Example: quiz answers

DCG INSTALLATION INSTRUCTION - johnsonsupply.com

SUNLINE 2000 . GAS / ELECTRIC. SINGLE PACKAGE AIR CONDITIONERS. INSTALLATION INSTRUCTION Supersedes: (295) (1096). MODELS D7CG 036, 048 & 060 (10 SEER) 035-14838. MODEL D2CG 072 (9 EER). (STYLE A & Belt Drive Option). CAUTION FOR YOUR SAFETY. SCROLL COMPRESSORS. OPERATE IN ONLY ONE. Do not store or use gasoline or DIRECTION. other flammable vapors or liquids If the compressor is in the vicinity of this or any other experiencing: appliance. - low amperage draw If you smell gas: - similar discharge and suction pressure 1. Open windows - increased noise level 2.

GENERAL YORK Model DCG units are single package air conditioners with gas heat designed for outdoor installation on a roof top or a slab. The units are completely assembled on rigid, permanently

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of DCG INSTALLATION INSTRUCTION - johnsonsupply.com

1 SUNLINE 2000 . GAS / ELECTRIC. SINGLE PACKAGE AIR CONDITIONERS. INSTALLATION INSTRUCTION Supersedes: (295) (1096). MODELS D7CG 036, 048 & 060 (10 SEER) 035-14838. MODEL D2CG 072 (9 EER). (STYLE A & Belt Drive Option). CAUTION FOR YOUR SAFETY. SCROLL COMPRESSORS. OPERATE IN ONLY ONE. Do not store or use gasoline or DIRECTION. other flammable vapors or liquids If the compressor is in the vicinity of this or any other experiencing: appliance. - low amperage draw If you smell gas: - similar discharge and suction pressure 1. Open windows - increased noise level 2.

2 Don't touch electrical switches. It is operating in reverse. 3. Extinguish any open flame. Switch two line voltage connections to correct. 4. Immediately call your gas supplier. GENERAL. YORK Model DCG units are single package air conditioners -Motorized Outdoor Air Damper Accy. with gas heat designed for outdoor INSTALLATION on a roof top or -Coil Guard a slab. -Low NOx Accessory The units are completely assembled on rigid, permanently -High Altitude Accy. (Natural Gas). attached base rails. All piping, refrigerant charge, and electrical -High Altitude Accy.

3 (Propane). wiring is factory-installed and tested. The units require only electric power, gas piping and duct connections at the point of INSTALLATION . -Gas Piping Accessory The gas-fired heaters have aluminized steel tubular heat -Propane Conversion Accessor exchangers and spark ignition with intermittent pilot. -Low Ambient Accessory This appliance is not to be used for temporary heating of Renewal Parts: buildings or structures under construction. Refer to Parts Manual for complete listing of replacement INSPECTION parts on this equipment.

4 As soon as a unit is received, it should be inspected for possible All forms referenced in this INSTRUCTION may be ordered from: damage during transit. If damage is evident, the extent of the damage should be noted on the carrier's freight bill. A separate Publications Distribution Center request for inspection by the carrier's agent should be made in Unitary Products Group writing. Refer to Form for additional information. Box 1592, York, PA 17405. REFERENCE APPROVALS. Additional information on the design, INSTALLATION , operation and Design certified by CGA and UL listed as follows: service of this equipment is available in the following reference forms: -General INSTALLATION 1.

5 For use as a forced air furnace with cooling unit. 2. For outdoor INSTALLATION only. -Pre-start & Post-start Check List 3. For INSTALLATION directly on combustible flooring or, in the , -Economizer Accessory on wood flooring or Class A, B, or C roof covering material. -Man. Outdoor Air Damper Accy 0-35% 4. For use with natural gas and/or propane (LP) gas. -Man. Outdoor Air Damper Accy 0-100%. Not suitable for use with conventional venting systems. Installer should pay particular attention to the words: NOTE, CAUTION and WARNING. Notes are intended to clarify or make the INSTALLATION easier.

6 Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury and/or equipment damage may result if INSTALLATION procedure is not handled properly. CAUTION. THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE WITH THE ENCLOSED INSTALLATION INSTRUCTIONS. AND ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES INCLUDING, BUT NOT LIMITED TO, BUILDING, ELECTRI- CAL, AND MECHANICAL CODES. WARNING. INCORRECT INSTALLATION MAY CREATE A CONDITION WHERE THE OPERATION OF THE PRODUCT COULD CAUSE. PERSONAL INJURY, PROPERTY DAMAGE AND/OR DEATH.

7 WARNING. DE-ENERGIZE THE ELECTRICAL POWER AND TURN OFF THE GAS SUPPLY TO THE UNIT BEFORE ATTEMPTING TO. INSPECT, REPAIR OR PERFORM MAINTENANCE TO THE UNIT. TABLE OF CONTENTS. General .. 1 MAINTENANCE & TROUBLE SHOOTING. 1 Normal 19. Reference .. 1 Cleaning Flue Passages and Heating Elements .. 19. Approvals .. 1 Troubleshooting ..19 & 20. 2. TABLES. INSTALLATION . No. Description Page Limitations .. 3 1 Unit Application Data .. 3. Location .. 3 2 Gas Heat Application 4. Rigging and Handling .. 3 3 Pipe Sizing .. 5. 3 4 Static Resistances.

8 8. Ductwork .. 3 5 Physical 9. Filters .. 4 6 Supply Air Blower Perf. 3 - 6 Ton Direct-Drive 9. Condensate Drain .. 4 7 Motor & Drive Data-Belt-Drive Blower .. 9. Service 4 8 Supply Air Blower Perf. 3 & 4 Ton Belt-Drive 10. 4 9 Supply Air Blower Perf. 5 & 6 Ton Belt-Drive 11. Power and Control 4 10 Electrical Data 12. Blower Speed 4 11 Electrical Data 12. Scroll 4 12 Superheat, 036 .. 12. Combustion Discharge .. 4 13 Superheat, 048 .. 13. Disconnect Switch Bracket For Optional Belt-Drive .. 5 14 Superheat, 060 .. 13. Gas Piping .. 5 15 Superheat, 072.

9 13. Gas Connection .. 6 16 Limit Control Setting .. 16. Units, Tanks and Piping .. 6 17 Belt Drive Supply Air Motor Pulley 17. Low NOx 6 18 Gas Rate - Cubic Feet Per Hour .. 18. Vent and Combustion Air 7. Optional Economizer Rain Hood ..7 & 8. OPERATION FIGURES. Cooling 15 No. Description Page Cooling Sequence of 15 1 Recommended Drain 4. Safety Controls (Cooling).. 15 2 Typical Field 5. Heating Sequence of Operation .. 15 3 External Supply Connection .. 6. Safety Controls (Heating) .. 15 4 Bottom Supply Connection .. 6. Heat Anticipator Setpoints.

10 16 5 Vent and Combustion Air 7. Pre-Start Check 16 6 Economizer Rain Hood Assembly .. 7. 7 Enthalpy Setpoint 8. START-UP 8 Center of 9. Operating 16 9 Dimensions and 14. Post-Start Check List (Gas) .. 16 10 Gas Valve 15. Manifold Gas Pressure Adjustment .. 16 11 Gas 16. Pilot 17 12 Proper Flame Adjustment .. 17. Burner 17 13 Typical Flame Appearance .. 17. Burner Air Shutter Adjustment .. 17 14 Belt Adjustment .. 17. Supply Air Blower and Temperature Rise Adjustment .. 17 15 Press. Drop versus Supply Air CFM .. 18. Checking Gas Input.


Related search queries