Example: bachelor of science

GENERAL SPECIFICATIONS FOR ELECTRICAL WORKS

PART-IVSUB STATIONSGENERAL SPECIFICATIONSFOR ELECTRICAL WORKSGOVERNMENT OF INDIACENTRAL PUBLIC WORKS DEPARTMENT2013 PUBLISHED UNDER THE AUTHORITY OF DIRECTOR GENERAL , CPWD, NEW DELHI All rights reserved. No part of this publication may be reproduced in any form or by any means, electronic or mechanical, including photocopy, recording or any information storage and retrieval system, without permission, in writing, from the Director GENERAL ( WORKS ), CPWD, New DelhiA GOVERNMENT OF INDIA PUBLICATIONP ublished by :DIRECTOR GENERAL ( WORKS )CPWD, NIRMAN BHAWAN, NEW DELHI-110 011&Printed & Marketed byM/s.

part-iv sub stations general specifications for electrical works government of india central public works department 2013 published under the authority

Tags:

  General, Electrical, Specification, Work, General specifications for electrical works

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of GENERAL SPECIFICATIONS FOR ELECTRICAL WORKS

1 PART-IVSUB STATIONSGENERAL SPECIFICATIONSFOR ELECTRICAL WORKSGOVERNMENT OF INDIACENTRAL PUBLIC WORKS DEPARTMENT2013 PUBLISHED UNDER THE AUTHORITY OF DIRECTOR GENERAL , CPWD, NEW DELHI All rights reserved. No part of this publication may be reproduced in any form or by any means, electronic or mechanical, including photocopy, recording or any information storage and retrieval system, without permission, in writing, from the Director GENERAL ( WORKS ), CPWD, New DelhiA GOVERNMENT OF INDIA PUBLICATIONP ublished by :DIRECTOR GENERAL ( WORKS )CPWD, NIRMAN BHAWAN, NEW DELHI-110 011&Printed & Marketed byM/s.

2 NABHI PUBLICATIONSN-101, 2nd Floor, Munshi Ram Building,Connaught Circus, New Delhi-110 001 Phone : 23354823, 43640045 Fax : 011-23416103E-mail : : at : M/s Jain Book Depot(A Nabhi Enterprise)C-4, Opposite PVR Plaza, Connaught Place, New Delhi-110001 Phone : 011-23416101/02/03 Fax : 011-23416103, Mobile : 09868913553/54/82E-mail : : Trade EnquiriesM/s. Nabhi Book AgencyGarage Municipal No. 8224, Backside of Shop No. C-4, Opp. PVR Plaza, Connaught Place, New Delhi-110001 Phone : 011-41532993, 9868913553/ 54 Website : , E-mail : leading Booksellers & Authorised Govt. DealersPrice : Rs.

3 300/- (excluding postage and forwarding charges etc.)MEMBERS OF THESPECIFICATION COMMITTEE FOR E&M WORKSSl. No. Name1 Sh. Singhal, Spl. DG (NR) Chairman2 Sh. S. Khan, CE(E) PWD Member3 Sh. Garg, CE (NDZ-VI) Member4 Sh. Pyare Lal, CE(E) BFLZ Member5 Sh. Prabhakar Singh, CE (NDZ-I) Member6 Sh. Arora, CE(E) Trg. Member7 Sh. Chawla, CE(E) PEWZ Member8 Sh. Ahuja, CE, CPM, Manesar Project Member9 Sh. Gurvinder Singh, CE (NDZ-VII) Member10 Sh. Varma, CE(E) CSQ Member11 Sh. Surendar Singh, DDG (Pers.) Member12 C T E or his representative Member13 CA (NDR), CPWD or his representative Member14 Sh.

4 Sakarwal, SE(E) DCEC-V Member15 Sh. Mittal, SE(E) LCEC Member16 Sh. Mathura Prasad, SE(TAS) CSQ Member17 Sh. Garg, SE(E)TAS, CSQ(E) Member SecretaryVIIREFERENCES OF AMENDMENTS Sl. No. Reference under which issued Chapter No. Item No. PageVIII1. Section 1 GENERAL 01 - 082. Section 2 High Voltage Panel 09 - 153. Section 3 Transformers 16 - 264. Section 4 Panels 27 - 315. Section 5 Cable WORKS 32 - 336. Section 6 Bus Trunking 34 - 387. Section 7 Earthing System 39 - 408. Section 8 Power Factor Improvement 41 - 429. Section 9 Safety Requirements 43 - 4410. Section 10 Unitised / Compact Sub-station 45 - 5111.

