VLT® 2800 Quick Guide - Danfoss

1 Quick WarningsHigh Voltage Warning:The voltage of the frequency converter is dangerous whenever it is connected tomains. Incorrect installation of the motor or frequency converter may cause damageto the equipment, serious injury or death. Consequently, it is essential to complywith the instructions in this manual as well as local and national rules and :Touching the electrical parts may be fatal - even after the equipment has been dis-connected from make sure that other voltage inputs have been discon-nected (linkage of DC intermediate circuit). Be aware that there may be high voltageon the DC link even when the LEDs are turned off. Before touching any potentiallylive parts of the frequency converter, wait at least 4 Current:The earth leakage current from the frequency converter exceeds mA. Accordingto IEC 61800-5-1 a reinforced Protective Earth connection must be ensured bymeans of a min. 10mm Cu or an addtional PE wire - with the same cable crosssection as the Mains wiring - must be terminated increase safety, install an RCDR esidual Current Device:This product can cause a DC current in the protective conductor.

VLT 2800 Quick Guide 1 Quick Guide ... VLT 2800 frequency converters allow side-by-side inst allation on a wall in any position as the units do not require ventilation on the side. Because of the need for cooling, there must be 10 cm free air passage above and below the frequency converter.

Tags:

  Guide, Inst, Allation, Installa tion

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of VLT® 2800 Quick Guide - Danfoss

1 1 Quick WarningsHigh Voltage Warning:The voltage of the frequency converter is dangerous whenever it is connected tomains. Incorrect installation of the motor or frequency converter may cause damageto the equipment, serious injury or death. Consequently, it is essential to complywith the instructions in this manual as well as local and national rules and :Touching the electrical parts may be fatal - even after the equipment has been dis-connected from make sure that other voltage inputs have been discon-nected (linkage of DC intermediate circuit). Be aware that there may be high voltageon the DC link even when the LEDs are turned off. Before touching any potentiallylive parts of the frequency converter, wait at least 4 Current:The earth leakage current from the frequency converter exceeds mA. Accordingto IEC 61800-5-1 a reinforced Protective Earth connection must be ensured bymeans of a min. 10mm Cu or an addtional PE wire - with the same cable crosssection as the Mains wiring - must be terminated increase safety, install an RCDR esidual Current Device:This product can cause a DC current in the protective conductor.

2 Where a residualcurrent device (RCD) is used for extra protection, only an RCD of Type B (time de-layed) shall be used on the supply side of this product. See also Danfoss ApplicationNote on RCD, earthing of the frequency converter and the use of RCDs must alwaysfollow national and local Thermal Protection:Protection against Motor overload is not included in the factory setting. If this func-tion is required, set par. 128 Motor Thermal Protection to data value ETR trip or datavalue ETR warning. For the North American market: The ETR functions provideoverload protection of the motor, class 20, in accordance with in high altitudes:For altitudes above 2 km, please contact Danfoss regarding PELV. VLT 2800 Quick Guide1 Quick - VLT is a registered Danfoss trademark1 Safety Instructions The frequency converter must be disconnected from the mains if repair work is to becarried out. Check that the mains supply has been disconnected and the prescribed timehas passed before removing motor and mains plugs.

3 Make sure the frequency converter is properly connected to earth. Protect users against supply voltage. Protect the motor against overloading according to national and local regulations. The earth leakage current exceeds mA. For ELCB types, please see application The [STOP/RESET] key on the control panel of the frequency converter does not dis-connect the equipment from mains and is thus not to be used as a safety switch. Note that the frequency converter has more voltage inputs than L1, L2 and L3 when DCbus terminals are used. Check that all voltage inputs are disconnected and that the pre-scribed time has passed before repair work is commenced. Warning against unintended motor can be brought to a stop by means of digital commands, bus commands,references or a local stop, while the frequency converter is connected to mains. If per-sonal safety considerations make it necessary to ensure that no unintended start oc-curs, these stop functions are not parameters are being changed, the motor may start.

4 Consequently, the stop key[STOP/RESET] must always be activated, following which data can be motor that has been stopped may start if faults occur in the electronics of the frequencyconverter, or if a temporary overload or a fault in the supply mains or the motor con-nection ceases. Use on Isolated MainsSee section RFI Switch in the operating instructions regarding use on isolated is important to follow the recommendations regarding installation on IT-mains, since sufficientprotection of the complete installation must be observed. Not taking care using relevant moni-toring devices for IT-mains may result in Quick GuideVLT 2800 Quick - VLT is a registered Danfoss trademark1 IntroductionUse this Quick Guide to carry out Quick andEMC-correct installation of the frequency con-verter in five the safety section beforeinstalling the !The Operating Instructions, , give further examplesof installation and describe allfunctions in Design Guide , , contains extensive in-formation.

5 AbbreviationsELCBE arth Leakage Circuit BreakersNONormally openNCNormally closedPD2 Dual phase (for 2822, 2840 that only run 3-phase as standard D2), 220 - 240 VRCDR esidual Current Device Available LitteratureNB!This Quick Guide contains only the very basic information necessary for installing andrunning the more information please consult the VLT 2800 Design Guide , 2800 Quick Guide1 Quick - VLT is a registered Danfoss trademark3 1 TitleLiterature 2800 Operating 2800 Design 2800 Data Instruction for VLT 2800 Filter 2800 NEMA 1 Terminal 2800 DeviceNet 2800 Blue Star Condensing 2880 - 2882 Spare Part 2800 LCP Remote-mounting Instruction for DP 2800 DeviceNet N2 Filter Resistor RTU against Electrical = Revision Number, Y = Language codeApplication notes can be found on + Approvals Disposal InstructionEquipment containing electrical components must not be disposed oftogether with domestic must be separately collected with electrical and electronic wasteaccording to local and currently valid Mechanical InstallationVLT 2800 frequency converters allow side-by-side installation on a wall in any position as the unitsdo not require ventilation on the side.

