Example: quiz answers

Zelio Timing relays - Steven Engineering

Zelio . Timing relays Catalog 2010. Courtesy of Steven Engineering , Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) Courtesy of Steven Engineering , Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) Contents Zelio Timing relays b Selection 4. b 6. b page 6 and 7. b page 8 and 9. b page 10 to 15. b Catalog page 16 to 25. b Dimensions and page 26 to 36. For user guides and instruction sheets, visit Telemecanique and Zelio are registered trademarks of Schneider Electric. Other trademarks used herein are the property of their respective owners. 3. Courtesy of Steven Engineering , Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) Selection guide Zelio Timing relays Applications Zelio Timing relays enable simple automation cycles to be set up using wired logic.

4 Applications Zelio timing relays enable simple automation cycles to be set up using wired logic. They can also be used to complement the functions of PLCs.

Tags:

  Early, Timing, Zelio, Zelio timing relays

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Zelio Timing relays - Steven Engineering

1 Zelio . Timing relays Catalog 2010. Courtesy of Steven Engineering , Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) Courtesy of Steven Engineering , Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) Contents Zelio Timing relays b Selection 4. b 6. b page 6 and 7. b page 8 and 9. b page 10 to 15. b Catalog page 16 to 25. b Dimensions and page 26 to 36. For user guides and instruction sheets, visit Telemecanique and Zelio are registered trademarks of Schneider Electric. Other trademarks used herein are the property of their respective owners. 3. Courtesy of Steven Engineering , Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) Selection guide Zelio Timing relays Applications Zelio Timing relays enable simple automation cycles to be set up using wired logic.

2 They can also be used to complement the functions of PLCs. Output Solid state Relay Timing relays with solid state output Relay outputs provide isolation between the reduce the amount of wiring supply circuit and the output. required (wired in series). The It is possible to have several output circuits. durability of these Timing relays is independent of the number of operating cycles. Type Modular Industrial Modular Industrial Time ranges v 7 ranges: v 1 or 2 ranges Depending on Depending on model: 1 s, depending on model: v 4 ranges: 10 s, model: v 6 ranges s, 1 min, 10 s, 1 s, s, 10 min, 30 s, 10 s, 20 s, 1 h, 300 s, 1 min, 160 s 10 h, 60 min 10 min, v 7 ranges: 100 h 1 h, 1 s, 10 h 10 s, v 7 ranges: 1 min, 1 s, 10 min, 10 s, 1 h, 1 min, 10 h, 10 min, 100 h 1 h, v 7 ranges: 10 h, 1 s, 100 h 3 s, 10 s, 30 s, 100 s, 300 s, 10 min v 10 ranges: 1 s, 3 s, 10 s, 30 s, 100 s, 300 s, 30 min, 300 min, 30 h, 300 h Relay type RE11 Lppp RE9 RE11 Rppp RE88865ppp RE7.

3 See pages 16, 26 17, 28 16, 26 18 ,19, 32, 28. 4. Courtesy of Steven Engineering , Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) Zelio Timing relays enable simple automation cycles to be set up using wired logic. They can also be used to complement the functions of PLCs. Relay Relay outputs provide isolation between the supply circuit and the output. It is possible to have several output circuits. Optimum Plug-in Panel mounted Universal Miniature Analog v 1 range depending on model: v 7 ranges: v 7 ranges: 14 ranges: s, 1 s, 1 s, s, 3 s, 10 s, 1 10 s, 3 s, 10 s, 1 min, 1 min, 12 s, 30 s, 10 min, 1 10 min, 30 s, 300 s, 1 h, 1 h, 120 s, 30 min 10 h, 1 10 h, 300 s, 100 h 10 100 h 12 min, 30 min, 120 min, 300 min, 12 h, 30 h, 120 h, 300 h RE8 RE88867ppp REXLpTMpp RE48 Appp 20, 28 21 , 22, 34 23, 33 24, 35.

4 5. Courtesy of Steven Engineering , Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) Introduction Zelio Timing relays Introduction A Timing relay is a component which is designed to time events in industrial DIN rail mounted relays automation systems by closing or opening contacts before, during, or after a set Timing period. There are two main families of Timing relays : b DIN rail mounted relays (RE7, RE8, RE9, RE11, REXL ) designed for mounting on DIN rails in an enclosure, b Panel-mounted relays type RE48A designed for mounting on the front of a panel to give users easy access to the settings. These relays have one, two, or four outputs. Sometimes the second output can be timed or instantaneous. RE11 RE7, RE8, RE9 REXL If the power is switched off during the Timing period, the relay reverts to its initial position.

5 Application examples: Panel mounted relays b opening automatic doors, b alarm, b lighting in toilets, b car park barriers RE48A. Definitions b Relay output: This is the most common type of output. When the relay is energized, the moving armature is attracted by the coil and so actuates the contacts, which change state. When the relay is de-energized, both the armature and the contacts revert to their initial position. This type of output allows isolation between the supply and the output. There are three types of outputs: v C/O: changeover contact. When the relay is de-energized, the circuit N/C. C. between the common point C and N/C is closed. When the relay is N/O. operating (coil energized), the circuit between the common point C and N/O is closed. v N/C: a contact that is closed without being actuated is called a N/C. Normally Closed (N/C) contact.

