CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES

CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURESSECTION provisions of this CHAPTER shall govern thematerials, systems and assemblies used for structuralfire resis-tanceand fire-resistance-rated construction separation of adja-cent spaces to safeguard against the spread of fire and smokewithin a building and the spread of fire to or from following words and terms shall, for thepurposes of this CHAPTER , and as used elsewhere in this code,have the meanings shown opening around the fundamental component of build-ing construction, listed in Table 601, which may or may not beof fire-resistance-rated construction and is constructed ofmaterials based on the building type of RADIATION installedin a ceiling membrane of a fire-resistance-rated floor/ceiling orroof/ceiling assembly to limit automatically the radiative heattransfer through an air inlet/outlet FIRE/ SMOKE installed in ducts and air transfer openings designed toclose automatically upon the detection of heat and resist thepassage of flame and SMOKE .

CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 701 GENERAL 701.1 Scope. The provisions of this chapter shall govern the materials ...

Tags:

  7 fire and smoke protection features

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES

1 CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURESSECTION provisions of this CHAPTER shall govern thematerials, systems and assemblies used for structuralfire resis-tanceand fire-resistance-rated construction separation of adja-cent spaces to safeguard against the spread of fire and smokewithin a building and the spread of fire to or from following words and terms shall, for thepurposes of this CHAPTER , and as used elsewhere in this code,have the meanings shown opening around the fundamental component of build-ing construction, listed in Table 601, which may or may not beof fire-resistance-rated construction and is constructed ofmaterials based on the building type of RADIATION installedin a ceiling membrane of a fire-resistance-rated floor/ceiling orroof/ceiling assembly to limit automatically the radiative heattransfer through an air inlet/outlet FIRE/ SMOKE installed in ducts and air transfer openings designed toclose automatically upon the detection of heat and resist thepassage of flame and SMOKE .

2 The device is installed to operateautomatically, controlled by a SMOKE detection system, andwhere required, is capable of being positioned from a fire com-mand Ceiling radiation damper, Combinationfire/ SMOKE damper, Fire damper and SMOKE damper. material, device or construction installed torestrict the movement of air within open spaces of concealedareas of building components such as crawl spaces, floor/ceil-ing assemblies, roof/ceiling assemblies time period that thethrough-penetrationfirestop systemlimits the spread of fire through the penetrationwhen tested in accordance with ASTM E 814 or UL fire-resistance-rated wall assembly ofmaterials designed to restrict the spread of fire in which conti-nuity is installed in ducts and airtransfer openings designed to close automatically upon detec-tion of heat and resist the passage of dampersareclassified for use in either static systems that will automaticallyshut down in the event of a fire, or in dynamic systems that con-tinue to operate during a fire.

3 A dynamicfire damperis testedand rated for closure under elevated temperature door component of afire DOOR combination of afire door,frame, hardware and other accessories that together provide aspecific degree of fire PROTECTION to the vertical assembly of materialsdesigned to restrict the spread of fire in which openings are PROTECTION period of time that anopening protective will maintain the ability to confine a fire asdetermined by tests prescribed in Section 715. Ratings arestated in hours or property of materials or theirassemblies that prevents or retards the passage of excessiveheat, hot gases or flames under conditions of period of time a build-ing element, component or assembly maintains the ability toconfineafire, continues to perform a given structural function,or both, as determined by the tests, or the methods based ontests, prescribed in Section JOINT assemblage ofspecific materials or products that are designed, tested andfire-resistance rated in accordance with either ASTM E 1966 orUL 2079 to resist for a prescribed period of time the passage offire through joints made in or between SEPARATION distance measuredfrom the building face to one of the following:1.

4 The closest interiorlot line;2. To the centerline of a street, an alley or public way; or3. To an imaginary line between two buildings on the distance shall be measured at right angles from the faceof the fire-resistance-rated wall having protectedopenings, which restricts the spread of fire and extends contin-uously from the foundation to or through the roof, with suffi-cient structural stability under fire conditions to allow collapseof construction on either side without collapse of the WINDOW window constructed andglazed to give PROTECTION against the passage of materials or materials approvedfor use as fireblocking, installed to resist the free passage offlame to other areas of the building through concealed FIRE DOOR combination of afiredoor, a frame, hardware and other accessories installed in a hor-izontal plane, which together provide a specific degree of fireprotection to a through-opening in a fire-resistance-rated floor(see Section ).

5 2010 FLORIDA BUILDING CODE fire-resistance-rated flooror roof assembly of materials designed to restrict the spread offire in which continuity is linear opening in or between adjacent fire-resis-tance-rated assemblies that is designed to allow independentmovement of the building in any plane caused by thermal, windor any other opening made throughone side (wall, floor or ceiling membrane) of an material,device or construction installed to resist for a prescribed timeperiod the passage of flame and heat through openings in a pro-tective membrane in order to accommodate cables, cable trays,conduit, tubing, pipes or similar composed principally of fibersmanufactured from rock, slag or glass, with or without vitreous fiber insulation madeby melting predominately igneous rock or furnace slag, andother inorganic materials, and then physically forming the meltinto through-penetrationfirestop or amembrane-penetration applied to afire dooror other openingprotective, means equipped with an device that will ensureclosing after having been enclosed space extending through one or morestoriesof a building, connecting vertical openings in succes-sive floors.