6 Because of the need for cooling, there must be 10 cm freeair passage above and below the frequency units with enclosure IP 20 must be integrated in cabinets and panels. IP 20 is not suitable forremote mounting. In some countries, in the USA, units with enclosure NEMA 1 are approvedfor remote Quick GuideVLT 2800 Quick - VLT is a registered Danfoss trademark1 NB!With the IP 21 solution all units require a minimum of 100 mm air on each side. Thismeans that side-by-side mounting is NOT mmAaBbCDE a bF cS2 VLT 2803 - 2803 - 2822* 2840* 2805 - 2822 - 2855 - 2880 - : * Only 3-phaseDrill holes in accordance with the measurements given in the above table. Please note the differ-ence in unit all four the decoupling plate to the power cables and the earth screw (terminal 95). Motor coils (195N3110) and RFI 1B filter (195N3103)Illustration : Motor coilsVLT 2800 Quick Guide1 Quick - VLT is a registered Danfoss trademark5 1 Terminal cover The drawing below gives the dimensions for NEMA 1 terminal covers for VLT 'a' depends on the unit type.

7 IP 21 solutionTypeCode numberABCVLT 2803-2815 200-240 V,VLT 2805-2815 380-480 V195N21184780170 VLT 2822 200-240 V,VLT 2822-2840 380-480 V195N21194795170 VLT 2840 200-240 V,VLT 2822 PD2, TR1 2855-2875380-480 V195N212047145170TR1 2880-2882 380-480 V,VLT 2840 PD2195N212647205245 Table : Dimensions1 Quick GuideVLT 2800 Quick - VLT is a registered Danfoss trademark1 EMC filter for long motor cablesFilterDimensions192HA719 ABC bJKLMN7545619060162412192H4720 ABC bJKLMN9050625770162412192H4893 ABC bJKLMN140506257120162412 VLT 2800 Quick Guide1 Quick - VLT is a registered Danfoss trademark7 Electrical Electrical Installation in GeneralNB!All cabling must comply with national and local regulations on cable cross-sectionsand ambient temperature. Copper conductors required, (60-75 C) of terminal tightening (Nm)Torque, Control Cables (Nm)2803 - 2875 Power mains - - - 32880 - 2882,2840 PD2 Power mains - - 3 Table : Tightening of terminals. Power CablesNB!

8 Please note that the power terminals can be mains to the mains terminals of the frequency converter, L1, L2 and L3 and the earthconnection to terminal 95. VLT 2803 - VLT 2815 VLT 2822 - VLT 28401 Quick GuideVLT 2800 Quick - VLT is a registered Danfoss trademark1 VLT 2880 - VLT2882 Fit screened/armoured cable from the motor to the motor terminals of the frequency converter, U, V, W. The screen ends in a screen connector. Mains connection NB!Please note that at 1 x 220-240 Volt the neutral wire must be attached to terminalN (L2) and the phase wire must be connected to terminal L1 (L1). (L2)L1(L1)(L3)Mains voltage 1 x 220-240 V NL1 (L2)L1(L1)(L3)Mains voltage 3 x 220-240 V L2L1L3 voltage 3 x 380-480 V L1L2L3 connectionNB!Please check that the mains voltage fits the mains voltage of the frequency con-verter, which can be seen from the units with RFI-filters may not be connected to mains supplies in which thevoltage between phase and earth is more than 300 Volts.

9 Please note that for theIT mains and the delta earth the mains voltage can exceed 300 Volts between phaseand earth. Units with type code R5 (IT mains) can be connected to mains supplieswith up to 400 V between phase and Technical data for correct dimensioning of cable cross-section. See also the section entitledGalvanic isolation in the Operating Instructions for further details. VLT 2800 Quick Guide1 Quick - VLT is a registered Danfoss trademark9 Motor connection Connect the motor to terminals 96, 97, 98. Connect earth to terminal Technical data for correct dimensioning of cable types of three-phase asynchronous standard motors can be connected to a frequency con-verter. Normally, small motors are star-connected (230/400 V, / Y).NB!In motors without phase insulation paper, an LC filter should be fitted on the outputof the frequency factory setting is for clockwise direction of rotation can be changed by switching two phases on the motor terminals. Parallel connection of motors The frequency converter is able to control several motors connected in consult the Operating Instructions for further !

10 Be aware that the total cable length, listed in the section EMC !Parameter 107 Automatic motor adaption, AMT cannot be used when motors areconnected in parallel. Parameter 101 Torque characteristic must be set to Specialmotor characteristics [8] when motors are connected in parallel. 1 Quick GuideVLT 2800 Quick - VLT is a registered Danfoss trademark1 Motor Cables See General Specifications for correct dimensioning of motor cable cross-section and length. SeeEMC Emissions for relationship between length and EMC comply with national and local regulations on cable !If an unscreened/unarmoured cable is used, some EMC requirements are not com-plied with, see EMC test results in the Design the EMC specifications regarding emission are to be complied with, the motor cable must bescreened/armoured, unless otherwise stated for the RFI filter in question. It is important to keepthe motor cable as short as possible so as to reduce the noise level and leakage currents to aminimum.