6 N/O. v N/O: a contact that closes when actuated is called a Normally Open (N/O) contact. b Solid state output: These outputs are entirely electronic and involve no moving parts; service life is therefore increased. b Breaking capacity: The current value that a contact is capable of breaking in specified conditions. b Mechanical durability: The number of mechanical operating cycles of the contact or contacts. b Minimum switching capacity (or minimum breaking capacity): The minimum required current which can flow through the contacts of a relay. b G (Gate) Input: Gate input allows Timing in progress to be interrupted without resetting it. 6. Courtesy of Steven Engineering , Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) Definitions (continued) Zelio Timing relays Definitions (continued). Functions Timing functions are identified by letters.

7 Main Timing Complementary Definitions functions functions (1). A (2) Delay on energization Ac Timing after closing and opening of control contact Ad Timing on closing of control contact Ah Flashing single cycle by operation of control contact Ak Asymmetrical On-delay and Off-delay with external control At Delay on energization with memory Aw Off-delay on energization or on opening of control contact B (2) Timing on impulse, one shot Bw Pulse output (width adjustable). C (2) Timing after opening of control contact D (2) Symmetrical flashing, start with output in rest position Di (2) Symmetrical flashing, start with output in operating position H (2) Timing on energization He Pulse-on de-energization Ht Timing on energization with memory K Delay on de-energization (without auxiliary supply). L (2) Asymmetrical flashing, start with output in rest position Li (2) Asymmetrical flashing, start with output in operating position Lt Asymmetrical flashing with partial stop of Timing N Safeguard O Delayed safeguard P Delayed fixed-length pulse Pt Impulse counter (On-delay).

8 Qc Star-delta Timing Qe Star-delta Timing Qg Star-delta Timing Qt Star-delta Timing T Bistable relay Tt Timed impulse relay W On-delay after opening of control contact (1) Complementary functions enhance the main Timing functions. Example: Ac: Timing after closing and opening of control contact. (2) The most commonly used Timing functions. 7. Courtesy of Steven Engineering , Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) Selection Zelio Timing relays Selection table Selection criteria b Functions (On-delay or Off-delay, counter, flashing). b Supply voltage (example: a/c 12 240 V). b Timing range for a Timing relay (example: s 100 h). b Type of output (contact or solid state) and required Number of contacts. b Breaking capacity or Rated current of contacts, expressed in amperes. This is the maximum current which may flow through the contacts.

9 Functions Timing Supply Type of Rated Relay range voltage output current A s 100 h c 12 V 2 C/O contacts 5A REXL2 TMJD. 4 C/O contacts 3A REXL4 TMJD. s 100 h c 24 V 2 C/O contacts 5A REXL2 TMBD. 4 C/O contacts 3A REXL4 TMBD. s 100 h a 24 V 2 C/O contacts 5A REXL2 TMB7. 4 C/O contacts 3A REXL4 TMB7. s 100 h a 120 V 2 C/O contacts 5A REXL2 TMF7. 4 C/O contacts 3A REXL4 TMF7. s 100 h a 230 V 2 C/O contacts 5A REXL2 TMP7. 4 C/O contacts 3A REXL4 TMP7. 10 s a/c 24 240 V 1 solid state output A RE9TA11MW. 30 s A RE9TA31MW. 3 300 s A RE9TA21MW. 40 s 60 min A RE9TA51MW. 1 s 100 h A RE11 LAMW. s 300 h 2 timed C/O contacts 5 A RE48 ATM12MW. s 300 h a/c 24 V, a 110 240 V 1 C/O contact 8A RE7TL11BU. 3 s 8A RE8TA61 BUTQ. 10 s 8A RE8TA11 BUTQ. 30 s 8A RE8TA31 BUTQ. 3 s 300 s 8A RE8TA21 BUTQ. 20 30 min 8A RE8TA41 BUTQ. s 300 h a/c 24 V, a 110 240 V, 2 C/O contacts 8A RE7TP13BU.

10 A/c 42 48 V. A, Ac, At, B, Bw, C, D, Di, H, Ht 1 s 100 h a 24 240 V 1 solid state output A RE11 LMBM. 1 s 100 h a/c 12 V 1 C/O contact 8A RE11 RMJU. 1 s 100 h a/c 12 240 V 1 C/O contact 8A RE11 RMMW. 8A RE11 RMMWS. 1 s 100 h c 24 V, a 24 240 V 1 C/O contact 8A RE11 RMMU. A, At 1 s 100 h c 24 V, a 24 240 V 1 C/O contact 8A RE11 RAMU. A, At, Aw s 300 h a 110 240 V, a/c 24 V, 1 C/O contact 8A RE7TM11BU. a/c 42 48 V. A, At, B, C, D, Di, H, Ht 1 s 10 h c 24 V, a 24 240 V 1 C/O contact 5A RE11 RMEMU. A, B, C, Di s 300 h a/c 24 240 V 2 C/O contacts 5A RE48 AML12MW. A, C, D, Di, H, Qg, Qt, W s 300 h a 110 240 V, a/c 24 V, 2 C/O contacts 8A RE7MY13BU. a/c 42 48 V. s 300 h a/c 24 240 V 2 C/O contacts 8A RE7MY13MW. A, C, D, Di, H, W s 300 h a 110 240 V, a/c 24 V, 1 C/O contact 8A RE7ML11BU. a/c 42 48 V. A, D, Di, H 10 s and 3 300 s a/c 24 240 V 1 solid state output A RE9MS21MW.