shall not exceed 1,000 Acceptance criteria for textile and expandedvinyl wall or ceiling coverings tested to ASTM E 84 orUL wall and ceiling coverings and expandedvinyl wall and ceiling coverings shall have a Class A flamespread index in accordance with ASTM E 84 or UL 723 andbe protected by anautomatic sprinkler systeminstalled inaccordance with Section or Test speci-men preparation and mounting shall be in accordance withASTM E Thickness having a thickness lessthan inch ( mm)

8 Applied directly to the surface ofwalls or ceilings shall not be required to be Heavy timber portions of struc-tural members complying with the requirements for buildingsof Type IV construction in Section shall not be subject tointerior Foam plastics shall not be used asinte-rior finishexcept as provided in Section This sectionshall apply both to exposed foam plastics and to foam plasticsused in conjunction with a textile or vinyl facing or Textile wall used as INTERIOR wall fin-ish materials, textile wall coverings, including materials havingwoven or nonwoven, napped, tufted, looped or similar surfaceand carpet and similar textile materials, shall be tested in themanner intended for use, using the product mounting system,including adhesive, and shall comply with the requirements ofSection , or Textile ceiling used as INTERIOR ceilingfinish materials, textile ceiling coverings, including materialshaving woven or nonwoven, napped, tufted, looped or similarsurface and carpet and similar textile materials, shall be testedin the manner intended for use, using the product mountingsystem, including adhesive, and shall comply with the require-ments of Section or Expanded vinyl wall used as interiorwall finish materials, expanded vinyl wall coverings shall betested in the manner intended for use, using the product mount-ing system, including adhesive, and shall comply with therequirements of Section , or Expanded vinyl ceiling used as inte-rior ceiling finish materials.

9 Expanded vinyl ceiling coveringsshall be tested in the manner intended for use, using the productmounting system, including adhesive, and shall comply withthe requirements of Section or INTERIOR finish requirements based on and ceiling finishshall have a flame spread index notgreater than that specified in Table for the group andlocation wall and ceiling finishmaterialstested in accordance with NFPA 286 and meeting the accep-tance criteria of Section , shall be permitted to be usedwhere a Class A classification in accordance with ASTM E 84or UL 723 is finishmaterials regulated by thischapter shall be applied or otherwise fastened in such a mannerthat such materials will not readily become detached wheresubjected to room temperatures of 200 F (93 C) for not lessthan 30 OREGON STRUCTURAL SPECIALTY CODEINTERIOR FINISHES 2M:\data\CODES\STATE CODES\Oregon\2010\Structural Specialty_Building\Final VP\ , January 08, 2010 12:10:29 PMColor profile.

10 Generic CMYK printer profileComposite Default Application of INTERIOR finish materials to fire-resis-tance-rated structural finishmate-rials are applied on walls, ceilings or structural elementsrequired to have afire-resistance ratingor to be ofnoncombustible construction, they shall comply with the pro-visions of this Direct attachment and furred walls and ceilings are required by any provision inthis code to be of fire-resistance-rated or noncombustibleconstruction, theinterior finishmaterial shall be applieddirectly against such construction or to furring strips notexceeding 13/4inches (44 mm) applied directly against suchsurfaces. The intervening spaces between such furringstrips shall comply with one of the following:1. Be filled with material that is inorganic or non-combustible;2.