5 Appendix I List of Indian Standards 52 - 5512. Appendix II Model NIT (for Sub-station) 56 - 9713. Appendix III Technical Parameter of Compact Air insulated & sandwich bus trunking system. 98 - 10014. Appendix IV Tables: Area Sub-station, Genset, Rated Values of ACBs, Defl ection of Oil Tanks, Conventional Bus Trunking, and Short Circuit Rating of Cables. 101 - 10715. Appendix V Specifi cations to be watched for ACBs/MCCBs/ Compact Sub-station/ Compact Bus Trunking. 108 - 11416. Annexure I Lay out plan of Sub-station cum Fire pump house (independent building) 115 - 11517.

6 Annexure II Lay out plan of Sub-station with DG Set 116 - 11618. Annexure III Lay out plan of Sub-station; DG Set & AC Plant Room 117 - 11719. Annexure IV Location & Requirements for Sub-Station 118 - 11920. Annexure V Abstracts from IS 13947 for Switchgears 120 - 12721. Annexure VI A few Defi nitions for Switchgears 128 - 130S. No. Section No. Description Page (IX)1 SECTION SCOPE These GENERAL specifi cations cover the details of Sub Station Equipments (Transformers, HT Panels, Bus Trunkings/ Rising Mains and other related items) to be supplied, the inspection as may be necessary before dispatch, delivery at site, installations, testing, commissioning, putting into operation and handing over in working condition of the equipment for sub-stations for working voltage of 11000/433 volts.

7 The GENERAL specifi cations are subject to revision from time to time. The tender specifi cations for a particular job shall clearly indicate the applicable version of these specifi cations. (Where Licensee is supplying power at 33 KV/ KV etc. Voltages, sub-station equipments of suitable specifi cation and capacity shall be provided). These specifi cations do not cover sub-station installation in mines, quarries and installation of similar nature, having hazardous atmosphere. These however do not bind the NIT approving authority from incorporating better and new, technologically superior, products Related Documents These technical specifi cation shall be read in conjunction with the standard conditions of the contract with correction slips, as are relevant for commercial aspects, as well as schedules and drawing and requirements under these specifi cations.

8 In the event of any discrepancy between these specifi cations and inter connected documents, the technical requirements as per the contract specifi cations shall be followed and deemed to be having overriding DEFINITIONS The defi nitions of terms are in accordance with relevant Indian standards. Extra Low Voltage (ELV) : Not exceeding 50 Volts Low Voltage (LV) : Normally exceeding 50 Volts but not exceeding 250 Volts. Medium Voltage (MV) : Normally exceeding 250 V but not exceeding 650 V. High Voltage (HV) : Normally exceeding 650 V but not exceeding 33 KV.

9 Extra High Voltage (EHV) : Normally exceeding 33 KV. (Source: NBC, 2005, Part-8, Section to ) SYSTEM GENERAL A sub-station installation is a combination of a number of major equipments like Transformers, High Voltage Panel, Medium Voltage (MV) Panels, Inter-connecting Cables, Bus Ducts, Protection and Metering etc. individually engineered in each case depending upon the requirements, size and capacity of sub-station and in coordination with the licensee of the area concerned. Generally supply at 230/415 or 433 Volts subject to verifi cation for loads up to 100 KVA, 11 KV for loads up to 5 MVA and 33/ 66 KV for loads more than 5 MVA.

10 While selecting the Transformer(s) for a substation it will be desirable to provide at least one standby Transformer, so that a certain amount of redundancy is built in the system. It may also be necessary to install capacitor banks/other modern systems to improve power factor, simultaneously controlling the Harmonics, for economy consideration as well as to comply with the requirements of local utility. Metering aspects as well as protection arrangements will also depend upon the Licensee s Items of work A sub-station installation work shall generally comprise of supply, installation, testing and commissioning of the following: (a) High Voltage Panels.