6 Or floors and walls or construction formingthe boundaries of a continuous membrane, either verticalor horizontal, such as a wall, floor or ceiling assembly, that isdesigned and constructed to restrict the movement of space within a buildingenclosed bysmoke barrierson all sides, including the top installed in ducts and airtransfer openings designed to resist the passage of SMOKE . Thedevice is installed to operate automatically, controlled by asmoke detection system, and where required, is capable ofbeing positioned from a fire command result of a factory and/or field method of joiningor connecting two or more lengths of afire-resistant joint sys-teminto a continuous time period that the penetration firestop sys-tem, including the penetrating item, limits the maximum tem-perature rise to 325 F (163 C) above its initial temperaturethrough the penetration on the nonfire side when tested inaccordance with ASTM E 814 or UL opening that passesthrough an entire FIRESTOP of specific materials or products that are designed,tested and fire-resistance rated to resist for a prescribed periodof time the spread of firethrough penetrations.

7 The F and Trating criteria for penetration firestop systems shall be in accor-dance with ASTM E 814 or UL 1479. See definitions of F rat-ing and T rating. SECTION 703 FIRE-RESISTANCE RATINGS AND FIRE prescribed herein forfire resistanceshall conform to the requirements of this Fire-resistance ratingofbuilding elements, components or assemblies shall be deter-mined in accordance with the test procedures set forth inASTM E 119 or UL 263 or in accordance with Section materials, systems or devices that have not been testedas part of a fire-resistance-rated assembly are incorporated intothe building element, component or assembly, sufficient datashall be made available to thebuilding officialto show that therequiredfire-resistance ratingis not reduced. Materials andmethodsofconstructionused to protect joints and penetrationsin fire-resistance-rated building elements, components orassemblies shall not reduce the requiredfire-resistance :In determining thefire-resistance ratingofexterior bearing walls, compliance with the ASTM E 119 orUL 263 criteria for unexposed surface temperature rise andignition of cotton waste due to passage of flame or gases isrequired only for a period of time corresponding to therequiredfire-resistance ratingof an exterior nonbearingwall with the samefire separation distance, and in a build-ing of the same group.

8 When thefire-resistance ratingdetermined in accordance with this exception exceeds thefire-resistance ratingdetermined in accordance with ASTME 119 or UL 263, the fire exposure time period, water pres-sure and application duration criteria for the hose stream testof ASTM E 119 or UL 263 shall be based upon thefire-resistance ratingdetermined in accordance with Nonsymmetrical wall wallsand partitions of nonsymmetrical construction shall betested with both faces exposed to the furnace, and theassignedfire-resistance ratingshall be the shortest durationobtained from the two tests conducted in compliance withASTM E 119 or UL 263. When evidence is furnished toshow that the wall was tested with the least fire-resistant sideexposed to the furnace, subject to acceptance of thebuildingofficial, the wall need not be subjected to tests from theopposite side (see Section forexterior walls).

9 Combustible aggre-gates are permitted in gypsum and portland cement concretemixtures for fire-resistance-rated construction. Any compo-nent material or admixture is permitted in assemblies if theresulting tested assembly meets the fire-resistance testrequirements of this Restrained tested under ASTM E 119 or UL 263 shall not beconsidered to be restrained unless evidence satisfactory tothebuilding officialis furnished by theregistered designprofessionalshowing that the construction qualifies for FLORIDA BUILDING CODE BUILDINGFIRE AND SMOKE PROTECTION FEATURES restrained classification in accordance with ASTM E 119 orUL 263. Restrained construction shall be identified on Alternative methods for determining fire application of any of the alternative methods listed in thissection shall be based on the fire exposure and acceptance crite-ria specified in ASTM E 119 or UL 263.

10 The requiredfire resis-tanceof a building element, component or assembly shall bepermitted to be established by any of the following methods orprocedures:1. Fire-resistance designs documented in Prescriptive designs of fire-resistance-rated buildingelements, components or assemblies as prescribed inSection Calculations in accordance with Section Engineering analysis based on a comparison of buildingelement, component or assemblies designs havingfire-resistance ratingsas determined by the test proce-dures set forth in ASTM E 119 or UL Alternative PROTECTION methods as allowed by Noncombustibility tests indicated in and shall serve as criteria for acceptance ofbuilding materials as set forth in Sections , in Type I, II, III and IV construction. The term noncombustible does not apply to the flame spread charac-teristics ofinterior finishortrimmaterials.