Example: marketing

Two- and Four-Wire Conventional Smoke Detectors

Effective: December 2017K-70-140 Two- and Four-Wire Conventional Smoke DetectorsESL/ interlogix 700 Series ProductsSTANDARD FEATURES Two- wire and Four-Wire ConventionalPhotoelectric Smoke and Heat Detectors Advanced alarm verification feature reduceschance of nuisance alarms Automatic drift compensation Head and terminal base design (base soldseparately) Low-profile design blends into the ceiling Self-diagnostic capability continually monitorsoperation Meets NFPA 72 sensitivity test requirements Field-replaceable optical chamber Extensive two- wire compatibility listings Remote LED indicator available for 721U, 721 UTand 741UT Detectors Compatible with most Kidde, Fenwal andChemetron Conventional Control Panels(See compatibility chart in Datasheet No.)

Effective: December 2017 K-70-140 Two- and Four-Wire Conventional Smoke Detectors ESL/Interlogix 700 Series Products STANDARD FEATURES • Two-Wire and Four-Wire Conventional

Tags:

  Four, Wire, Smoke, Detectors, Conventional, Interlogix, Four wire conventional smoke detectors

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Two- and Four-Wire Conventional Smoke Detectors

1 Effective: December 2017K-70-140 Two- and Four-Wire Conventional Smoke DetectorsESL/ interlogix 700 Series ProductsSTANDARD FEATURES Two- wire and Four-Wire ConventionalPhotoelectric Smoke and Heat Detectors Advanced alarm verification feature reduceschance of nuisance alarms Automatic drift compensation Head and terminal base design (base soldseparately) Low-profile design blends into the ceiling Self-diagnostic capability continually monitorsoperation Meets NFPA 72 sensitivity test requirements Field-replaceable optical chamber Extensive two- wire compatibility listings Remote LED indicator available for 721U, 721 UTand 741UT Detectors Compatible with most Kidde, Fenwal andChemetron Conventional Control Panels(See compatibility chart in Datasheet No.)

2 K-70-100) FM Approved UL Listed CSFM ApprovedDESCRIPTIONThe ESL/ interlogix 700 Series Conventional photoelectricsmoke detector is an interchangeable head and basedetector with a light-scattering optical sensor that providesoutstanding stability and excellent response to a widerange of fires. A pulsed infrared LED light source and ahigh-speed photodiode sensing element are housed in anomnidirectional sensing chamber protected by an insectscreen. For easy cleaning, the detector features a field-replaceable optical chamber (P/N 211-10 PKG).The Model 721UT photoelectric detector includes anintegral fixed temperature and rate-of-rise heat detector.

3 A remote LED indicator is available for Models 721U,721UT, and 741UT Detectors . This functionality requiresthe Model 702U base and the 706U1B Remote LEDindicator. The ESL/ interlogix 700 Series Smoke Detectors areconventional self-diagnostic Detectors specificallydesigned for the demands of commercial and industrialenvironments. If the detector drifts out of its UL Listed sen-sitivity range or fails internal diagnostics, the alarm LEDflashes once a second to indicate a trouble condition. Thismeets NFPA 72 field sensitivity testing requirements with-out the need for external diagnostic information is activated by applying amagnet near the detector s integral reed switch.

4 This initi-ates a self-diagnostic routine and provides visual indica-tion of sensitivity level, or if service is required. Themagnet test causes the LED to blink. The number of blinkcounts corresponds to a Smoke detector sensitivity , if they become dirty over time, ESL/ interlogix 700 Series Detectors automatically adjust the alarm thresholdthrough built-in drift compensation. If the detector needs tobe cleaned, the patented field replaceable optical chambermakes cleaning quick and SPECIFICATIONSThe ESL/ interlogix 700 Series photoelectric Smoke detec-tor is a low-profile, self-diagnostic, two- wire detector thatmonitors its own sensitivity and operational status.

5 Thedetector meets NFPA 72 field sensitivity testing require-ments without the need for external meters. Built-in driftcompensation automatically adjusts the sensitivity if thedetector gets dirty. The ESL/ interlogix 700 Series photo-electric detector features an alarm verification feature tofurther reduce the chance of a nuisance alarm. Normalsensing occurs every 9 seconds. This rate doubles when asignal exceeding the alarm threshold value is sensed. Twoadditional successive signals above the threshold level ini-tiate an alarm. The optical sensing chamber is fieldreplaceable, allowing quick and easy cleaning and Fire Systems400 Main StreetAshland, MA 01721 USAPh: trademarks are the properties of their respective literature is provided for informational purposes only.

6 KIDDE-FENWAL, INC. believes this data to be accurate, but it is published and presented without any guarantee or warranty whatsoever. KIDDE-FENWAL, no responsibility for the product s suitability for a particular application. The product must be properly applied to work correctly. If you need more information on this product, or if you have a particular problem or question, contact KIDDE-FENWAL, Rev AE 2017 Kidde-Fenwal, SPECIFICATIONSORDERING - 33 VDC, non polarity sensitiveMaximum ripple (peak to peak)10% (vp - p)Typical standy current (24V)70 ATypical alarm current (24V)up to 60 mA max, if not limited by control panelPhotoelectric , + , temperature32 F to 100 F (0 C to 38 C)Operating humidity range0 to 95% Non-condensingRFI immunity20 V/m min.

7 0-1000 MHzRemote LED output current5 mA min, mA maxLED indicatorFlashes approximately every 9 seconds for Normal State, flashes once every second for Trouble State, turns on steady for AlarmDrift compensation ft, maxEnvironmentalHeat Sensor Ratings (721UT, 741UT)Fixed 135 F/Rate of rise 15 F/min, > 105 F ( C/min., > C)Maximum wind velocity300 ft/min Field wiring size12-18 AWGUL two- wire compatibility identifierS10A (711U, 721U, 721UT)Note:Refer to Kidde Fire Systems Datasheet Number K-70-100 for Smoke detector :ESL/ interlogix 700 Series Smoke Detectors and accessories are manufactured by ESL/ interlogix and re-sold by Kidde Fire Systems using original ESL/ interlogix part head and baseDetector head dimensions4 in.

8 D x in. H (10cm x )Base dimensions701U, 702U: 6 in. D x in. H ( cm x cm) Total height, (head and base) in. (5 cm) HRegulationsListingUL 268, FM, CSFM711 USmoke detector head only, photoelectric, two-wire721 USmoke detector head only, photoelectric, two- wire , output for remote LED721 UTSmoke detector head only, photoelectric, two- wire w/integral heat detector, output for remote LED741 UTSmoke detector head only, photoelectric, Four-Wire , w/integral heat detector, alarm relay ( ) output and output for remote LED701 USmoke detector base, 3 terminals, 6 in. detector base, 6 terminals, 6 in. dia.(required for use with the 706U1B Remote LED)204-12/24 VGEnd-of-Line, power supervision relay for Four-Wire applications211-10 PKGR eplacement optical chamber for Smoke Detectors , set of 1006-117883-001 Test magnet SM200-12 PKGC anned Smoke for functional testing of Smoke detectors706U1 BRemote LED indicator for 721U, 721UT and 741UT (Requires use of 702U base)